![Fancom LM.60i Скачать руководство пользователя страница 20](http://html1.mh-extra.com/html/fancom/lm-60i/lm-60i_manual_3349743020.webp)
LM.60i
8. Control
A5911664 - GB 100503
16
8.
Control
8.1.
The LM.60i as IO-network module
8.1.1. Addressing
In a single IO-network all the IO-network modules must have a unique
address (1..31).
Set an address using dipswitches 1 thru 5
This address is also set on the control computer used to
control the LM.60i
See appendix 1 for an overview of the addresses
8.1.2. Temperature measurement
As IO-network module the LM.60i can measure the temperature itself. This
value can be used by the control computer, or to control independently in
the case of an emergency.
To enable the analog input to be used for a
temperature sensor, the jumpers of JP1 must be set
to the Temp position.
To activate temperature measurement, set dipswitch
6 to OFF.
1
2 3
4 5
6
7
8
Temp
.
1
2 3
4 5
6
7 8
ON
Содержание LM.60i
Страница 1: ...LM 60i Manual GB...
Страница 34: ...LM 60i Appendix 3 A5911664 GB 100503 30 Appendix 3 Mountings...
Страница 35: ...LM 60i Appendix 3 A5911664 GB 100503 31 1 Mounting cable reel...
Страница 37: ...LM 60i Appendix 3 A5911664 GB 100503 33 3 Mounting CE protection cover on cable reel...
Страница 38: ...LM 60i Appendix 3 A5911664 GB 100503 34 4 Mounting pipe chain coupling 1...