Installation Manual Essentials 120213 
 

11 

 

the dampers are already stroking.  This will depend on the outdoor setting and the outdoor 
temperature. 

Depending on the present outdoor temperature turning the outdoor thermostat will either 
open or close the dampers.  Turn the setting dial to actuate the system for both open and 
closed conditions.  Verify status on LEDs.  Once this is verified go ahead and set the outdoor 
thermostat to the setting desired by the occupant.  FAMCO recommends 70 – 72 degrees. 

Unless you are installing optional equipment, you are done with installation.   

IMPORTANT:  

If you are installing optional devices these devices should also be tested for 

proper operation.  Testing these devices can be done in a manner similar to testing the outside 
air thermostat. 

ALWAYS follow equipment manufacturers testing and operation instructions.

 

Information about installing auxiliary devices can be found below.  Install diagrams can be 
downloaded at famcoiaq.com/manuals. 

 

TROUBLESHOOTING 

If the system is powered, and does not open the damper box as expected, there are four items 
that should be checked: 

1)

 

IAQ Economizer switch may be OFF. 

2)

 

LIMIT Switch is OPEN or no jumper is installed. 

3)

 

Outdoor thermostat setting requirements have not been met. (Not cool enough 
outside.) 

4)

 

There is no call for cooling.  Either the existing HVAC system thermostat must be calling 
for cooling, or an Indoor Low Limit thermostat installed with the economizer must be 
calling for cooling. 

The OVRD switch overrides both the outdoor thermostat and the call for cooling.  If the system 
does not function properly while using the OVRD switch the likely cause is the LIMIT not being 
installed or satisfied. 

If the damper indicator light is showing a RED – DAMPER light after 90 seconds this means that 
the damper is either 1) Not moving, or 2) Not being detected in the proper position.  If the RED 
– DAMPER light does not go out, visually inspect the damper box to see if it is operating 
properly.  If the damper is stroking, but not being detected in the proper condition you will 
need to remove the cover, (bulge in insulation on side of box,) and adjust the clamp on the 
damper shaft.  After adjustment, test operation several times to make sure OPEN and CLOSED 
lights are indicating properly. 

Содержание ECONOMIZER BREATHE SMARTER

Страница 1: ...Installation Manual Essentials 120213 BREATHE SMARTER TM PATENT PENDING...

Страница 2: ...g HVAC system is functioning properly before beginning installation 4 Place damper box in the location where it will be installed 5 Install outside air intake louver transition and connect flex duct t...

Страница 3: ...TANT Turn off the HVAC system at the breaker box before beginning installation Do not use the existing furnace transformer to power the IAQ Economizer The furnace transformer is not sized to support p...

Страница 4: ...CAN BE EASILY ACCESSED BY OCCUPANT OUTSIDE AIR TEMPERATURE THERMOSTAT EXISTING FURNACE BOARD OUTSIDE AIR FLEX DUCTWORK ADDED NOT PROVIDED IN KIT IMPORTANT MINIMIZING TURNS AND BENDS IN DUCTWORK IS CRI...

Страница 5: ...duct from the intake transition to the FRESH AIR port on the Damper Box Cut the main return duct in a location that will allow re connection to the damper box The damper box will replace a section of...

Страница 6: ...VAC only Other sources of power will damage the unit DO NOT power the unit with power from the AC unit The furnace transformer will not have sufficient capacity to provide for the IAQ Economizer Provi...

Страница 7: ...T cable are terminated correctly before plugging it into the Logic Box Connect the Power Cable to the Logic Box IMPORTANT There is one auxiliary connection that is required for the Logic Box to functi...

Страница 8: ...Step 1 2 2 efore Furnace Board After To Logic Box To Thermostat Condensing Unit Yellow Yellow Green Green White Red Condensing Unit Yellow Green Red White To Thermostat Condensing Unit Yellow Yellow...

Страница 9: ...Installation Manual Essentials 120213 8 STEP 3 Plug the other end of the furnace cable into the logic box connection marked FURNACE...

Страница 10: ...Installation Manual Essentials 120213 9 3 GANG OR SURFACE MOUNT OPTIONS FIGURE 3 3 GANG FLUSH SURFACE E SET SCREW...

Страница 11: ...use the Override OVRD switch to initiate an air introduction If the Yellow light went out before you switched the OVRD switch and the Red light lit wait 90 seconds The Green light should light indicat...

Страница 12: ...pen the damper box as expected there are four items that should be checked 1 IAQ Economizer switch may be OFF 2 LIMIT Switch is OPEN or no jumper is installed 3 Outdoor thermostat setting requirements...

Страница 13: ...Installation Manual Essentials 120213 12 All components of the IAQ Economizer are tested before shipping...

Страница 14: ...NSFORMER CAPACITY IS 50VA LOGIC BOX TRANSFORMER TYPICALLY CONSUME LESS THAN 20VA DEVICES USING PWR OUT CANNOT EXCEED 50VA TOTAL TRANSFORMER CAPACITY EXTERNAL DEVICES PROVIDING A POWERED SIGNAL TO THE...

Страница 15: ...using AUX START 1 Typical Uses Outdoor air low or high limit outdoor humidity or dew point limit Multiple devices need to be wired in series T2 Input used to allow a different setpoint to call for ec...

Страница 16: ...ction is allowed Multiple devices need to be wired in parallel POWER Power simply provides 24 VAC that can be used to power other control devices used with the system The top terminal is 24VAC the bot...

Страница 17: ...Installation Manual Essentials 120213 16 AUXILLIARY CONNECTIONS FIGURE 5 LIMIT T2 EXT START 2 PWR OUT HRV INTRUPT EXT START 1 13 NOT USED 12 COMMON 11 ECON SIG 10 COMMON 9 24VAC 8 7 6 5 4 3 2 1...

Страница 18: ...LIMIT CONDITIONS MET SYSTEM ON STAT CALLING EXT START 2 ON DAMPER CORRECT OPEN DAMPER S FAN ON COMPRESSOR ON YES YES YES YES YES YES YES NON ECON SUPPORTED COOL CALL YES ERROR INDICATION NO DAMPER PO...

Отзывы: