![Falcon SG5K-1TX Скачать руководство пользователя страница 30](http://html1.mh-extra.com/html/falcon/sg5k-1tx/sg5k-1tx_owners-operating-manual_540246030.webp)
SG Series
TM
UPS PLUS
®
5-6kVA MODELS
28
Electrical Input
Nominal AC Voltage
120V
230V
230V
120V
230V
230V
AC Voltage Range
87-140V
170-275V
170-275V
87-140V
170-275V
170-275V
Current-Amps
38.7
20.3
19.5
46.6
24.3
23.4
Frequency
50/60 Hz
±
5%
Efficiency (Typical)
> 79%
> 82%
> 79%
> 82%
Power Factor Correction
> 0.95
Electrical Output
Watts
3500
4200
AC Voltage
(Switchable except where noted)
120 & 208V or
120 & 220V or
120 & 240V
(No Switching)
(1)
120V
(1)
(1)
208V
220V
230V
240V
208V
220V
230V
240V
120 & 208V or
120 & 220V or
120 & 240V
(No Switching
)
(1)
120V
(1)
(1)
208V
220V
230V
240V
208V
220V
230V
240V
Isolation Transformer
No
Yes
No
No
No
Yes
No
No
Frequency
60Hz
50/60Hz
50/60Hz
50/60Hz
60Hz
50/60Hz
50/60Hz
50/60Hz
Voltage Regulation
±
4%
±
3%
±
4%
±
3%
Frequency Stability
±
0.3% (Battery Mode)
Step Load Change
±
7% for 100% load variation
THD – Linear Loads
< 3%
THD – Non-Linear Loads
< 7%
<5%
< 7%
<5%
Overload
105% for 50 Seconds
Crest Ratio
3:1
(1) Contact the factory for output settings.
.
Battery
DC Voltage
240V
Type
12V, 7AH Sealed Lead Acid Maintenance-Free
Back Up Time @ Full Load
@ 1/2 Load
9 Minutes
28 Minutes
7 Minutes
18 Minutes
Recharge Time
10 Hours to 90%
Battery times are approximate.
Electrical Connections Input
-1TX
Hardwire
Hardwire
-1TXC
L5-50P
-2T
Hardwire
Hardwire
-2TC
L6-30P
L6-30P
-2TX
Hardwire
Hardwire
-2TXC
L6-30P
L6-30P
Electrical Connections Output
-1TX
Hardwire
Hardwire
-1TXC
(2) duplex
5-20R &
(1) L6-30R
-2T
Hardwire
Hardwire
-2TC
(1) L6-30R
(1) L6-30R
-2TX
Hardwire
Hardwire
-2TXC
(2) duplex
5-20R &
(1) L6 -30R
(2) duplex
5-20R &
(1) L6-30R
Contact the factory for other input/output options.
Environmental
Operating Temperature
0º C to 35º C (32º F to 95º F)
Humidity
10% to 95% Non – Condensing
Altitude
7,000 Feet
Cooling
Low Velocity Forced Air Fans
Audible Noise @ 1 Meter
< 55dBA
Controls and Indicators
LED
Line, Inverter, Battery Reserve, Load, Bypass, Alarm, Crest, Battery & Load Capacity Level
Audible Alarms
DC Mode, Low Battery, Over/Under Voltage, Over/Under Frequency, High Temp., Over Load, Fault Alarm
Communications
RS-232 Serial Port (Bundled UPSilon 2000 Software)
Mechanical
Dimensions H x W x D i nches
(mm)
Hardwired Models
Receptacle Models
32.1 x 10.2 x 21.8 (815.3 x 259.0 x 553.7)
32.1 x 10.2 x 27.0 (815.3 x 259.0 x 685.8)
Weight lb. (kg)
T
TX
TC
TXC
216 (98)
299 (136)
239 (108)
322 (146)
Agency Listing
UL1778, CUL,
FCC Class A
-2T: UL1778, CUL, FCC Class A, CE
All others:
UL1778, CUL, FCC Class A
UL1778, CUL,
FCC Class A
-2T: UL1778, CUL, FCC Class A, CE
All other s:
UL1778, CUL, FCC Class A
Model Number
SG5K -1TX & -
-1TXC
SG5K -2TX &
-2TXC
SG5K -2T
& -2TC
SG6K-1TX
SG6K-2TX &
-2TXC
SG6K-2T
& -2TC
Nominal VA
5000
5000
5000
6000
6000
6000
A
vailable Options: Extended Run Time Battery Packs, Make-Before-Break Maintenance Bypass, SNMP/HTTP Network Card,
Frequency & Voltage Conversion.
©
2004 Falcon
®
Electric, Inc. All rights reserved. Falcon
®
and the Falcon Electric logo are registered trademarks of Falcon Electric, Inc.
All other brand names and trademarks are the property of their respective owners.
The information and specifications stated in this document are subject to change without notice.