background image

SPECIFICATION 

MODEL 

MLP-300-1 

MLP-500-1 

Nominal Voltage 

120Vac 

Voltage Range 

80-143Vac 

Current 3.6A 

6.0A 

INPUT 

Frequency 

50/60Hz 

±

5% (auto detecting) 

VA 300 

500 

Voltage 120Vac 

 

On Line Voltage Regulation 

±

10% 

On Battery Voltage 
Regulation 

±

10% 

AVR Operation 

Buck AVR (down/up)   

Boost AVR (up/down) 

 

126/121Vac 
103/108Vac 

Power 180W 

300W 

Current 

1

 2.9A 

4.9A 

Frequency 

50/60Hz  

±

1 Hz 

Waveform 

Step Wave (modified sine wave) 

Transfer Time 

Bypass to Inverter 
Inverter to Bypass 

 

<10 ms 

<2 ms 

Surge Protection 

Metal Oxide Varistor 

OUTPUT 

Protection 

Short circuit & overload, Excessive battery discharge & overcharge 

DC Voltage 

12Vdc 

Type 

12V, 5AH, HC1221W 

Recharge Time to 90% 

8 Hours 

BATTERY 

Run time 100% 
                 50% 

4.2min. typ. 
 21min. typ. 

3.4 min. typ. 
9.6 min. typ. 

Buck and Boost with Auto Voltage Regulator 

Fax/Modem Surge Protection 

DC Cold Start  

FEATURES 

Special 

Green Mode Operation 

Audible 

Alarms 

On Battery (6 sec. intervals) 

Low Battery (1 sec. Intervals) 

Overload (continuous) 

Indicators 

L.E.D. 

AC Normal – Green 

On Battery – Orange 

Battery Defective, Overcharging, Low Cut-off - Red 

Control 

Type Microprocessor 
Computer True 

RS-232 

Interface 

Options 

USB Converter cable, UPSILON shutdown & management software 

Temperature 

0

°

C - 40

°

C (32

°

F – 104

°

F) 

Humidity 

10% - 90% Non-condensing 

Environment 

Max. Altitude 

5000 feet (1500 meters) 

Input Cord  

6 Foot Cord with 5-15P 

Output Receptacles  

(2) NEMA 5-15R 

Weight 

15.4 lbs.  (7kg) 

Mechanical 

Dimensions                  (mm) 
H x W x D                   inches 

(180 x 78 x 320) 

7.09 x 3.07 x 12.6 

Approvals 

Agency 

UL, FCC Class A 

1 Computer load. 

Backup times are for reference only. Actual duration may vary depending on temperature, battery condition and type of load. 

3. Models are available with a contact closure computer interface. For these models add a “C” to the end of the desired model number. 

 
 
 
 
 
 
 
 
 