Installation & User Manual Falcon Electric, Inc.
FN2 Series OM480051 Rev.: C 8
Operating Conditions
The UPS must be installed in a clean, temperature controlled, indoor environment, free from
moisture, flammable gasses, fumes, corrosive substances and conductive contaminants.
Avoid direct sunlight.
Do not install the UPS in a flammable or otherwise hazardous environment.
Avoid vibration and areas subject to physical impact.
To prevent overheating, keep all ventilation openings free from obstruction. Keep the UPS rear
panel at least 12 inches away from the wall or other obstructions.
Temperature:
•
Operating Temperature Range: 0°C to 40°C (32°F to 104°F)
Humidity:
•
10% to 90% relative humidity, non-condensing
Altitude:
•
3280 ft (1000 m)