Clean all pipelines to remove dirt and scale before installation. Apply

a minimum amount of pipe compound to the male threads of the

fitting only.  

Do Not use teflon tape as a sealant. 

 Start with the third

thread back and work away from the end of the fitting to avoid

contaminating the transducer.  Install the transducer in the air line.

The inlet and outlet ports are labeled on the ends of the transducer.

Tighten connections securely.  Avoid undersized fittings that will limit

the flow through the transducer and cause pressure drop down

stream.

Electric Connection

Make connections as shown in Figure 8.

Pneumatic Connection

NOTE:

Oil free air  is required.  Use a filter to remove dirt and

liquid in the air line ahead of the transducer.  If an air

line lubricator is used, it MUST be located down-

stream to avoid interference with transducer perfor-

mance.
The user is responsible for insuring that the environ-

ment  in  which  the  unit    will  be  installed  and  the

operating gas are compatible with the materials in the

transducer.

1.

2.

3.

Shut off the valve that is supplying air to transducer.

It is not necessary to remove the Transducer from

the air line.

Remove the Orifice Assembly from the unit.  For

detailed information see Figure 1  “T6100 Calibration

Configuration on page 1.

Clean with alcohol and dry with compressed air.

To clean the Orifice, use the following procedure:

MAINTENANCE

Parts must be completely dry before reassembling.
If the standard maintenance procedure does not

correct the trouble, install the appropriate Service

Kit below:

20781-1

Service  Kits  also  include  Gasket,  O-Rings,  and

Membranes to replace "W" Option product.

NOTES:

The  information  set

forth in the foregoing

Operation and Mainte-

nance  Instructions

shall not be modified

or amended in any re-

spect  without  prior

written  consent  of

Fairchild  Industrial

Products Company.  In

addition, the informa-

tion  set  forth  herein

shall be furnished with

each product sold in-

corporating Fairchild's

unit  as  a  component

thereof.

LEGAL NOTICE:

Figure 8.

1

TROUBLE-SHOOTING

Table 1.  

Trouble-Shooting.

Problem

Solution 

(check)

Supply Pressure

Clogged Orifice

Input Signal

Pneumatic Connections

Zero and Span Adjust

Supply Pressure Low

Output Leakage

DC Signal

Loose Wires or Connections

Liquid in Air Supply

Dirt in Magnet Gap

No Output

Leakage

Low or Improper

Span Adjust

Erratic Operation

Failure of Transducer could result in out-

put pressure increasing to supply pres-

sure possibly causing personal injury or

damage to equipment.

WARNING:

SPLIT RANGE OPERATION

All units have the capability to be split ranged or set for any

output in the range as long as the Output Span is equal to

or greater than the minimum Span.