26
tightly to the stuffing box.
The manufacturer will not be held liable for any personal or material damage to the
machine resulting from incorrect installation or failure to comply with the
manufacturer’s specifications.
4.4
Gas connection
An AUTHORISED TECHNICIAN should always carry out the gas connection of the appliance.
The general installation must have a mains tap and a pressure regulator and it is
also advisable to install a shut-off cock on each individual appliance.
A pipe of at least Ø 12 x 10 mm should be used for the gas connection, together
with a ¾” nut to connect to the Fry-Top.
4.5
Conversion to other types of gas
If the appliance is prepared for a different type of gas to the one available in the installation, you
should proceed as follows:
4.5.1 Fry-top a gas con grifo válvula
1. Disconnect the gas supply to the appliance if connected (Any change to the conditions of the
gas circuit must be carried out by an AUTHORISED TECHNICIAN)
2. Burner conversion
a. Remove the burner injectors and replace with the correct model according to the gas
to be used (Table 3).
b. Set the air control to position H (table 3) depending on the gas to be used.
3. Pilot conversion
a. Release the ignition pipe.
b. Undo the pilot unit.
c. Remove the pilot injectors and replace with the correct model according to the gas
to be used (Table 3).
d. Replace the pilot unit and the ignition pipe.
Rair