III.b  … assembling and dismantling 

Assembling and dismantling must solely be carried out with the power disconnected! 
Prior to the installation, it may be necessary that the float/s or the density module is disassembled. 

During the assembly, it must be ensured that the float/s or the module is/are mounted the right way on 

the sensor tube. 
Only for the TORRIX Ex ... with screw terminals the opening of the sensor head is provided. Further 

disassembly may damage the filling level sensor and invalidate its approval. 

III.c  … installation 

The installation must be carried out only with the power disconnected. Special rules and regulations, 

including EN 60079-14 and local installation regulations, must be observed. 
If a device is supplied with screw-in unit, the thread of the screw-in unit must be fitted with suitable 

sealing material, screwed into the existing sleeve and tightened. With a riser installation, the plastic 

centring aid is plugged onto the sensor head. Then let the sensor slide into the riser tube until it stands 

firmly on the bottom. If the filling level sensor is supplied without process connection, the installer is 

responsible for compliance with the EX-requirements. 
General information (see also EN 60079-26, section 4.3): 

If a device is installed in the boundary wall between Zone 0 and Zone 1, it must be ensured that a 

sufficiently tight gap (IP66 or IP67) is achieved after installation. 

Flexible filling level sensor (TORRIX Ex … Flex …, VISY-Stick … Flex …) 

This type can be produced with different sensor bases to serve for stabilizing the sensor. A foot can 

be a magnetic base. The magnet is then encapsulated in an electricity conducting plastic and can 

therefore be used in potentially explosive areas. 

LPG filling level sensor VISY-Stick … LPG … 

The adjustable installation kit for LPG tanks was developed to allow the sensor to be installed and 

removed at any time without any additional work and without having to open the tank. The adjustable 

installation kit for LPG tanks consists of a jacket pipe with special LPG float made of BUNA and a ¾“ 

NPT cutting ring fitting. In the case of installation with a cutting ring fitting, the position of the sensor 

can no longer be altered after the union nut has been tightened. 

Environmental sensor VISY-Stick Sump … 

This environmental sensor can be fixed with the mounting kit. 

When wiring the sensor to the associated equipment (preferably blue coloured cable), the approved 

inductance and capacitance of the associated equipment must not be exceeded. The terminals of the 

sensor must be connected to the same terminals of the isolating amplifier. 
For the level sensors with screw terminals type TORRIX Ex ... and TORRIX Ex HART ... , the terminal des-

ignation is "+" and "-". For devices with M12 connectors, the pin assignments are as follows: 

Pin 

TORRIX Ex SC … 

VISY-Stick … 

TORRIX Ex C … 

TORRIX Ex TAG … 

VISY-Stick … TLS 

TORRIX Ex RS485 … 

VISY-Stick … RS485  M12-Cable (Female) 

 

 

A (+) 

 

B (-) 

Table 1: Terminal assignment of the sensors 
 

 

Содержание VISY-Density LPG

Страница 1: ...Technical Documentation FAFNIR GmbH Schnackenburgallee 149 c 22525 Hamburg Germany T 49 40 39 82 07 0 F 49 40 390 63 39 VISY X VISY Probes Version 13 Edition 2019 02 Art no 207194...

Страница 2: ...anced Ethanol 10 3 3 5 VISY Stick N for AdBlue urea solution 11 3 3 6 VISY Stick Flex Flex Biodiesel Flex E15 12 3 3 7 VISY Stick LPG 13 3 3 8 VISY Density LPG module 13 4 Environmental sensors 14 4 1...

Страница 3: ...eturn shipment 32 7 List of figures 32 8 List of tables 32 9 Annex 33 9 1 VISY Stick 33 9 1 1 EC Declaration of Conformity 33 9 1 2 EU Type Examination Certificate 34 9 1 3 Instructions 40 9 2 VISY Re...

Страница 4: ...s tinction between liquids VISY Stick Interstitial with adjustable measuring range for monitoring the interme diate chamber in double walled tanks VISY Reed Interstitial with fixed measuring points fo...

Страница 5: ...t tank data delivery data and the various alarms signalled by the VISY Command central unit For configu ration and operation of the display module with VISY SoftView see the following technical docume...

Страница 6: ...ions must be observed in order to reduce the risk of injury electric shocks fire or damage to the equipment Do not change or modify the system or add any equipment without the prior consent of the man...

Страница 7: ...cable ducts are available at the petrol station it is possible to instead opt for the wireless tank gauging system In this case the benefit of installing the wireless system is that it does not entai...

Страница 8: ...smits pulses through the wire which generate a circular magnetic field 8 Permanent magnets 9 are used as filling level sensors which are installed in both the product float 5 and the water float 6 The...

Страница 9: ...lation with screw in unit for mounting on the tank lid 3 3 Types The following level sensors then are described VISY Stick Biodiesel E15 VISY Stick Advanced Advanced Biodiesel Advanced E15 VISY Stick...

Страница 10: ...s available for riser installation and for installation with screw in unit Figure 2 VISY Stick Biodiesel E15 Riser installation Installation with screw in unit M12 coupling 1 brown 2 white A 3 blue 4...

Страница 11: ...with 0 15 Ethanol The sensor is available for riser installation and for installation with screw in unit Figure 3 VISY Stick Advanced Installation with screw in unit and R2 reducer Riser installation...

Страница 12: ...riser installation and for installation with screw in unit Figure 4 VISY Stick Ethanol Installation with screw in unit Riser installation M12 coupling 1 brown 2 white A 3 blue 4 black B Equipotential...

Страница 13: ...sensor is available for riser installation and for in stallation with screw in unit Figure 5 VISY Stick Advanced Ethanol Dimensions in mm M12 coupling 1 brown 2 white A 3 blue 4 black B Equipotential...

Страница 14: ...t of AdBlue Figure 6 VISY Stick N for AdBlue urea solution M12 coupling 1 brown 2 white A 3 blue 4 black B Equipotential bonding connection Probe head Compression fitting cutting ring fitting G 3 8 st...

Страница 15: ...sensor installation is possible only with screw in unit Figure 7 VISY Stick Flex Probe length appr 123 47 2 43 120 Adjusting range M12 coupling 1 brown 2 white A 3 blue 4 black B Equipotential bondin...

Страница 16: ...Stick LPG 3 3 8 VISY Density LPG module See Technical Documentation VISY Density LPG Art No 350213 M12 coupling 1 brown 2 white A 3 blue 4 black B Equipotential bonding connection Probe head Cutting r...

Страница 17: ...age detection of product lines to the fuel dispensers VIMS product pipe or leakage detection of filling lines to the tanks VIMS delivery pipe The VISY Stick sensors operate according to the magnetostr...

Страница 18: ...ch detects the penetration of a liquid into the intermediate chambers of double walled tanks The sensor is available for riser installation and for installation with screw in unit Figure 9 VISY Stick...

Страница 19: ...rs of double walled tanks The reed contact indicates the penetration of a liquid into the dry space Figure 10 VISY Reed Interstitial Dry Cable length 5000 mm White marking Four 4 wire cable brown whit...

Страница 20: ...t could poten tially accumulate in the sump and is capable to distinguish between water and fuel The sensor is tamper proofed For the mounting an installation kit is available art no 910036 Figure 11...

Страница 21: ...iquids is not required The sensor detects liquids that may accumulate in the sumps The float switch is used as a pure alarm switch Figure 12 VISY Reed Sump Cable length 2000 mm Marking blue for VISY R...

Страница 22: ...ight liquid layer and gives an alarm when a con figurable threshold is reached Figure 13 VISY Stick Oil Separator Installation on the side wall of the oil separator 47 2 appr 123 Probe length M12 coup...

Страница 23: ...e probe tube otherwise they will slip down suddenly when you erect the sensors and could be damaged when striking the circlip During the installation following data of the VISY Stick sensors tanks and...

Страница 24: ...s Figure 14 VISY Stick installation with riser and screw in unit Riser installation Installation with Screw in unit Connection cable Sealing cap with cable gland Equipotential cable Riser installation...

Страница 25: ...robe tube gently onto the bottom of the tank and then lift it again to incor porate an appropriate safety distance To fix the probe tube first tighten the stuffing box and then tighten the locking scr...

Страница 26: ...pipes The VISY Stick for risers see Figure 14 is in stalled as follows 1 As shown in the figure below pull the riser installation kit art no 900111 over the probe head and adjust it to 3 or 4 inches d...

Страница 27: ...between 100 150 Ncm 6 Let the VISY Stick sensor slowly slide into the riser and place carefully on the bottom of the tank 7 Install a suitable cable gland in the sealing cap of the riser and guide the...

Страница 28: ...towards the probe head and secure then seal in the thread of the screw in unit 4 Slide the float onto the weight at the lower end of the probe 5 Feed the lower end of the probe magnetic base into the...

Страница 29: ...The device number of the new VISY Stick sensor Check the installation offset value and correct as necessary 5 2 6 Installation kit for VISY Stick Sump An installation kit art no 910036 is available fo...

Страница 30: ...ng fitting with NPT external thread for process connection and a com pression fitting with PTFE clamping ring for fixing the sensor see figure below Figure 17 Variable LPG installation kit for liquid...

Страница 31: ...the bottom of the tank mark that position on the pipe and fix the pipe 10 mm below the marking safety distance If there is no safety distance between the probe tube and the bottom of the tank the tube...

Страница 32: ...ws If not already connected plug the M12 coupler of the supplied FAFNIR connection ca ble onto the M12 connector of the probe head First tighten the union nut of the coupling by hand and then tighten...

Страница 33: ...e carried out by the installer in accordance with the nationally applicable installation regulations For this purpose the equipotential terminal of the probe head can be used 5 3 1 Voltage surge prote...

Страница 34: ...transmitted to VISY Command during configuration of the individual measuring points using the VISY Setup software application Figure 20 shows the probe distance b from the lowest point of the tank bot...

Страница 35: ...tive measuring principle 5 Figure 2 VISY Stick Biodiesel E15 7 Figure 3 VISY Stick Advanced 8 Figure 4 VISY Stick Ethanol 9 Figure 5 VISY Stick Advanced Ethanol 10 Figure 6 VISY Stick N for AdBlue ure...

Страница 36: ......

Страница 37: ......

Страница 38: ......

Страница 39: ......

Страница 40: ......

Страница 41: ......

Страница 42: ......

Страница 43: ...TAG The TORRIX Ex SC filling level sensors are connected to the VP or VPI isolating amplifier II Standards The equipment is designed in accordance with the following European standards EN 60079 0 2012...

Страница 44: ...nsured that a sufficiently tight gap IP66 or IP67 is achieved after installation Flexible filling level sensor TORRIX Ex Flex VISY Stick Flex This type can be produced with different sensor bases to s...

Страница 45: ...is maintenance free In case of a defect it must be send back to the manufacturer or one of its representations In accordance with the requirements for dielectric strength in EN 60079 11 clause 6 3 13...

Страница 46: ...PL TORRIX Ex RS485 A TORRIX Ex RS485 Flex TORRIX Ex RS485 PL TORRIX Ex TAG A TORRIX Ex TAG Flex TORRIX Ex TAG PL VISY Stick Advanced RS485 VISY Stick Flex RS485 Ex ia IIB T4 Ga Ex ia IIB T4 T3 Ga Gb...

Страница 47: ...ease consult table 3 and table 5 for the maximum temperatures depending on temperature classes and categories or equipment protection levels Typ TORRIX Ex SC bzw VISY Stick Temperature class Ta TF Cat...

Страница 48: ...C Category 1 2G or EPL Ga Gb sensor head installed in Zone 1 and sensor tube in Zone 0 T6 40 C 40 C 20 C 60 C T5 40 C 55 C T4 40 C 80 C T3 T2 T1 40 C 85 C Category 2G or EPL Gb filling level sensor c...

Страница 49: ...a 30 C 135 C 40 C 85 C Types VISY Stick TLS Ta 110 C 135 C 40 C 77 C Ta 110 C Observe EN 60079 14 40 C 85 C Types TORRIX Ex C TORRIX Ex RS485 TORRIX Ex TAG VISY Stick RS485 Ta 55 C Observe EN 60079 14...

Страница 50: ......

Страница 51: ......

Страница 52: ......

Страница 53: ......

Страница 54: ......

Страница 55: ...groups IIA IIB and IIC The approval applies to the device versions VISY Reed Interstitial Dry VISY Reed Interstitial Wet VISY Reed Sump Dispenser VISY Reed Sump Manhole III b assembling and dismantlin...

Страница 56: ...overhaul and repair The environmental sensors are generally maintenance free In case of a defect it must be send back to FAFNIR or one of his representations The unit complies with the dielectric str...

Страница 57: ...20 C 60 C Category 2 resp equipment protection level Gb environmental sensor installed in zone 1 T6 40 C 50 C T5 40 C 65 C T4 T3 T2 T1 40 C 85 C Table V Maximum temperatures of environmental sensors F...

Страница 58: ...ble ambient temperature probe head and the connection data please refer to the approvals and operating instructions With a battery powered radio transmitter all sensors can be used as wireless version...

Страница 59: ...Blank page...

Страница 60: ...FAFNIR GmbH Schnackenburgallee 149 c 22525 Hamburg Germany Tel 49 40 39 82 07 0 Fax 49 40 390 63 39 E mail info fafnir com Web www fafnir com...

Отзывы: