VAPORIX Service Dongle and VAPORIX Diagnostics
Page 10/19
4.5
Resetting alarm after rectifying error
If an alarm has been triggered at a dispenser point and the cause of the error has
been rectified, the alarm can be reset in the VAPORIX-Control unit.
1. Turn coding switch to "5" for dispenser side A or to "6" for dispenser side B.
2. Press button.
The alarm and the 72-hour time limit are reset.
3. To log out, turn coding switch to "9" and press button (yellow LED goes out)
or perform further service activities.
4.6
Checking the vapour recovery system
To ensure that hydrocarbons are no longer present during a dry calibration of the
vapour recovery system, the manually operated terminal can be used to perform
a simulation of fuel transfer. In that case the service dongle must be connected,
and the coding switch must be turned to switch position "7".
The switch position also ensures that any downstream corrective control modules
are deactivated for the duration of the service work.
Fig. 2b: Operating the VAPORIX service dongle
10
5
6
3
4
3 LED, yellow
4 LED, green
5 Coding switch
6 Button
10 LED