SEPARIX-C/-T and SEPARIX-Control CT
Page 20/37
3
Normally, the measuring transducer triggers an alarm whenever the interface sensor is in air/light
fluid, or whenever the level sensor is in fluid. For custom applications, measuring transducer config-
uration settings make it possible to invert the alarm triggering so that an alarm is triggered
whenever the interface sensor is in water or the high-level sensor is in air. In cases of doubt, check
whether the measuring transducer has been configured correctly for the application concerned.