fafnir 81 D-Ex Series Скачать руководство пользователя страница 2

 

Page 2/3 

 

FAFNIR GmbH 

  Schnackenburgallee 149 c 

  22525 Hamburg 

  Tel.: +49 / (0)40 / 39 82 07-0 

  www.fafnir.de 

  [email protected] 

 

 

When wiring the sensor to the measuring transducer (preferably blue coloured cable), the approved 
inductance and capacitance of the measuring transducer must not be exceeded. 
The sensors have a two-pole screw or plug connection or cable tail. Attention does not need to be paid 
to polarity. 
The integration of the sensors without overvoltage protection into the equipotential bonding is not 
required. For integration of the sensors with overvoltage protection into the equipotential bonding, a 
PA terminal is provided. 

III.d 

… 

adjustment 

No Ex-relevant adjustments are required for operation of the sensors. 

III.e 

… 

putting into service 

Before putting into service, all devices  must be checked for correct connection  and installation. The 
electrical supply, including the connected devices, must be checked. 

III.f 

… 

maintenance (servicing and emergency repair) 

The sensors are generally maintenance-free. In the case of a defect, this must be returned to the man-
ufacturer or one of its representatives. 
The sensors, in particular the probe tip, may be cleaned. Grease-dissolving cleansing agents can be used 
to remove any firmly clinging grease or oil residues. Sharp-edged objects are unsuitable for cleaning 
since they could damage the sensor. 
When performing an insulation test of the intrinsically safe circuit with 500 V under well-controlled con-
ditions, according to EN 60079-25, Clause 12 it is necessary to disconnect sensors with overvoltage pro-
tection  since  there  is  no  compliance  with  the  requirements  for  dielectric  strength  according  to 
EN 60079-11, Clause 6.3.13. For all other sensors, there is compliance between the intrinsically safe cir-
cuit and the chassis or, if present, other intrinsically safe circuits with 500 V

AC

IV 

Equipment marking 

Manufacturer: 

FAFNIR GmbH, 22525 Hamburg 

Type designation: 

81 D-Ex 

… or 83

 UV-

… or LS

 300 

… or SEPARIX

-T 

 

Certificate number: 

TÜV 00 ATEX 1656 X 

Ex-Kennzeichnung: 

 

 

 

 

81 D-Ex / 83 UV-

… / LS

 300 

… / SEPARIX

-T 

 

 

 

 

II 1 G 
II 1/2 G 

Ex ia IIC T4 Ga 
Ex ia IIC T4 Ga/Gb 

 

81 D-Ex U / LS 300 

…U…

 

 

 

 

II 1/2 G 

Ex ia IIC T4 Ga/Gb 

 

LS 300 

 C 

 

 

 

II 1 G 
II 1/2 G 

Ex ia IIB T4 Ga 
Ex ia IIB T4 Ga/Gb 

CE marking: 

 0044 

Technical data: 

U

i

 

 

30 V 

I

i

 

  200 mA 

P

i

 

 

1 W 

 
 

 

Отзывы: