51 52 53
4
DIP-SWITCH N° 4:
ON:
Pre- ashing
OFF:
No pre- ashing
10
DIP-SWITCH N° 10:
ON:
Flasher. Deactivated during dwell time,
automatic mode
OFF:
Flasher. Activated during dwell time,
automatic mode
External
asher:
It is possible to connect an external ashing
lamp to the bollard in addition to the
incorporated LED lights. The asher will be
on during the rising and lowering
movements and during the dwell time (if
pre-selected)
230 V - 100 W max
12
DIP-SWITCH N° 12:
ON:
Motor run time max. 90 s
OFF:
Motor run time max. 18 s
Light
on
= post down, gateway cleared
Light
off
= post up, gateway closed
Flashing
0,5 s (fast)
= post moving up
Flashing
1 s (normal)
= post moving down
With an external time clock:
2 short ashes
followed by a longer pause
Output for any possible 24 Vdc application
3
8
Accessory
Electrical connections
Dip-switches and LED status of the various functions
24 V - 3 W max.
Light indicating
bollard in motion :
24 Vdc output:
Motors:
Limit switches:
+
-
T2
DWELL TIME
1 s - 180 s
T1
MOTOR RUN TIME
1 s - 22 s
55 56
Signalling LED lights:
Output for the LED lights that are always on
blinking during the rising and lowering
movements of the post and with the post in
standing position. They go off with post in
down position.
200 mA for the accessories
51 52 53
11 12
55 56
L8 ON
= it goes off with post 1 down
L9 ON
= it goes off with post 1 up
Bollard 1
MOTOR 1
16 17 18
M1
L10 ON
= it goes off with post 2 down
L11 ON
= it goes off with post 2 up
L12 ON
= it goes off with post 3 down
L13 ON
= it goes off with post 3 up
Important:
if the bollard does not operate in
phase with the open/close commands as
required, swap connections to 17/18.
GB
CONTROLLER FOR TALOS M50
ANTI-TERRORISM RETRACTABLE BOLLARDS