Dimensional Diagrams

 

Ducted

Ductless

11”

* it is highly recommended that 

professional style cooking always be 

vented to the outside.

WARNING!

 

Product specifications are subject to change without notification.  Consult the installation instructions before you begin installing this rangehood.

Ductless Installations*

For installations where ductwork is 

impossible or highly impractical, a 

Charcoal Filter Kit

 is available.  A 

charcoal filter, which attaches un-

der the blower assembly, absorbs 

smoke and odors. 

Make your ductrun as straight and short as possible.  The ductrun should not 

exceed 35 equivalent feet if ducted with the required minimum of 6” round duct.  

Count 45º angles as 3 feet, 90º elbows as 5 feet, and 90º flat elbows as 12 feet.

For best results, use no more than three 90° elbows. Make sure that there is 

a minimum of 24” of straight duct between elbows if more than one is used. 

Do not install two elbows together. If you must elbow right away, do it as far 

away from the hood’s exhaust opening as possible.

Pre-Planning Your Installation - 

Important: Consult the installation instructions before you begin installing this rangehood.