Installation manual MatriX 800/500 I,II,III and 800/650 I,II,III

 

 

10 < 

<

 

<

 

4

 

Preparation and installation 

instructions 

 

4.1

 

Gas connection 

The gas connection must comply with the 
applicable local standards. 
 

 

Please note! 

 

Provide a flexible gas connection with at 
least 0,5m extra length, so that the 
control unit can be removed for 
installation and service! 

 

Calculate the gas pipe so that no 
pressure drop occurs. 

 
We advise using a gas connection directly from the 
gas meter to the appliance, with a shut-off valve in 
the proximity of the appliance, which must always 
be freely accessible. Position the gas connection so 
that it is easily accessible for service and the 
burner unit can be disassembled at any time. 
 

4.2

 

Electrical connection 

Install a 230VAC/50Hz wall socket near the 
fireplace for connecting the Control box FAB1806. 
 
See fig. 2.8 for the wiring diagram: 

A = I.T.C. (Intelligent Technical Controller) 
B = electronics 
C = gas valve 
D = solenoid valve 
E = Symbio LED module (optional) 
F = ignition pin 
G = ionization pin 
H = power cable 
I = configuration plug 

 

4.3

 

Smart Home installation 

The controller can be connected to an external 
source, such as a Domotica system, by using a 
Faber Interface Unit (article number A9323000). 
 

4.4

 

Preparing the fireplace 

 

Remove the fireplace from its packaging. 
Ensure that the gas supply pipes under 
the appliance are not damaged. 

 

Remove the glass and any mouldings, 
store them at a safe place and remove the 
packaged parts from the fireplace. 

 

Prepare the gas connection on the 
regulator. 

 

4.5

 

Positioning the fireplace 

Take into account the installation requirements 
(see chapter 3). Place the fireplace at the right 
place and level it. 

Rough height adjustment: 

 

With the adjustable (optional) legs. 

Accurate height adjustment:  

 

With the adjustable feet. 

 

Hanging on the wall 
The fireplace can also be mounted on the wall by 
using the optional wall bracket set, see attachment 
16.9 (article number A9322996). 
Therefore remove the existing brackets and use 
the supplied spacer for vertical alignment, see fig. 
1.7. 
 

4.6

 

Mounting flue gas exhaust materials 

Assemble the flue gas exhaust materials according 
to the installation manual supplied with the flue 
gas exhaust material! 

 

The distance to combustible materials 
must be min. 50mm, calculated from 
outside of the flue material. 

 

Never start immediately with length-
adjustable concentric flue material on the 
appliance. 

 

Horizontal sections should be installed to 
allow a slope towards the fireplace  

(3 degrees). 

 

Build the system from the fireplace. If this 
is not possible you can make use of an 
extendable adapter section. 

 

For fitting of the flue system, the 0,5m 
length-adjustable pipe must be used. 
Make sure that the inner pipe is always 
15mm longer than the outer pipe. Wall- 
and roof terminal can also be cut. These 
components must be secured with a self-
tapping screw. 

 

4.7

 

Constructing the false chimney 

Before positioning the false chimney, we advise to 
perform a functional test with the fireplace as 
defined in chapter 7 “Checking the installation”. 
 
False chimney 

 

Construct the false chimney of non-
combustible material in combination with 
metal profiles or of masonry/concrete 
blocks. 

 

Always use a lintel or reinforcing bars 
while bricking the false chimney. They 
should not be placed directly on the 
fireplace. 

 

Make sure that the fireplace never 
functions as a load-bearing construction, 
because of the expansion of the fireplace 
through warmth. 

 

 

Содержание e-MatriX 800-500 I

Страница 1: ...Installation manual MatriX 800 500 I II III MatriX 800 650 I II III ENG 40011730 1940 ...

Страница 2: ...Installation manual MatriX 800 500 I II III and 800 650 I II III 2 1 0 1 1 1 2 1 3 ...

Страница 3: ...Installation manual MatriX 800 500 I II III and 800 650 I II III 3 1 4 1 5 1 6 ...

Страница 4: ...Installation manual MatriX 800 500 I II III and 800 650 I II III 4 1 7 1 8 1 9 2 0 ...

Страница 5: ...Installation manual MatriX 800 500 I II III and 800 650 I II III 5 2 1 2 2 2 3 2 4 2 5 ...

Страница 6: ...Installation manual MatriX 800 500 I II III and 800 650 I II III 6 2 6 2 7 2 8 3 0 3 1 ...

Страница 7: ...Installation manual MatriX 800 500 I II III and 800 650 I II III 7 3 2 3 3 3 4 3 5 3 6 3 7 3 8 ...

Страница 8: ...ty instructions Please note It is advisable to always install a screen for the fireplace if children elderly or disabled people are present in the same room as the fireplace If regularly vulnerable persons can be present in the room without supervision sufficient protection must always be placed around the fireplace This appliance must be installed according with the rules in force and used only i...

Страница 9: ... Faber can guarantee proper performance The distance to combustible materials must be min 50mm calculated from outside of the flue material EN 1856 1 T600 N1 D Vm L20040 O 50 Outlets fig 1 8 The balanced flue pipe for combined air supply and discharge can use a wall terminal or a roof terminal Verify that the desired outlet meets the local regulations regarding pollution and ventilation openings P...

Страница 10: ...Place the fireplace at the right place and level it Rough height adjustment With the adjustable optional legs Accurate height adjustment With the adjustable feet Hanging on the wall The fireplace can also be mounted on the wall by using the optional wall bracket set see attachment 16 9 article number A9322996 Therefore remove the existing brackets and use the supplied spacer for vertical alignment...

Страница 11: ...e those first fig 2 5 The following points are of interest fig 2 6 K built in frame L distance profiles M glass supports N top edge of the combustion chamber Remove all distance profiles L Please note Make sure that the screws of the front distance profile L will be replaced in order to ensure the air tightness of the appliance For the height of the plateau see point N fig 2 6 and 2 7 Take into ac...

Страница 12: ...ed is good Move or remove any chips glass granulate to create a nice glow bed Install the front glass and check the fire image 7 Checking the installation Checking for gas leaks Check with a gas leak finder all connections and pipes for gas leakage Check primary pressure Check if the primary pressure correspond to the data on the rating plate Measuring the primary pressure Close the shutoff valve ...

Страница 13: ...he App and its settings Emphasize the danger of fingerprint burns at the glass Give advice and instructions on care and cleaning of the glass Handover to customer o installation manual o user manual o decoration instruction card o suction cups o sample Faber glass polish 9 Annual maintenance Check Check and clean if necessary the combustion chamber the burner the wooden logs for breakage the glass...

Страница 14: ...nd pipes entirely in the horizontal plane See elbows I K and Q and the elements H J L M P and R fig 12 1 and 12 2 Horizontal length The Horizontal Length consists of the elements H J L M P and R fig 12 1 and 12 2 Elbows 90 in the horizontal plane Horizontal elbows are elbows entirely in the horizontal plane fig 12 1 12 2 and 12 3 I K and Q Elbows 45 or 30 in the horizontal plane Horizontal elbows ...

Страница 15: ...x x x x x x x x x 10 60 2 0 2 0 2 x x x x x x x x 11 60 2 30 2 0 2 x x x x x x x x 12 60 2 30 2 0 2 x x x x x x x x 13 70 2 30 2 0 2 x x x x x x x x 14 70 2 30 2 30 2 0 2 x x x x x x x 15 70 2 30 2 30 2 0 2 x x x x x x x 16 70 2 30 2 30 2 0 2 x x x x x x x 17 80 2 30 2 30 2 0 2 x x x x x x x 18 80 2 40 2 30 2 30 2 x x x x x x x 19 80 2 40 2 30 2 30 2 x x x x x x x 20 80 2 40 2 40 2 30 2 x x x x x ...

Страница 16: ...0 3 50 4 50 4 45 4 45 4 40 4 x x 10 50 4 50 3 50 4 50 4 50 4 45 4 45 4 x x 11 60 4 60 3 60 4 50 4 50 4 50 4 45 4 x x 12 60 4 60 3 60 4 60 4 50 4 50 4 50 4 x x 13 60 4 60 3 60 4 60 4 60 4 50 4 50 4 x x 14 70 4 70 3 60 4 60 4 60 4 60 4 50 4 x x 15 70 4 70 3 70 4 60 4 60 4 60 4 60 4 x x 16 70 4 70 3 70 4 70 4 60 4 60 4 60 4 x x 17 80 4 70 3 70 4 70 4 70 4 60 4 60 4 x x 18 80 4 80 3 70 4 70 4 70 4 70 ...

Страница 17: ... 3 50 4 50 4 45 4 45 4 40 4 x x 10 50 4 50 3 50 4 50 4 50 4 45 4 45 4 x x 11 60 4 60 3 60 4 50 4 50 4 50 4 45 4 x x 12 60 4 60 3 60 4 60 4 50 4 50 4 50 4 x x 13 60 4 60 3 60 4 60 4 60 4 50 4 50 4 x x 14 70 4 70 3 60 4 60 4 60 4 60 4 50 4 x x 15 70 4 70 3 70 4 60 4 60 4 60 4 60 4 x x 16 70 4 70 3 70 4 70 4 60 4 60 4 60 4 x x 17 80 4 70 3 70 4 70 4 70 4 60 4 60 4 x x 18 80 4 80 3 70 4 70 4 70 4 70 4...

Страница 18: ...0 4 x x x x 10 70 4 70 4 60 4 60 4 60 4 60 4 60 4 x x x x 11 70 4 70 4 70 4 60 4 60 4 60 4 60 4 x x x x 12 70 4 70 4 70 4 70 4 60 4 60 4 60 4 x x x x 13 70 4 70 4 70 4 70 4 70 4 60 4 60 4 x x x x 14 70 4 70 4 70 4 70 4 70 4 70 4 60 4 x x x x 15 70 4 70 4 70 4 70 4 70 4 70 4 70 4 x x x x 16 80 4 70 4 70 4 70 4 70 4 70 4 70 4 x x x x 17 80 4 80 4 70 4 70 4 70 4 70 4 70 4 x x x x 18 80 4 80 4 80 4 70...

Страница 19: ... 4 x x x x 10 70 4 70 4 60 4 60 4 60 4 60 4 60 4 x x x x 11 70 4 70 4 70 4 60 4 60 4 60 4 60 4 x x x x 12 70 4 70 4 70 4 70 4 60 4 60 4 60 4 x x x x 13 70 4 70 4 70 4 70 4 70 4 60 4 60 4 x x x x 14 70 4 70 4 70 4 70 4 70 4 70 4 60 4 x x x x 15 70 4 70 4 70 4 70 4 70 4 70 4 70 4 x x x x 16 80 4 70 4 70 4 70 4 70 4 70 4 70 4 x x x x 17 80 4 80 4 70 4 70 4 70 4 70 4 70 4 x x x x 18 80 4 80 4 80 4 70 ...

Страница 20: ...Installation manual MatriX 800 500 I II III and 800 650 I II III 20 12 Examples flue materials ...

Страница 21: ... 5m till 2m 1 5 Flue length 2m or more 2 Bend 90 0 1 Bend 45 30 or 15 0 2 Roof terminal 1 Wall terminal 0 Total Vertical Height TVH measured height rounded value meter meter Total Horizontal Length THL Calculation Part number x value result rounded value Total Length in meters x 1 90 Bend vertical to horizontal x 0 4 45 Bend vertical to horizontal x 0 2 90 Bend in horizontal direction x 1 5 45 Ben...

Страница 22: ...ue X then the installation is not possible Solution Change the TVH or THL Results Restrictor size Value for the comma mm Extra information Value behind the comma mark Install the air restrictor plate see installation manual 0 1 Install adapter 100 150 direct on top of the fire 0 2 In case of wall terminal install adapter 100 150 before the last bend in case of roof terminal just before the termina...

Страница 23: ... B B Energy efficiency index EEI 83 83 Type heating output control room temperature no no no no no yes Diameter outlet inlet 130 200 Technical data Type indication s MatriX 1050x500 I II III Matrix 800x500 I II III Type appliance C11 C31 C91 Gas connection 3 8 Indirect heating functionality no Category II2H3P Gas rate at full mark Power requirement for permanent pilot light if applicable Ppilot 0 ...

Страница 24: ...Energy efficiency index EEI 87 87 Type heating output control room temperature no no no no no yes Glen Dimplex Benelux Saturnus 8 Heerenveen The Netherlands With mechanical control of the room temperature by thermostat Control of room temperature with open window detection yes With electronic control of the room temperature With electronic control of the room temperature plus day time switch With ...

Страница 25: ...s Location Position outlet Distance mm D Under a gutter 500 E Under a roof edge 500 F Under a carport or balcony 500 G Vertical downpipe 300 H Inside and outside corners 500 J From wall surface to a wall outlet 1000 K Two gable outlets against over each other 1000 L Distance between two roof outlets 450 M Two roof outlets above each other on a pitched roof 1000 N Two gable outlets next to each oth...

Страница 26: ...Installation manual MatriX 800 500 I II III and 800 650 I II III 26 16 Dimensional drawings 16 1 MatriX 800 500 I ...

Страница 27: ...Installation manual MatriX 800 500 I II III and 800 650 I II III 27 16 2 MatriX 800 500 IIL ...

Страница 28: ...Installation manual MatriX 800 500 I II III and 800 650 I II III 28 16 3 MatriX 800 500 IIR ...

Страница 29: ...Installation manual MatriX 800 500 I II III and 800 650 I II III 29 16 4 MatriX 800 500 III ...

Страница 30: ...Installation manual MatriX 800 500 I II III and 800 650 I II III 30 16 5 MatriX 800 650 I ...

Страница 31: ...Installation manual MatriX 800 500 I II III and 800 650 I II III 31 16 6 MatriX 800 650 IIL ...

Страница 32: ...Installation manual MatriX 800 500 I II III and 800 650 I II III 32 16 7 MatriX 800 500 IIR ...

Страница 33: ...Installation manual MatriX 800 500 I II III and 800 650 I II III 33 16 8 MatriX 800 650 III ...

Страница 34: ...Installation manual MatriX 800 500 I II III and 800 650 I II III 34 16 9 Wall bracket MatriX 800 500 I II III and MatriX 800 650 I II III article number A9322996 ...

Страница 35: ...Installation manual MatriX 800 500 I II III and 800 650 I II III 35 16 10 Control box FAB1806 ...

Страница 36: ...Installation manual MatriX 800 500 I II III and 800 650 I II III 36 16 11 Ventilation grid article number A9296400 ...

Страница 37: ...Installation manual MatriX 800 500 I II III and 800 650 I II III 37 16 12 Adjustable feet article number A9319696 ...

Страница 38: ...Installation manual MatriX 800 500 I II III and 800 650 I II III 38 17 Decoration instruction card 17 0 17 1 17 2a ...

Страница 39: ...Installation manual MatriX 800 500 I II III and 800 650 I II III 39 17 2b 17 2c 17 2d 17 3 ...

Страница 40: ...Installation manual MatriX 800 500 I II III and 800 650 I II III 40 17 4 17 5 17 6 ...

Страница 41: ...Installation manual MatriX 800 500 I II III and 800 650 I II III 41 ...

Страница 42: ...Installation manual MatriX 800 500 I II III and 800 650 I II III 42 ...

Страница 43: ...Installation manual MatriX 800 500 I II III and 800 650 I II III 43 ...

Страница 44: ...www faber fires eu info faber fires eu Saturnus 8 NL 8448 CC Heerenveen Postbus 219 NL 8440 AE Heerenveen ...

Отзывы: