background image

Installation Instructions 

 

14 

 

 

 

 

 

    4.4.1 

Hanging on the wall 800/500-650-IIL, -IIR and -III 

 

 

The appliance can be wall-mounted with the optional wall bracket 
(see fig. 1.8).

 

 

 

 

When penetrating a non-combustible wall or ceiling the 
opening must be at least 5mm larger than the diameter of the 
discharge material. At a combustible wall or ceiling is this 
100mm larger than the diameter of the drainage material.

 

 

Horizontal sections should be installed with a slope towards

 

the fire (3 degrees).

 

 

Build the system from the fire. If this is not possible you can 
make use of an extendable adapter section.

 

 

For truing up the exhaust system use the 0,5m. pipe, which 
can be shortened and ensure that the inner pipe is always 
2cm longer than the outer pipe.

 

 

Parts, which are shortened, must be secured with a 
self-tapping screw.

 

 

Wall and roof terminals can also be cut.

 

 

Do not insulate but ventilate built-in flue material (approx.

 

100cm²).

 

 

 

If possible, carry out a performance test at the fire before finally 
finishing the installation.

 

 

    4.6.1 

False chimney 

 

 

*

 

Construct the false chimney of non-combustible material in 
combination with metal profiles or of masonry/concrete 
blocks.

 

*

 

Be aware of ventilation grids and service door (see fig. 1.0 to 
1.5). Place above the ventilation grids a screen plate made of 
non-combustible material (see fig. 1.1, 1.3 or 1.5)

 

*

 

Always use a lintel or reinforcing bars while bricking the 
outlet. They should not be placed  directly on the fire.

 

*

 

Built the false chimney against the appliance (see fig. 1.0 to 
1.5). Keep a minimum distance of 2mm between the false 
chimney and the appliance, because of the extension of the 
appliance.

 

 

    

4.6.2 

Installation and finishing 

 

For installation and finishing the following points are of interest: 

H = moldings (fig. 2.4 and 2.7)

 

I = distance profile (fig. 2.4)

 

J = upper side flange combustion chamber (fig. 2.5) 
K = distance holder/glass support (fig. 2.6)

 

L = distance holder/glass support (fig. 2.6)

 

 

Please note:

 

Ensure that the fire is not load-bearing with regard to the false

 

chimney breast.

 

 

    

4.6.3 Method I (fig. 2.2) 

 

Build the false chimney breast against the moldings H and distance 
profiles I (see fig. 2.4 and 2.7).

 

Keep a minimum distance of 2mm between the false chimney and 
the appliance, because of the extension of the appliance. Take into 
account the thickness of the finish!

 

 

    

4.6.4 

Method II (fig. 2.3) 

 

 

Remove the distance profiles “I” (see fig. 2.4).

 

 

Make sure that the screws of the front distance profile “I” will be 
replaced, in order to ensure the air tightness of the appliance.

 

 

For the height of the plateau, see point “J” (fig. 2.5).

 

 

See fig. 2.6, distance profiles K and L. Keep a minimum distance of

 

2mm because of the extension of the appliance.

 

 

 

   5  Removing the glass 

 

 

800/500-650-I

 

 

Remove the moldings “A” left and right (fig. 3.0).

 

 

Turn the left and right side clamps “B” up (fig. 3.0).

 

 

Place the suction cups on the glass and slide the upper list

 

“C” up (fig. 3.1).

 

 

See fig. 3.2, number:

 

1.

 

Slide the glass to the top so that the bottom will 
release.

 

2.

 

Now, carefully slide the glass to the left.

 

3.

 

Get the released side towards to you and put the glass 
on a safe place.

 

 

800/500-650-IIL and IIR

 

 

Remove molding “A” left or right (fig. 3.0).

 

 

Turn the left or right side clamps “B” up (fig. 3.0).

 

 

Place the suction cups on the glass and slide the upper list

 

“C” up (fig. 3.3).

 

 

See fig. 3.3, number:

 

1.

 

Slide the glass to the top so that the bottom will 
release.

 

2.

 

Now, carefully slide the glass to the left or to the right.

 

3.

 

Get the released side towards to you and put the glass 
on a safe place.

 

 

800/500-650-III

 

 

Place the suction cups on the glass and slide the upper list

 

“C” up (fig. 3.3).

 

 

See fig. 3.3, number:

 

1. 

Slide the glass to the top so that the bottom will 
release.

 

4. 

Get the released side towards to you and put the glass 
on a safe place.

 

4.5 

Installing the flue materials

 

4.6 

Constructing the false chimney

 

5.1 

Removing the glass from the front

 

Содержание e-MatriX 800-500 I

Страница 1: ...40011633 1630 MatriX 800 ENG MatriX 800 serie ...

Страница 2: ...Installation Instructions 2 1 0 1 1 1 2 1 3 ...

Страница 3: ...Installation Instructions 3 D E 1 8 1 4 1 5 1 6 1 7 ...

Страница 4: ...Installation Instructions 4 1 9 2 0 2 1 ...

Страница 5: ...Installation Instructions 5 2 2 2 3 2 4 ...

Страница 6: ...Installation Instructions 6 2 5 H H 2 6 2 7 ...

Страница 7: ...Installation Instructions 7 I T C versie Symax versie 2 8 2 9 ...

Страница 8: ...Installation Instructions 8 3 0 3 1 3 2 3 3 ...

Страница 9: ...Installation Instructions 9 3 4 3 5 ...

Страница 10: ...Installation Instructions 10 4 3 4 0 4 1 4 2 ...

Страница 11: ...Installation Instructions 11 4 4 4 5 WRONG OK ...

Страница 12: ...onents from paint building materials and carpeted floors etc are attracted These parts can settle as soot on cold surfaces Therefore do not light the fire shortly afterinstallation Light the fire for the first time and run for several hours on the highest setting so that the paint can cure Provide adequate ventilation so that any fumes can disperse we recommend vacating the room during this proces...

Страница 13: ...Hz must be installed near the fire For power supply make use of the included plug adapter See fig 2 8 or 2 9 for the wiring diagram of this connection and the LED Symbio module A plug adapter B control unit C receiver D LED Symbio module E control block F magnet valve 4 2 1 Smart Home installation You can connect the control unit to the receiver with an external source such as a Domotica home auto...

Страница 14: ...stion chamber fig 2 5 K distance holder glass support fig 2 6 L distance holder glass support fig 2 6 Please note Ensure that the fire is not load bearing with regard to the false chimney breast 4 6 3 Method I fig 2 2 Build the false chimney breast against the moldings H and distance profiles I see fig 2 4 and 2 7 Keep a minimum distance of 2mm between the false chimney and the appliance because o...

Страница 15: ...unit if the pressure is too high Measuring the burner pressure Check the burner pressure only with proper primary pressure Turn measuring nipple A see fig 1 7 some turns openand connect a measuring hose to the gas regulator The pressure must correspond to the value indicated in the technical specifications of this manual In case of deviation contact the manufacturer Please note Close all pressure ...

Страница 16: ...d and Mac Google Play Android smartphones and Android tablets Alternatively use the exhaust calculation table see chapter 13 The alternatives of outlet lengths and any restrictors are set out in the restrictor table In the table we work with start length STL total vertical height TVH and total horizontal length THL Start length STL This is the first part that is placed on the fire and represents a...

Страница 17: ...le at the right vertical TVH and horizontal length THL For x and if the values are outside the table then the combination is not allowed Only then adjust the TVH or THL If a value is indicated check that the calculated STL value is not lower than indicated in the table In this case STL must be adjusted The found value indicates the width of the restrictor 0 means no restrictor Standard is a restri...

Страница 18: ...2 60 2 30 2 0 2 x x x x x x x x 13 70 2 30 2 0 2 x x x x x x x x 14 70 2 30 2 30 2 0 2 x x x x x x x 15 70 2 30 2 30 2 0 2 x x x x x x x 16 70 2 30 2 30 2 0 2 x x x x x x x 17 80 2 30 2 30 2 0 2 x x x x x x x 18 80 2 40 2 30 2 30 2 x x x x x x x 19 80 2 40 2 30 2 30 2 x x x x x x x 20 80 2 40 2 40 2 30 2 x x x x x x x 21 80 2 50 2 40 2 30 2 x x x x x x x 22 80 2 50 2 40 2 30 2 x x x x x x x 23 80 ...

Страница 19: ... 3 50 4 50 4 50 4 45 4 45 4 x x x x 11 60 4 60 3 60 4 50 4 50 4 50 4 45 4 x x x x 12 60 4 60 3 60 4 60 4 50 4 50 4 50 4 x x x x 13 60 4 60 3 60 4 60 4 60 4 50 4 50 4 x x x x 14 70 4 70 3 60 4 60 4 60 4 60 4 50 4 x x x x 15 70 4 70 3 70 4 60 4 60 4 60 4 60 4 x x x x 16 70 4 70 3 70 4 70 4 60 4 60 4 60 4 x x x x 17 80 4 70 3 70 4 70 4 70 4 60 4 60 4 x x x x 18 80 4 80 3 70 4 70 4 70 4 70 4 60 4 x x ...

Страница 20: ...3 50 4 50 4 50 4 45 4 45 4 x x x x 11 60 4 60 3 60 4 50 4 50 4 50 4 45 4 x x x x 12 60 4 60 3 60 4 60 4 50 4 50 4 50 4 x x x x 13 60 4 60 3 60 4 60 4 60 4 50 4 50 4 x x x x 14 70 4 70 3 60 4 60 4 60 4 60 4 50 4 x x x x 15 70 4 70 3 70 4 60 4 60 4 60 4 60 4 x x x x 16 70 4 70 3 70 4 70 4 60 4 60 4 60 4 x x x x 17 80 4 70 3 70 4 70 4 70 4 60 4 60 4 x x x x 18 80 4 80 3 70 4 70 4 70 4 70 4 60 4 x x x...

Страница 21: ... 4 60 4 60 4 60 4 60 4 60 4 x x x x 11 70 4 70 4 70 4 60 4 60 4 60 4 60 4 x x x x 12 70 4 70 4 70 4 70 4 60 4 60 4 60 4 x x x x 13 70 4 70 4 70 4 70 4 70 4 60 4 60 4 x x x x 14 70 4 70 4 70 4 70 4 70 4 70 4 60 4 x x x x 15 70 4 70 4 70 4 70 4 70 4 70 4 70 4 x x x x 16 80 4 70 4 70 4 70 4 70 4 70 4 70 4 x x x x 17 80 4 80 4 70 4 70 4 70 4 70 4 70 4 x x x x 18 80 4 80 4 80 4 70 4 70 4 70 4 70 4 x x ...

Страница 22: ... 60 4 60 4 60 4 60 4 60 4 x x x x 11 70 4 70 4 70 4 60 4 60 4 60 4 60 4 x x x x 12 70 4 70 4 70 4 70 4 60 4 60 4 60 4 x x x x 13 70 4 70 4 70 4 70 4 70 4 60 4 60 4 x x x x 14 70 4 70 4 70 4 70 4 70 4 70 4 60 4 x x x x 15 70 4 70 4 70 4 70 4 70 4 70 4 70 4 x x x x 16 80 4 70 4 70 4 70 4 70 4 70 4 70 4 x x x x 17 80 4 80 4 70 4 70 4 70 4 70 4 70 4 x x x x 18 80 4 80 4 80 4 70 4 70 4 70 4 70 4 x x x ...

Страница 23: ...Installation Instructions 23 12 Examples flue materials fig 12 1 fig 12 2 fig 12 3 ...

Страница 24: ...e length 2m or more 2 Bend 90 0 1 Bend 45 30 or 15 0 2 Roof terminal 1 Wall terminal 0 Total Vertical Height TVH measured height rounded value meter meter Total Horizontal Length THL Calculation Part number x value result rounded value Total Length in meters x 1 90 Bend vertical to horizontal x 0 4 45 Bend vertical to horizontal x 0 2 90 Bend in horizontal direction x 1 5 45 Bend in horizontal dir...

Страница 25: ...the top row of the table Is the found value X then the installation is not possible Solution Change the TVH or THL Results Restrictor size Value for the comma mm Extra information Value behind the comma mark Install the air restrictor plate see installation manual 0 1 Install adapter 100 150 direct on top of the fire 0 2 In case of wall terminal install adapter 100 150 before the last bend incase ...

Страница 26: ... gr h 720 710 Burner pressure at full mark mbar 13 8 21 28 4 Injector main burner mm 4x 1 3 1x 1 6 1x 0 8 4x 0 9 1x 0 8 4x 0 9 Reduced input restraint mm adjustable adjustable adjustable Pilot flame SIT145 SIT145 SIT145 Code pilot flame injector Nr 36 Nr 23 Nr 23 Diameter outlet inlet mm 130 200 130 200 130 200 Gas controle valve GV60 GV60 GV60 Gas connection 3 8 3 8 3 8 Electrical connection V 23...

Страница 27: ... 341 0 443 gr h 860 830 Burner pressure at full mark mbar 13 8 20 5 27 1 Injector main burner mm 4x 1 3 1x 1 6 5x 0 9 5x 0 9 Reduced input restraint mm 2 1 1 6 1 6 Pilot flame SIT145 SIT145 SIT145 Code pilot flame injector Nr 36 Nr 23 Nr 23 Diameter outlet inlet mm 130 200 130 200 130 200 Gas controle valve GV60 GV60 GV60 Gas connection 3 8 3 8 3 8 Electrical connection V 230 230 230 Batteries rem...

Страница 28: ...ou need to comply with the applicable rules as defined over roof Location Position outlet Distance mm D Under a gutter 500 E Under a roof edge 500 F Under a carport or balcony 500 G Vertical downpipe 300 H Inside and outside corners 500 J From wall surface to a wall outlet 1000 K Two gable outlets against over each other 1000 L Distance between two roof outlets 450 M Two roof outlets above each ot...

Страница 29: ...e for remote Batteryremote NO Battery receiver Faultyadapter Faultyreceiver See inst manual 1x 9V Alkaline 4x 1 5V AAAlkaline Replace 6Vadapter Replace thereceiver YES Clearly audible click from the solenoid in NO the gas valve NO NO YES NO YES Pilot lights NO interrupted check Check Tie wraps removed Every second a spark ...

Страница 30: ...t from the burner and fire switch NO of Check flue calculation horizontal length to long Correct flue restrictor Flue parts not correct installed Wall roof terminal blocked Check the distance from thermocouple to pilot flame Measure the mvolts over the thermocouple required min 4mvolts over black and ground contact Short circuit in the thermocouple circuit Faulty solenoid Check the complete wiring...

Страница 31: ...rt circuit in wiring Install a ground cable from the gas valve to the appliance Check complete wiring about thermocouple circuit Replace faulty parts RESET the receiver Check the wiring from solenoid valve to receiver Faulty solenoid valve Faulty receiver Repaire the wiring Replace solenoid valve Replace receiver Fire can be switched off with the remote YES the fire works OK ...

Страница 32: ...Installation Instructions 32 17 1 MatriX 800 500 I 17 Dimensional drawings ...

Страница 33: ...Installation Instructions 33 17 2 MatriX 800 500 IIL ...

Страница 34: ...Installation Instructions 34 17 3 MatriX 800 500 IIR ...

Страница 35: ...Installation Instructions 35 17 4 MatriX 800 500 III ...

Страница 36: ...Installation Instructions 36 17 5 MatriX 800 650 I ...

Страница 37: ...Installation Instructions 37 17 6 MatriX 800 650 IIL ...

Страница 38: ...Installation Instructions 38 17 7 MatriX 800 650 IIR ...

Страница 39: ...Installation Instructions 39 17 8 MatriX 800 650 III ...

Страница 40: ...Installation Instructions 40 17 9 Wall bracket ...

Страница 41: ...Installation Instructions 41 17 10 Remote acces door ...

Страница 42: ...Installation Instructions 42 17 11 Ventilation grid ...

Страница 43: ...Installation Instructions 43 17 12 Adjustable feet ...

Страница 44: ...Installation Instructions 44 Dealerinfo www faber nl info faber nl Saturnus 8 NL 8448 CC Heerenveen Postbus 219 NL 8440 AE Heerenveen ...

Отзывы: