INSTALLING THE INTERFACE
1.  Turn power OFF
2.  Plug in the XIB interface to the 2EASY con-

nector on the E024U board

3.  Wire the shadow loop detector NC output 

to the CL input on the XIB board. See Fig. 

2. 

4.  Connect Common from loop detector to 

Common (terminal 6) on E024U

5.  Also jump out the OP input on XIB board to 

Common (terminal 6) on E024U

6.  Turn power back ON
7.  Go through setup/learn mode on the 

E024U board

Shadow Loop Kit for E024U

J2

J3

DL1

DL2

J1

CL

OP

J1

( RED )

Connects  to    “2easy”  BUS    input            

on the E024U control board

J2

( RED )

Terminal block for the connection of 

the encoder

J3  CL

( GREEN )

Terminal for the NC connection of the 

shadow loop detector

J3 OP

( GREEN )

Not Used

DL1

LED for diagnostics of devices  

connected to the J3 OP terminal 

(not used)

DL2

LED for diagnostics of devices  

connected to the J3 CL terminal 

(see diagnostic table)

Through the use of the XIB interface board you can connect an additional loop detector (center or 

shadow) to the E024U board to keep the gate open if vehicles are obstructing the closing path.

Depending on the board revision you might need 

to upgrade the software on the E024U before you 

can use the shadow loop kit. The software can 

be downloaded from the faacusa.com website or 

requested from Technical Support. 
To do the upgrade:
1. 

Download software to a flash drive

2.  Disconnect batteries if present
3.  Turn AC power off and insert the Flash Drive 

into the USB connector on the board

4.  Turn AC power back on. The USB2 LED will 

flash to confirm beginning of software update. 

(Warning: Do not turn the power off or remove 

the flash drive until the USB2 LED turns off.)

5.  Wait until the USB2 LED turns off
6. 

Remove the USB flash drive

Fig 1: XIB board description

DIAGNOSTIC TABLE

OFF

SLOW FLASHING               

(FLASH EVERY 5 secs.)

ON STEADY

FAST FLASHING      

(FLASH EVERY 0.5 secs)

DL1

“XIB” board 

malfunction 

or no power

J3 OP terminal open 
(missing jumper on the OP 

input)

J3 OP terminal closed
(normal condition) 

Error condition on the 

BUS

DL2

“XIB” board 

malfunction 

or no power

J3 CL terminal open 
(loop detector active or not 

connected)

J3 CL terminal closed
(loop detector in idle condi-

tion)