1257014-GB_v1.1
STD-1EU / STD-2EU
2
CONNECTION
1
230V
∼
2
230V
∼
3
Motor 1
4
Motor 1
5
Common motor 1
6
Motor 2 (STANDARD/2-EU version)
7
Motor 2 (STANDARD/2-EU version)
8
Common motor 2 (STANDARD/2-EU version)
9
Garage light contact (LUZ GAR.)
10
Garage light contact (LUZ GAR.)
11
Flash light contact (DESTELLO)
12
Flash light contact (DESTELLO)
13
Electro-lock outlet (12V
=
/ 1A)
14
Electro-lock outlet (12V
=
/ 1A)
15
Security device outlet (24V
∼
/ 0.75A)
16
24V
∼
common outlet
17
24V
∼
autotest outlet (TEST SEC.)
18
Common securities
19
Security Close contact (NC)
20
Security Open contact (NC)
21
Security Close edge (resistive contact 8k2)
22
Security Open edge (resistive contact 8k2)
23
Common ends of run
24
End of run Close motor 1
25
End of run Open motor 1
26
End of run Close motor 2 (STANDARD/2-EU version)
27
End of run Open motor 2 (STANDARD/2-EU version)
28
Common buttons
29
Pedestrian button (NO)
30
Start button (NO)
31
Close button (NO)
32
Common buttons
33
Stop button (NC)
34
Start button (NO)
INSTALLATION
Any handling of the panel for installation must be carried out with the power supply disconnected.
FITTING THE CASING
• Parts: front casing and container box.
• Unscrew the securing points. Insert the cables through the lower holes.
IMPORTANT CONSIDERATIONS FOR START-UP
If the door does not open when the button is first pushed, invert the motor cables.
Where inversions are made, the panel adds time to ensure the door closes.
Any optional cards must be connected to the panel with the power supply disconnected.
OPERATING
Start (ALT): Contact normally open to open and close. First time the button is pressed, it opens; the
second time (if it has not reached the end of the run), it stops and the third time it closes.