5.2.     VEHICLE ACCESS IN LOGIC “A” 

 

 

In the configuration for the management of a lane in logic “A” you 
need  to  add  a  detector  FG1.  Fasten  the  DIN  guide  on  the  two 
available screws and press the detector in place. 

 

Prepare a 24 Vdc power supply and perform the connections as 
shown in fig.13.

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

 
 
 
 
 
Presence Time and Reset 

The presence time can be set 
using the  
microswitch 
 

h

”. At the end of the  

presence time the detector 
 
 
 
signals “loop free” and self-calibrates. The presence time starts 
when the loop is engaged. An automatic reset is performed 

when the detector is activated or when the dip 

h

” setting changes.

 

 
 
 
 
 

Operation of the Relay  

The detector is equipped with 2 relays:  
Relay 1 supplies a presence  
contact, while Relay 2 sends a pulse 
when the loop is disengaged. The operation of  
Relay 1 can be selected by changing the setting of the 
dip “

r

”. 

 

N.B.: For this application you need to select the operation 

 

“N.O.” contact. 

 
 
 
 
 
 
Frequency selection 

The detector operating frequency 
can be set on  
two levels according to the position 
of the loop connector. 
Frequency depends furthermore 
on the loop shape, on the 
number of windings and on the cable total length. 

 

N.B.: For any further explanations on the operation of the 

detector  FG1, please refer to the specific instructions of 
the product.

 

 

5.3.     VEHICLE ACCESS IN LOGIC “P”

 

 

In the  configuration  for the management  of  a lane  in  logic  “P” 
you need to add the detector FG2. Fasten the DIN guide on the 
two available screws and press the detector base in place.  
 
 

fig.13:

 

the  token  insertion  slot  only  opens  when  a  vehicle  is  on  the 
magnetic loop.  The  gate  or  beam  opening  command must be 
connected  to  the  microswitch  of  the  accepting  module  (see 
Chapter. 5.1.).

 

 

For the detector FG1 programming, operate as follows:  

 
 

 

 

 

 

 
 

Sensitivity 

The detector sensitivity can 
be set on four  
different levels using the two first 
microswitches on top  
(close to letter 

s

). 

 
 
 
 
 

  

 
 
 
 
 
 
 

loop 

PRESENCE TIME 

                  5 minutes 

SENSITIVITY 

         LOW 

       MEDIUM-LOW 

      MEDIUM-HIGH 

      HIGH 

RELAY 1 FUNCTION 

    N.C. CONTACT 

   N.O. CONTACT 

FREQUENCY 

LOOP CONN.  

LOW 

LOOP 1 
(presence) 

LOOP 2 
(transit) 

Microswitch  1 
Token acceptor module 

Board 
624 MPS 

Ticket Dispenser 

 
   Shutter 

 
   
SHUTTER 

 
   HIGH 

Содержание F0254

Страница 1: ...forms to the essential safety requirements of the following EEC directives 73 23 EEC and following modification 93 68 EEC 89 336 EEC and following modification 92 31 EEC and 93 68 EEC Additional notes this product underwent tests in a typical homogeneous configuration all products by FAAC S p A Bologna 2nd January 2009 The Managing Director A Marcellan 1 ...

Страница 2: ... gas or inflammable fumes is a serious danger to safety 8 FAAC is not responsible for failure to observe Good Technique in the installation of the product 9 Before attempting any job on the system cut out electrical power 10 Make sure that a differential switch with threshold of 0 03A is fitted upstream of the system 11 Make sure that the earthing system is perfectly realised and connect the yello...

Страница 3: ...strian configuration the token insertion slot must be always open in this case the shutter must be physically removed In the vehicle configuration by interfacing a Single or a Two Channel Detector you can enable the token insertion only in the presence of a vehicle in this case pedestrians are not allowed to use the lane Tab 1 Technical Specifications GRS 02 Token Acceptor 2 DIMENSIONS fig 2 3 POW...

Страница 4: ...ll if possible adequate means of protections against accidental impact Check that an efficient earth socket is available for connecting the housing of the Token Acceptor 4 2 POSITIONING THE COMPONENTS 4 2 1 PEDESTRIAN ACCESS Before placing the foundation plate of the GRS 02 Token Acceptor make sure the following conditions are observed The Token Acceptor must be installed in such a way not to expo...

Страница 5: ... laying the cable directly in a chase made in the existing pavement or this is the best solution realising a cable duct in PVC before the pavement is made In both cases the cable must be laid not over 5 cm from the surface and not less than 15 cm from covers or other metallic objects In case of a cable duct you can use a normal single pole cable with 1 5 mm section On the contrary the cable direct...

Страница 6: ...inth as shown in fig 10 and wall the foundation plate supplying one or more sheaths for routing electrical cables Using a spirit level check if the plate is perfectly level Wait for the cement to set fig 10 3 Prepare the electric cables for the connection as indicated in Chapter 3 1 3 2 or 3 3 according to the type of use For easy connection let the cables come out of the foundation plate hole for...

Страница 7: ...y can be set on two levels according to the position of the loop connector Frequency depends furthermore on the loop shape on the number of windings and on the cable total length N B For any further explanations on the operation of the detector FG1 please refer to the specific instructions of the product 5 3 VEHICLE ACCESS IN LOGIC P In the configuration for the management of a lane in logic P you...

Страница 8: ...esence OFF OFF LOW ON OFF MEDIUM LOW OFF ON MEDIUM HIGH ON ON HIGH SW3 SW4 LOOP 2 SENSITIVITY transit OFF OFF LOW ON OFF MEDIUM LOW OFF ON MEDIUM HIGH ON ON HIGH Frequency selection The detector operating frequency can be set on two levels using the dip SW5 The detector automatically changes the frequencies of both loops Frequency depends furthermore on the loop shape on the number of windings and...

Страница 9: ...HE CONNECTION OF PHOTOCELLS AND SAFETY DEVICES REFER TO PARAGRAPH 4 1 BEAM BREAKTHROUGH BARRIER 620 640 SET IN LOGIC P OPEN CLOSED COMMANDS OPEN BARRIER CLOSED BARRIER LOOP 2 Safety stop command logic p on 624 BLD OPEN CLOSED COMMON CONTACT BARRIER PHOTOCELL MICROSWITCH ON GRS 02 ON N O CONTACT RELAY ENGLISH ...

Страница 10: ...IC A OPEN CLOSED COMMANDS OPEN BARRIER OPEN COMMON CONTACT Safety stop command logic A on 624 BLD BARRIER PHOTOCELL MICROSWITCH ON GRS 02 ON N O CONTACT LOOP 2 MOTOR FAN MOTOR THRUST CAPACITOR BEAM BREAKTHROUGH FOR THE CONNECTION OF PHOTOCELLS AND SAFETY DEVICES REFER TO PARAGRAPH 4 1 RELAY ENGLISH ...

Отзывы: