INSTRUCTION MANUAL AUTOMATIC MAGNETIC LOCK DB310
5
Revision 9
Settings for EP103 with magnetic lock
When an electric magnetic lock is used, the magnetism must have time to release before the gate is
allowed to start moving. It is therefore possible to delay the start of gate movement with an adjustable
time in channel C39, 0.00 to 0.99 seconds. C39 is normally to be kept at its starting value 0.00, but if
the magnet still holds the gate leaf at the start the value must be increased until it no longer does so.
If the magnetic lock is of the overlap type, the delay time between the halves must be adjusted in chan-
nel C38, 0.1 to 9.9 seconds so that the halves do not jam together. A start value could be 3.0 seconds,
i.e. it takes 3 seconds from the time when the first half starts until the second half starts. When starting
from the closed position, it is always motor 1 that starts first, so think about how the two halves of the
magnetic lock are to be installed.
See also Commissioning of gate, section on magnetic lock, in the instruction manual for EP103.
No.
Name
Range
Factory Setting
C38
Time delay before second motor starts. Start
of motor 2 is delayed in opening, and start of
motor 1 is delayed in closing
0.1-9.9 seconds
0.1
C39
Time delay before first motor starts. Start of
motor 1 is delayed in opening, and start of
motor 2 is delayed in closing
0.00-0.99 seconds 0.00
Settings for EP104 and EP105 with magnetic lock
When an electric magnetic lock is used, the magnetism must have time to release before the gate is
allowed to start moving. It is therefore possible to delay the start of gate movement with an adjustable
time in channel C470, 0.00 to 0.99 seconds. C470 is normally to be kept at its starting value 0.00, but if
the magnet still holds the gate leaf at the start the value must be increased until it no longer does so.
If the magnetic lock is of the overlap type, the delay time between the halves must be adjusted in chan-
nel C460, 0.1 to 9.9 seconds so that the halves do not jam together. A start value could be 3.0 seconds,
i.e. it takes 3 seconds from the time when the first half starts until the second half starts. When starting
from the closed position, it is always motor 1 that starts first, so think about how the two halves of the
magnetic lock are to be installed.
No.
Name
Range
Factory Setting
C460 Time delay before second motor starts. Start
of motor 2 is delayed in opening, and start of
motor 1 is delayed in closing
0.1-9.9 seconds
0.1
C470 Time delay before first motor starts. Start of
motor 1 is delayed in opening, and start of
motor 2 is delayed in closing
0.00-0.99 seconds 0.00