Settings for EP103 with magnetic lock

When an electric magnetic lock is used, the magnetism must have time to release before the gate is 

allowed to start moving. It is therefore possible to delay the start of  gate movement with an adjustable 

time in channel C39, 0.00 to 0.99 seconds. C39 is normally to be kept at its starting value 0.00, but if 

the magnet still holds the gate leaf  at the start the value must be increased until it no longer does so. 

If  the magnetic lock is of  the overlap type, the delay time between the halves must be adjusted in chan-

nel C38, 0.1 to 9.9 seconds so that the halves do not jam together. A start value could be 3.0 seconds, 

i.e. it takes 3 seconds from the time when the first half starts until the second half starts. When starting 

from the closed position, it is always motor 1 that starts first, so think about how the two halves of  the 

magnetic lock are to be installed. 

See also Commissioning of  gate, section on magnetic lock, in the instruction manual for EP103.

No. 

Name

Range

Factory Setting

C38

Time delay before second motor starts. Start 

of motor 2 is delayed in opening, and start of 

motor 1 is delayed in closing

0.1-9.9 seconds

0.1

C39

Time delay before first motor starts. Start of 

motor 1 is delayed in opening, and start of 

motor 2 is delayed in closing

0.00-0.99 seconds 0.00

Settings for EP104 and EP105 with magnetic lock

When an electric magnetic lock is used, the magnetism must have time to release before the gate is 

allowed to start moving. It is therefore possible to delay the start of  gate movement with an adjustable 

time in channel C470, 0.00 to 0.99 seconds. C470 is normally to be kept at its starting value 0.00, but if 

the magnet still holds the gate leaf  at the start the value must be increased until it no longer does so. 

If  the magnetic lock is of  the overlap type, the delay time between the halves must be adjusted in chan-

nel C460, 0.1 to 9.9 seconds so that the halves do not jam together. A start value could be 3.0 seconds, 

i.e. it takes 3 seconds from the time when the first half starts until the second half starts. When starting 

from the closed position, it is always motor 1 that starts first, so think about how the two halves of  the 

magnetic lock are to be installed. 

No. 

Name

Range

Factory Setting

C460 Time delay before second motor starts. Start 

of motor 2 is delayed in opening, and start of 

motor 1 is delayed in closing

0.1-9.9 seconds

0.1

C470 Time delay before first motor starts. Start of 

motor 1 is delayed in opening, and start of 

motor 2 is delayed in closing

0.00-0.99 seconds 0.00