Parameters Settings | Checking
1.
Press
“
”and “ ” together for 5 seconds to enter “parameter checking” status, parameter code “P0” will blink on
the left, parameter value “2” will display on the right.
2.
Press “
” Key and “
” Key to check the parameters.
3.
Press “
” key to exit "parameter checking" status.
Modifying parameters
4.
In "parameter checking" status, press “
” to enter "parameter setting" status. At this moment the
“
parameter value
”
will blink.
5.
In "parameter setting" state, press “
” and “
” to change the parameters value
6.
Press “
”to confirm and return to the previous status; Or press “
” key to quit and return to the previous status.
Parameter Table
NO.
Content
Adjust range
Step
length
Default
P0
Water pump running way
0
:
Continuation
1
:
Water temp control
2
:
time/water temp control
1
2
P1
Time setting ( only available when the water pump
running way is set to “2”
10 ~ 120 min
5 min
60 min
P2
Compressor continuously running time in
defrosting mode
30 ~ 90min
1min
35 min
P3
Defrosting start temp
-17 ~ 0
℃
1
℃
-7
℃
P4
Defrosting running time
1 ~ 12min
1min
12 min
P5
Defrosting quit temp
8 ~ 30
℃
1
℃
13
℃
P6
Single pump option
On/off
0 ~ 100
1
off
P10
Compressor speed control
0
:
Auto
,
1
:
Manual
1
0
P12
Electronic expansion valve overheat level
(
heating
)
-10 ~ 20
1
3
P13
Electronic expansion valve overheat level
(
cooling
)
-10 ~ 20
1
5
P14
Electronic expansion valve manual/auto
0
:
Auto
,
1
:
Manual
1
0
P15
Electronic expansion valve opening setting
(
heating
)
50 ~ 240
2P
175
(
H5
)
P16
Electronic expansion valve opening setting
(
cooling
)
50 ~ 240
2P
175
(
H5
)
P20
Power off memory function
0 — NO
,
1 — YES
1
1