Introduction

PD-33 DL is a passive infrared detector intended for presence 

detection and the control of light fittings over a DALI bus. It uses 

a pyroelectric sensor that reacts to changes in thermal radiation. 

Properties

• 

PD-33 DL is able to turn on, dim and turn off DALI light fit-

tings.

• 

It uses broadcast or group addressing.

• 

Multiple detectors work together if they are controlling the 

same group of light fittings or if they are using broadcast 

addressing.

• 

The light level can be controlled directly (100%, 10%, 0%) 

or by choosing preset levels from scenes 10, 14 and 15.

• 

Adjustable presence delay of 2 seconds to 20 minutes.

• 

Timer controls duration of low-level lighting before switch-

off, 5 minutes or 30 minutes.

• 

Configuration for office environments that use a different 

form of signal processing when presence is detected.

• 

“No start” mode can be selected that simply keeps lighting 

switched on. (Switched on manually with pushbutton.)

• 

Power is supplied via the DALI bus (max. consumption 12 

mA).

• 

Settings are adjusted using knobs and jumpers on the de-

tector circuit board.

• 

Lens can be replaced to adjust the detection range. A 

choice of lenses is available.

Commissioning

• 

Check that the 

“Activity Low/Office” 

jumper is set to the 

“Low” position

• 

Carry out a walk test over the entire detection area. 

Note!

 The lens must be fitted and the cover must be in 

place. Adjust vertically and horizontally as required. 

• 

After the walk test and adjustment, the presence delay 

should be set to the lowest setting. In dynamic lighting con-

trol applications, such as stairways and corridors, a suitable 

time is 1–2 minutes. In other applications, such as class-

rooms and garages, the time can be set to 6–8 minutes or 

in line with the light source supplier’s recommendations.  

• 

Set the 

“Occupancy Activity”

 jumper to match the level of 

activity in the premises. 

• 

We recommend that the LED is disconnected once adjust-

ment is complete (see “Detector settings”), to minimise the 

risk of tampering. 

Basic terminology

•  Broadcast

: Broadcast addressing means that the detector 

sends its DALI commands to all light fittings at the same time.

•  Groups:  

The light fittings in a DALI system can also be con-

trolled using group addresses. (DALI supports 16 groups.) 

•  Direct control: 

The light fittings are controlled by setting the 

lighting level with DALI commands (Direct level). 

•  Scene: 

Each light fitting can have 16 programmed scenes. 

Each scene means that the light fitting is lit at a certain level 

(intensity). The light levels of the scenes for each light fitting 

can be programmed using a computer.

•  Operating mode: Direct level or Extronic. 

Direct level means 

that the light levels are controlled directly and at preset levels.  

Extronic means that the light fittings are switched between 

scenes 10, 14 and 15.

•  Delays;

 

•  Presence delay:

 The length of time that the lighting re-

mains switched on at the normal level after presence is no 

longer detected.  

Low-level delay

: (Timer delay, base level duration) The 

length of time that the lighting remains at the base level be-

fore it is switched off completely.  

•  No start: 

The lighting is not switched on automatically when 

presence is detected. It can be switched on manually using 

a pushbutton.

•  Normal level: – 

light  level  that  is  used  when  someone  is 

present in the premises. 

•  Base level: – 

low light level that is used when premises are 

empty.

Contents

Introduction ...........................................................................................1

Commissioning .....................................................................................1

Basic terminology .................................................................................1

Detector settings...................................................................................2

Mode Direct level: Direct control of light level.......................................3

Application example, “Mode Direct level” .............................................4

Mode Extronic: Control using scenes 10, 14 and 15 ............................5

Application example “Mode Extronic” ...................................................6

Wiring examples ...................................................................................9

Lens ....................................................................................................10

Replacing and adjusting lenses  .........................................................10 

Technical specification  .......................................................................10

PRESENCE DETECTOR PD-33 DL 

v 1.1

Installation instructions

Order no. 13150, E no. 13 060 85

Extronic Elektronik AB +46 8 609 29 00

2015-12-14

Содержание PD-33 DL

Страница 1: ... of activity in the premises We recommend that the LED is disconnected once adjust ment is complete see Detector settings to minimise the risk of tampering Basic terminology Broadcast Broadcast addressing means that the detector sends its DALI commands to all light fittings at the same time Groups The light fittings in a DALI system can also be con trolled using group addresses DALI supports 16 gr...

Страница 2: ... delay 1 5 Groups 1 to 5 get 1 5 lighting level during low level delay F Used with level selectors NP 2T DL and NP 3T DL 6 E Not used Mode selector Selection number 0 9 A F Choice of control by broadcast or groups 1 to 15 Selection number determines which group is used Selection number 0 is used for Broadcast Selection numbers 1 to 9 send DALI commands to the re spective group Selection numbers A ...

Страница 3: ...belong to the same group or are in Broadcast mode To prevent the lighting from being switched on automatical ly No start remove the LED indication jumper The lighting can be switched off using one or more push buttons that send the DALI command off The lighting can be switched on using one or more push buttons that send the DALI command recall max level A 30 minute low level delay can be selected ...

Страница 4: ...ation example Mode Direct level G1 Simple example of controlling a DALI loop with PD 33 DL No programming of light fittings is needed Broadcast to all light fittings with direct control of all light fittings in the loop and without any need for programming detectors or light fittings When presence is detected the light fittings are switched on at the normal level of 100 After the presence delay th...

Страница 5: ...ommand go to scene 1 5 or 10 A 30 minute low level delay can be obtained if the Occu pancy activity jumper is removed normally 5 minutes Manual scenes can be created using scenes 1 5 to pro vide lighting for cleaning or showing films for example Detectors assigned to different groups work independently of each other Manual control off Manual control No start Using scenes 1 to 5 manually Presence s...

Страница 6: ...nic 0 Broadcast Selection number Mode Extronic 0 Broadcast Selection number Mode Extronic 0 Broadcast Selection number Mode Extronic 0 Broadcast Selection number Application example Mode Extronic E1 Garage with some light fittings that are never switched off Setting Mode Extronic The detectors jointly control the whole garage using scenes 10 14 and 15 The light fittings near the entrances should n...

Страница 7: ...The low level delay time is increased from 5 minutes to 30 min utes by removing the Occupancy Activity jumper In this case the light fittings are programmed to Scene 10 Max light level when presence is detected normal level Scene 14 Low level no presence detected 5 base level Scene 15 0 Scene 1 100 cleaning lighting manual level that is switched on with pushbutton 230 VAC Mode Extronic Selection n...

Страница 8: ...lows Scene 1 Manual board lighting and main lighting Scene 2 Manual projector mode Scene 3 Main lighting is switched on manually normal level Scene 10 Automatic level Scene 14 Low level delay of 5 minutes at base level Scene 15 Switched off 0 lighting when no one is present Main lighting Board lighting Pushbutton scene 1 main lighting and board lighting Pushbutton scene 3 main lighting Pushbutton ...

Страница 9: ...italout Max 200mA Timer 0 120minutes ExtronicAB Stockholm Sweden LevelswitchNP 3TDL 100 240VAC Buspowersupplyandbuscontroller fordigitallydimmableluminaires Timerforswitchingofthelight 12345678910111213 141516171819202122232425 Timer 15m 30m 1h 2h 0 100 100h 100 100h 0 2 5 5 10 20 Slow Fast StartBlock Min Max LowLevel Light Sensor SwitchDet Off Min Max 4 5 6 78 9 10 11 15 16 19 20 22 23 24 Min Reg...

Страница 10: ...circuit board is moved upwards it lowers the detection field and vice versa The vertical adjustment of the circuit board is preset at 5 The recommended installation height for best detection is 1 9 2 2 m Masking lens elements Lens elements can be masked to limit the detection area Self adhesive aluminium foil tape like that used to protect win dows will block 100 per cent of thermal radiation Acce...

Отзывы: