Mounting
This section outlines the various options for:
•
Mounting the TLP Pro 1220MG, 1520MG, and 1720MG
•
•
•
Mounting the TLP Pro 1220TG, 1520TG, and 1720TG
•
•
Mounting the TLP Pro 1220MG, 1520MG, and 1720MG
Rack Mounting
These touchpanels can be mounted in any standard 19-inch equipment rack, using the optional
rack mounting kit.
•
TLP Pro 1220MG
: RM 2 kit
•
TLP Pro 1520MG
: RM 3 kit
•
TLP Pro 1720MG
: RM 3 kit
Read the Underwriters Laboratories Guidelines for Rack Mounting below and follow the
instructions provided with the appropriate kit.
Underwriters Laboratories Guidelines for Rack Mounting
The following Underwriters Laboratories (UL) guidelines are relevant to the safe installation of
these products in a rack:
•
Elevated operating ambient temperature
— If the unit is installed in a closed or multi-
unit rack assembly, the operating ambient temperature of the rack environment may be
greater than room ambient temperature. Therefore, install the equipment in an environment
compatible with the maximum ambient temperature (Tma: +104 °F, +40 °C) specified by
Extron.
•
Reduced air flow
— Install the equipment in the rack so that the equipment gets adequate
air flow for safe operation.
•
Mechanical loading
— Mount the equipment in the rack so that uneven mechanical
loading does not create a hazardous condition.
•
Circuit overloading
— Connect the equipment to the supply circuit and consider the
effect that circuit overloading might have on overcurrent protection and supply wiring.
Give appropriate consideration to the equipment nameplate ratings when addressing this
concern.
•
Reliable earthing (grounding)
— Maintain reliable grounding of rack-mounted equipment.
Pay particular attention to supply connections other than direct connections to the branch
circuit (such as the use of power strips).
TLP Pro 1220, TLP Pro 1520, and TLP Pro 1720 Series • Mounting