12
ExtremeSwitching SLX 9140 Hardware Installation Guide
9036857-00 Rev AA
Installing the device in a rack
Installing the device in a rack
NOTE
You need a #2 Phillips screwdriver for installation.
Before mounting the device in a rack, pay particular attention to the following factors:
•
Temperature: Because the temperature within a rack assembly may be higher than the ambient room temperature, check that
the rack-environment temperature is within the specified operating temperature range. (Refer to
•
Mechanical loading: Do not place any equipment on top of a rack-mounted unit.
•
Circuit overloading: Be sure that the supply circuit to the rack assembly is not overloaded.
•
Grounding: Rack-mounted equipment should be properly grounded. Particular attention should be given to supply connections
other than direct connections to the mains electricity supply.
To mount the product into a four-post rack using the included rack-mount kit (XBR-R000297), refer to
on page 12 for the installation procedure.
To mount the product into a two-post rack, you can order the two-post rack kit with the part number XBR-R000294. For the procedure
to install this kit, refer to
“Installing the Universal Two-Post Rack Kit (XBR-R000294)”
To mount the product into a four-post rack, you can also order the four-post rack kit with the part number XBR-R000296. For the
procedure to install this kit, refer to
“Installing the Universal Four-Post Rack Kit (XBR-R000296)”
Four-post rack mount installation (XBR-R000297)
Use the following instructions to install the SLX 9140 switch in EIA racks that are between 46 cm and 79 cm (18 to 31 in.) using the
four-post flush-mount rack kit included with the switch.
Time and items required
Allow 15 to 30 minutes to complete the installation.
The following items are required to install the device using the four-post flush-mount rack kit:
•
#2 Phillips torque screwdriver
•
1/4-inch slotted-blade screwdriver
CAUTION
Do not install the device in an environment where the operating ambient temperature might exceed 50°C (122°F).
CAUTION
Make sure the rack housing the device is adequately secured to prevent it from becoming unstable or falling over.
Содержание ExtremeSwitching SLX 9140
Страница 6: ...vi ExtremeSwitching SLX 9140 Hardware Installation Guide 9036857 00 Rev AA ...
Страница 10: ...x ExtremeSwitching SLX 9140 Hardware Installation Guide 9036857 00 Rev AA Contacting Extreme Technical Support ...
Страница 12: ...2 ExtremeSwitching SLX 9140 Hardware Installation Guide 9036857 00 Rev AA Supported hardware and software ...
Страница 54: ...44 ExtremeSwitching SLX 9140 Hardware Installation Guide 9036857 00 Rev AA Connecting network devices ...
Страница 76: ...66 ExtremeSwitching SLX 9140 Hardware Installation Guide 9036857 00 Rev AA Regulatory compliance environmental ...