ExTox ET-1D Series Скачать руководство пользователя страница 4

 

Instruction Manual 

ExTox Control Unit ET-1D Series 

 

Page 4 of 17 

1

 

Introduction 

This Instruction Manual generally describes operation, installation and maintenance of the 
following ExTox-Products: 
 

Wall mounted 

DIN-Rail 

Control Panel 

19''-Rack 

Artikel-Nr. 

230 V / 24 V 

230 V / 24 V 

230 V / 24 V 

230 V / 24 V 

ET-1D 

303010 303011 303014 303015 

ET-1DA 

305010 305011 305014 305015 

 
Type specific data for each device should be taken from a corresponding separate and spe-

cific Data Sheet. This Data Sheet forms consequently part of this Instruction Manual. Refer-
ences on the Data Sheet within this text are marked with 

)

DB

Please read this Instruction Manual carefully before installation and initial operation of the 
control unit. We kindly ask you to pay attention to all details and cross-references. 
We kindly ask you not to repair the control unit or to perform any changes which go beyond 

the measures described herein. Otherwise you endanger your own safety and your warranty 
claims of merchantability. In such cases please contact ExTox or authorised ExTox Service 

Partner. Third parties take the responsibility for correct performance of work when mainte-
nance and repairs are done by them. 
On receipt of goods please take care that packing and consignment are not damaged and 
the goods supplied correspond to the articles described in the delivery note. Please do also 

compare with your order. In case of any damage please inform your forwarding agent and 
your supplier.  Please keep the damaged packing.  
Please keep in mind that control units are sensitive measuring devices and take special care 

when unpacking and installing them. 
 

Содержание ET-1D Series

Страница 1: ...Instruction Manual ExTox Control Unit ET 1D Series...

Страница 2: ...to the requirements of the regulations and stan dards valid for industrial application The Control Unit of the ET 1D series is a compact and easily understandable system for sin gle transmitters It is...

Страница 3: ...5 4 Channel Fault 12 5 5 Fault of Control Unit 13 5 6 Programme Run Monitoring Watchdog 13 5 7 Initialisation 13 5 8 Service Mode 13 5 9 Analogue Outputs 4 20 mA Type ET 1DA only 13 6 Application 14...

Страница 4: ...nit We kindly ask you to pay attention to all details and cross references We kindly ask you not to repair the control unit or to perform any changes which go beyond the measures described herein Othe...

Страница 5: ...for our control units The control units in combination with ExTox transmitters comply with EN 60079 29 1 and EN 45544 for Gas Detection Systems Furthermore they are in conformity with the European Di...

Страница 6: ...can be used to quit the integrated acoustic signalling device and horn relay Under normal operation the functional key F4 is not set If you leave indication under normal operation by pressing F1 NEXT...

Страница 7: ...wo keys for ca 5 s again cancels the release Release is automatically reset if the keys are not used for more than 10 minutes Attention During service mode Service On the release remains permanently P...

Страница 8: ...on both are deactivated The horn relay can be reset via key F3 HORN even if the alarm condition is still present Attention This function should only be used for exter nal acoustic signallers Hint The...

Страница 9: ...ut current which rests at the input of the control unit is displayed The two last menu items serve for the adjustment of the control unit without any work to be necessary at the transmitter Adjustment...

Страница 10: ...ed during operation the ET 1D offers the possibility of a device internal adjustment Therefore the determined current value is converted with an offset factor and a gain factor directly after recordin...

Страница 11: ...ings are permanently displayed Relays Alarm 1 and 2 K1 K2 not triggered Fault K3 not triggered Horn K4 not triggered Integrated Signaller mute 5 2 Alarms Minimum one configured alarm level is triggere...

Страница 12: ...ot triggered Horn K4 corresponding to measuring operation 5 1 or Alarm 5 2 Integrated Signaller corresponding to measuring operation 5 1 or Alarm 5 2 5 4 Channel Fault The input current of the transmi...

Страница 13: ...he initialisation 5 7 is passed If the ET 1D does not enter normal operation again please contact the ExTox Service 5 7 Initialisation After connection of the ET 1D to the power supply it is passing a...

Страница 14: ...agen EN 45544 4 Electrical devices used for the direct detection and direct concentration measurement of toxic gases and vapours Part 4 Guide for selection installation use and maintenance Merkblatt T...

Страница 15: ...les for the gas sen sors should better be run separately On the type in wall mounted housing and for DIN Rail installation the housing has to be opened To do this you have to remove the blind plates o...

Страница 16: ...ection T 023 Toxic Gases Vapours and Oxygen T 021 1 Month Visual Check 4 Months Functional Check 1 Year System Check 1 Month Visual Check 6 Months Functional Check 1 Year System Check You as user of t...

Страница 17: ...ible maintenance personnel The measures corresponding to your application have to be determined and the person in charge for maintenance has to be familiar with all details 8 4 System Check The system...