background image

RD200-en-GB_V1.0   4/18 

Testing for Leaks in Air Conditioning 

1.

 

Add refrigerant to the air conditioning system in order to maintain a pressure of 340Kpa 
(50PSI). Leaks may go undetected if the ambient temperature is < 15°C (59°F), because of 
insufficient pressure. 

2.

 

Before testing, conduct a visual and audible inspection of the entire refrigerating system 
including all pipes, hoses, and components. Look for leaks, damage, or corrosion. Listen for 
the sound of air escaping. 

3.

 

Set the sensitivity level to high by pressing the High sensitivity button (red LEDs will briefly 
flash) and then slowly pass the probe near all potential sources of leaks and gage the meter’s 
response by observing the color-coded leak-level LEDs and listening for the audible tones. 
Always make measurements along a continuous route for best results.  

4.

 

The two green LEDs represent the absence of a leak or a very small leak, the two yellow LEDs 
represent a moderate leak, and the three red LEDs represent the detection of a large leak. 

5.

 

Once an area of leakage is detected set the meter to low sensitivity mode by pressing the 
Low sensitivity button (green LEDs will briefly flash) and inspect the area of the leak again to 
determine the precise location. 

6.

 

The distance of the sensor (7) to the surface of the component under test should be 5mm 
(0.2”) or nearer. Move the probe slowly, no more than 25~50mm/second (1 to 2”/second). 
See the Measurement Considerations section for more information. 

Note: To pinpoint a large leak more effectively, use compressed air on the suspected area of the 
leak to help determine the precise location. 

Testing for Leaks in an Evaporator Core 

1.

 

When checking for a leak in an evaporator core, adjust the air conditioning blower to the 
highest setting for 15 seconds, and then power it OFF. 

2.

 

Wait approximately 10 minutes for refrigerants to accumulate inside the air conditioning 
evaporator. 

3.

 

Insert the sensor into the resistance block of the fan (if there is no water) or place it at the 
opening of the nearest heating, ventilating, or air conditioning container of the evaporator. 

4.

 

Check for visual and audible alarms to determine if there is a leak. 

Measurement Considerations 

 

If you do not detect a leak, try the low sensitivity mode (press Low sensitivity button) and check 
again. 

 

If there is wind in the area of test, shielding the suspected leak area from the wind will yield 
better results. 

 

Do not allow moisture or solvent near the sensor, this may introduce false alarms.  

 

When you suspect a large leak, using compressed air in the area of the leak may help 
determine the exact location of the leak. 

 

To verify leaks, conduct tests several times in succession. 

 

Содержание RD200

Страница 1: ...User Manual Refrigerant Leak Detector Model RD200 Additional User Manual Translations available at www extech com ...

Страница 2: ...e sensitivity levels Battery status LED indicator Test solution included allows the user to check the condition of the sensor 50 cm 19 7 flexible gooseneck probe Safety Please read the safety information carefully before attempting to operate the meter Failure to do so could cause personal injury or damage to the meter Please read this manual carefully to ensure safe and correct use Do not attempt...

Страница 3: ...ch ON or if the low battery LED 4 glows red 2 While powering on the leak level LEDs 2 will light in sequence left to right and the start up tone will sound once 3 The meter will start heating the sensor 7 during a 2 minute warm up period the leak level LEDs will continue to light in sequence during the warm up 4 After the warm up the audible tone will sound twice indicating that the detector is re...

Страница 4: ...The distance of the sensor 7 to the surface of the component under test should be 5mm 0 2 or nearer Move the probe slowly no more than 25 50mm second 1 to 2 second See the Measurement Considerations section for more information Note To pinpoint a large leak more effectively use compressed air on the suspected area of the leak to help determine the precise location Testing for Leaks in an Evaporato...

Страница 5: ...equipment Checking the Probe Condition with the Test Solution The test bottle provided contains an ethanol solution that emits a gas when the bottle is opened If the sensor is in good condition it will detect the gas and the meter will provide audible and visual alerts If alerts do not occur the sensor should be replaced immediately Always tightly seal and safely store the test bottle when not in ...

Страница 6: ... 2 minutes approx Response Time Instantaneous Auto Power OFF Automatic shut off after 10 minutes Low Battery Indication Battery status LED glows red Power Supply 9V Battery rear compartment under protective jacket Battery Life 30 hours of normal use Operating Conditions 0 C to 50 C 32 F to 122 F 80 RH Storage Conditions 10 C to 80 C 14 F to 176 F 70 RH Length Flexible Gooseneck only 50 2cm 19 8 Le...

Отзывы: