6.1
Single-pole applications
6.1.1
Locating Opened Wires
Figure 6.1
Locating opened wires. Diagram shows one transmitter in a fixed location and
one Receiver being used in two locations. The Receiver position on the left is detecting a sig-
nal, while the Receiver position on the right is not detecting a signal.
1. Connect the red, positive (+) terminal to a single conductor.
2. Connect the black (
COM
) terminal to earth ground. If convenient, use the
supplied ground spike for an outdoor earth ground connection.
3. If there are additional conductors in the same conduit or cable, they will al-
so have to be connected to earth ground.
4. The Receiver can now detect the location of the wiring fault.
6.1.2
Locating and Tracing Lines and Receptacles
WARNING
Do not perform this test on a live circuit.
#NAS100035; r. AA/71038/71038; en-US
11