461960 V1.1  8/07 

Alarm Hysteresis value setting 

1. 

After selecting the "Control Hysteresis value" , press the "Set” button twice, the 
display will show " ALHy ", the meter is now ready for the "Alarm Hysteresis” value 
setting. 

2. 

Use the "

” button and the "

” button to adjust the desired Alarm Hysteresis 

value. 

Note: When adjusting the value, the "SV” indicator will light. 

 

Example : 
High limit value : 100, Low limit value : 20, Alarm Hysteresis value : 5 
 
 
 
 
 
 
 
 
 

1. 

The alarm relay will be On when measuring value up to 100. The alarm relay will 
turn Off again when measuring value down to 95. 

2. 

The alarm relay will be On when measuring value down to 20. The alarm relay will 
turn Off when measuring value up to 25. 

 
 

SYSTEM RESET 

Power on the meter. Use two fingers to press the "Set” button and "Function” button 
continuously for more than 5 seconds until the display show the text "rSt". Release the 
buttons. "rSt" will flash 2 times and the display will then to the normal screen. The meter 
system will be reset, all the calibration data will be cleared and the meter's internal 
functions will return to the default values. 

Содержание 461960

Страница 1: ...on Street Melrose MA 02176 Phone 781 665 1400 Toll Free 1 800 517 8431 Visit us at www TestEquipmentDepot com Back to the Extech 461960 Product Page Test Equipment Depot 800 517 8431 99 Washington Str...

Страница 2: ...ORATION warrants this instrument to be free of defects in parts and workmanship for one year from date of shipment a six month limited warranty applies to sensors and cables If it should become necess...

Страница 3: ...ble Insulation or Reinforced Insulation Safety Procedures Do not use fingers or any tool to touch the Wire Terminals Do not exceed 0 5A relay contact load The instrument contains no user serviceable p...

Страница 4: ...in indicator 13 Wire terminals 14 Case holder 15 RS232 terminal Terminal connections Do not input an over voltage to the AC input terminals 1 Input the ACV power 90 to 260 ACV to T1 T2 2 Connect the C...

Страница 5: ...3 Press the Function button once until the ft min indicator is on The display will show the ft min value 4 Under the surface speed measurement the PV indicator will also light 5 To calculate m min Tot...

Страница 6: ...ue Setting 1 After setting the Low Limit value press the Set button twice the display will show HILt the meter is now ready for the humidity High Limit value setting 2 Use the button and the to adjust...

Страница 7: ...on press the Set button twice the display will show dIA now the meter is ready for the Roller diameter value setting 2 Use the button and the button to adjust the Roller diameter value in the unit of...

Страница 8: ...relay will be On when measuring value up to 100 The alarm relay will turn Off again when measuring value down to 95 2 The alarm relay will be On when measuring value down to 20 The alarm relay will tu...

Страница 9: ...Power Supply DC 12 V 50 mA max Data Output RS 232 PC serial interface Operating Temperature 32 to 122 F 0 to 50 C Operating Humidity Less than 80 R H Power Supply 90 to 260 ACV 50 60 Hz Power Consumpt...

Страница 10: ...dity 35 to 95 RH Wire Dimension 4 7 mm Dia x 2 m x 3 cores Cable length 6 ft 1 8 meters 461957 Photoelectric Sensor Specifications Range Up to 6000 RPM 100 Hz Power 12 24VDC 10 Consumption 40mA max Re...

Отзывы: