Page
3
ML548_ES | v3
Expo Technologies UK
T: +44 (0) 20 8398 8011
Expo Technologies US
T: +1 (440) 247 5314
Expo Technologies China
T: +86 532 8906 9858
Relief Valve Unit and Purge Outlet Valve with integral spark arrestor
Note: There must be a 1.5 mbarg difference between the minimum pressure and intermediate sensors and a 5 mbarg
difference between the RLV lift-off point and the high pressure.
Purge Flow Sensor:
Set at 6.4 mbarg (Tolerance: -0, +10%).
CLAPS Sensor:
Minimum: 5.0 mbarg.
Maximum:15 mbarg.
Default Setting: 10 mbarg.
Tolerance: -0, +10%
Note: there must be a 2.5 mbarg difference between the intermediate and CLAPS sensor calibration point.
For example: Minimum pressure = 5 mbarg, intermediate pressure = 6.5 mbarg, CLAPS sensor = 9 mbarg.
Purge Time:
User selectable, in 1 minute intervals, up to 99 minutes (tolerance -0, +3
seconds).
Default Setting 99 minutes.
Weight:
110 kg (242.5lb).
Type:
RLV104/SS/PV/OV/LT, Design number D760RLV.
Bore:
Purge Outlet Valve Ø 104 mm, Relief Valve Ø 104 mm.
Relief Valve Lift-Off Pressure:
Minimum:
20 mbarg.
Maximum:
35 mbarg.
Default:
30 mbarg (+0, -20%).
Flow Rate:
Range:
2000, 3000, 4000, 5000, or 6000 NI/min.
Default:
2000 NI/min.
Material:
Housing:
Stainless steel 316L.
Gasket:
Silicone foam.
Spark arrestor:
Stainless steel mesh.
Mounting Method:
Rectangular cut-out and fixing holes as per drawing.
Weight:
7 kg (15.4 lb).
Содержание MiniPurge D760-ES
Страница 3: ...ML548_ES v3 ii Section 11 Glossary 20 Section 12 Drawings and Diagrams 20 Section 13 Certifications 21...
Страница 33: ......
Страница 34: ......
Страница 35: ......
Страница 36: ......
Страница 37: ......
Страница 38: ......
Страница 39: ......
Страница 40: ......
Страница 41: ...2...
Страница 42: ...2...
Страница 43: ......
Страница 44: ......
Страница 45: ......
Страница 46: ......
Страница 47: ......
Страница 48: ......
Страница 50: ......
Страница 51: ......