UK |
7
3112009_CFIR_UK
Warning
To minimise the risk of fire, electric shock, personal injury
and/or damage to the product please observe the following:
• Please always read the manual and only use the product in accordance with the
manufacturer’s instructions. If in doubt, contact one of the Exodraft specialized dealers.
•
All installations must be carried out by properly qualifi ed personnel in accordance with
national legislation and regulations.
•
This product must be earthed. Get assistance from an qualifi ed electrician when in doubt.
•
The chimney fan must always remain switched on when the fireplace is in use.
•
Ensure that the chimney has been swept before mounting the fan to avoid chimney fires.
• Prior to servicing the product, disconnect the power and ensure that it cannot accidentally
be reconnected.
•
Exodraft always recommends the use of a smoke alarm when a solid fuel fireplace is
installed.
• If the Exodraft fan system has been designed for solid fuel/multi fuel installations, please
ensure that the design meets the requirements of BS EN15287-1. If this cannot be achie-
ved, a smoke alarm must be installed in the same room as the heat appliance.
• Note! Fans serving biomass boilers must be cleaned more often due to extensive residue/
soot building. It is essential that a regular inspection and cleaning schedule is implemen-
ted, especially in the early days of usage, to experience how often regular inspections and
cleaning should be carried out.
UK
Your energy.
Optimized.
Product information
An Exodraft CFIR Inline fan is intended for use as a true in-line draft inducer. It can be installed in-line in the
vertical or horizontal section of the fluepipe.
It is specifically designed for applications where reliable and efficient operation, low noise level, low energy
consumption, variable speed and compact design are critical.
The CFIR is for use with condensing and non-condensing appliances operating at a maximum flue gas
temperatures of 600 °C.
Typical uses are mechanical venting of gas-fired or oil-fired boilers and water heaters. The CFIR is for
indoor or outdoor installation where ambient temperatures are in the range of -40 °C to 50 °C.
The CFIR Inline fan should only be used with appliances operating on Natural Gas, LP-Gas/Butane or fuel
oil. It should never be used with incinerators or solid-fuel burning equipment. The temperature of the flue
gases going through the Inline fan should not exceed 600 °C.
The CFIR is not suitable for pulsating boilers.
ATTENTION! It is always recommended to install a CO alarm in the boiler room.
Incorrect firing may result in problems with soot, chimney fires, etc. which might damage the product.
Please check out this site for advice about lighting and maintaining a fire:
www.exodraft.com
Scope of supply
• Exodraft CFIR Inline fan
• Installation manual and user instructions
Accessories and spare parts
The table below shows the accessories and spare parts available for the CFIR-models.
Accessories*
Spare parts
Frequency inverter
Inlet cone
Outlet cone
Motor
Impeller
Gasket
U-band
*This manual does not describe the specific use of accessories. We refer to the separate manuals for such components.
For more details contact your Exodraft dealer.