Exide Sonnenschein SOLAR Скачать руководство пользователя страница 2

2.5 Alternating currents

When recharging acc. to fig.1 the actual value of
the alternating current is occasionally permitted
to reach 10 A (RMS)/ 100 Ah nominal capacity. In
a fully charged state during float charge the
actual value of the alternating current must not
exceed 5 A (RMS)/ 100 Ah nominal capacity.

2.6 Charging currents

The charging current should range between 10 A
to 35 A / 100Ah nominal capacity (guide values). 

2.7 Temperature

The recommended operation temperature range
for lead acid batteries is 10° C to 30° C (best 20° C
± 5 K). Higher temperatures will seriously reduce
service life. Lower temperatures reduce the avai-
lable capacity. The absolute maximum tempera-
ture is 55° C and should not exceed 45° C in ser-
vice.

2.8 Temperature-related charge voltage

The temperature related adjustment has to be
carried out acc. to fig. 1. An adjustment of the
charge voltage must not be applied within a
temperature range 15° C to 35° C.

2.9 Electrolyte

The electrolyte is diluted sulphuric acid and fixed 
in a gel.

3. Battery maintenance and control

Keep the battery clean and dry to avoid leakage
currents. Plastic parts of the battery, especially
containers, must be cleaned with pure water
without additives.

At least every 6 months measure and record:

Battery voltage

Voltage of several blocs/cells

Surface temperature of several blocs/cells

Battery-room temperature

If the bloc/cell voltages differ from the average
float charge voltage by values more than speci-
fied in the following table or if the surface tem-
perature difference between blocs/cells exceeds
5 K, the service agent should be contacted.

In addition, annual measurements and recor-
ding:

Voltage of all blocs/cells

Surface temperature of all blocs/cells

Battery-room temperature

Annual visual checks:

Screw connections

Screw connections without locking device
have to be checked for tightness.

Battery installation and arrangement

Ventilation

4. Tests

Tests have to be carried out according to 
IEC 60896-21, DIN 43539 part 1 and 100 (draft). 

Capacity test, for instance, acceptance test
on site:

In order to make sure the battery is fully

charged  the following IU-charge methods must
be applied: Option 1: float charge (see item 2.3),

72 hours. Option 2: 2.40 Vpc, 

16 hours (max.

48 hours) followed by float charge (see item 2.3),

8 hours. The current available to the battery

must be between 10 A/100 Ah and 35 A/100Ah
of the nominal capacity

5. Faults

Call the service agents immediately if faults in
the battery or the charging unit are found.
Recorded data as described in item 3. must be
made available to the service agent. It is recom-
mended that a service contract is taken out with
your agent.

6. Storage and taking out of operation

To store or decommission cells for a longer
Period of  time they should be fully charged and 
stored in a dry and cold but frost-free room,
away from direct sun light. To avoid damage the 
following charging methods can be chosen:

Type

Upper value

Lower value

2 V cells 

+0.2

-0.1

6 V blocs

+0.35

-0.17

12 V-blocs

+0.48

-0.24

1. Maximum storage time is 17 months at 

20° C. Equalizing charges will be required

at higher temperatures, for instance, after
8.5 months at 30° C.

2. Float charging as detailed in 2.3.

7. Transport

Cells/bloc batteries must be transported in an
upright position. Batteries without any visible
damage are not defined as dangerous goods
under the regulations for transport of dangerous
goods by road (ADR) or by railway (RID). They
must be protected against short circuits, slip-
ping, upsetting or damaging. Cells/bloc batteries
may be suitable stacked and secured on pallets
(ADR and RID, special provision 598). It is prohi-
bited to staple pallets.
No dangerous traces of acid shall be found on
the exteriors of the packing unit.
Cells/bloc batteries whose containers leak or are
damaged must be packed and transported as
class 8 dangerous goods under UN no. 2794.

Fig. 1: Charge voltage vs. temperature for solar mode. Charge modes

:

1) 

With switch regulator (two-step controller): Charge on curve B (max. charge voltage)
for max. 2hrs per day, then switch over to continuous charge – Curve C

2) 

Standard charge (without switching) – Curve A

3) 

Boost charge (Equalizing charge with external generator): Charge on curve B for max.
5hrs per month, then switch over to curve C.

Содержание Sonnenschein SOLAR

Страница 1: ...harge current IN I100 I100 C100 100h Final discharge voltage Uf see technical data in these instructions Nominal temperature TN 20 C Assembly by EXIDE Technologies order no date Commissioned by date Security signs attached by date Control of insulation resistance New batteries 1M Ω Used batteries 100 Ω Volt Connect the battery with the correct polarity to the charger pos pole to pos terminal The c...

Страница 2: ...for instance acceptance test on site In order to make sure the battery is fully charged the following IU charge methods must be applied Option 1 float charge see item 2 3 72 hours Option 2 2 40 Vpc 16 hours max 48 hours followed by float charge see item 2 3 8 hours The current available to the battery must be between 10 A 100 Ah and 35 A 100Ah of the nominal capacity 5 Faults Call the service agen...

Страница 3: ... 70 75 SB 12 100 57 84 89 90 100 SB 12 130 78 101 105 116 130 SB 12 185 103 150 155 165 185 SB 06 200 104 153 162 180 200 SB 06 330 150 235 260 280 330 Uf cell 1 7 Vpc 1 7 Vpc 1 7 Vpc 1 75 Vpc 1 80 Vpc 8 3 Sonnenschein A 600 SOLAR Discharge time 1 h 3 h 5 h 10 h 100 h Capacity C1 Ah C3 Ah C5 Ah C10 Ah C100 Ah 4 OPzV 240 123 6 167 4 193 5 218 0 290 0 5 OPzV 300 154 5 209 4 241 5 272 0 360 0 6 OPzV ...

Страница 4: ...09 Druckhaus Bechstein Printed in Germany Subject to change 56029045 5 0 IX 07 Exide Technologies GmbH Im Thiergarten 63654 Büdingen Germany Tel 49 0 60 42 81 544 Fax 49 0 60 42 81 398 www industrialenergy exide com ...

Отзывы: