Sales
x
Service
x
Recycling 888.563.6300 in the USA 800.268.2698 in Canada
3
CHARGER SPECIFICATIONS
The
Element
system specifications are listed below.
LMT-06kW-48-xxxS
LMT-10kW-48-
xxxT
LMT-10kW-80-
xxxT
Nominal VA Ratings
48V / 150A
48V / 250A
80V / 120A
Input Specs.
Voltage
480VAC, 3-phase +10% Delta Connection with Earth
Ground
Current (nominal)
8.3A rms / phase
13.8A rms /
phase
13.8A rms /
phase
AC Circuit Size
15A
20A 20A
Power Factor
0.96 (Active Power Factor Correction)
Output Specs.
Voltage
48V Nom. /
62.5V Max.
48V Nom. /
62.5V Max.
80V Nom. /
110V Max.
Current 150A
Max.
250A Max.
120A Max.
Power
6 kW Max.
10 kW Max.
10 kW Max.
Pk-Pk Voltage Ripple
< 1%
Efficiency (typical)
92% at Full Load
Protection
Input
¾
Under voltage
¾
Over Voltage
Output
¾
Over Current
¾
Over Voltage
¾
Over temperature
¾
Battery reverse polarity protection
Operating Conditions
Ambient Temperature
0 – 40
o
C
Humidity 10-90%
RH
non-condensing
Interface
Communication
Isolated RS-232 (Ethernet optional)
User Interface
LCD/Keypad, RS-232, IR with a PDA (Palm Pilot)
Cooling
Forced air (fans)
Mechanical
Dim. WxDxH
29"x8.5"x28"
Weight
~ 98 lb
Output Cabling
2/0 cables
Output Connectors
SBX w/aux. contacts or Euro Connector
Auxiliary Contacts
Interface with 5k
ȍ
battery thermistor (optional)
Certifications
UL and cUL Listed
Note: Design and/or specifications are subject to change without notice. If questions arise,
contact your local sales representative for clarification.