4.1.6 Damper
Service menu
Damper
Description
DAMPER
Show current operating status. Set functions and forced
fan control of damper.
Submenu
Any comments
Outdoor air damper
Outdoor air damper, status
●
Current damper position: Open/closed
●
Current supply air [m3/h] [l/s]
Shown at Belimo Mod-
bus damper motor
Damper motor, Modbus
●
Current damper setting [%]
●
Absolute position [Feedback]
●
Test run: Yes/No
●
Communication [Active] / [Inactive]
Shown only in case of
modulating damper mo-
tor
Set outdoor air damper
●
Current damper setting [%]
●
Set correction factor
●
Set offset [V]
●
Current supply air [m3/h] [l/s]
Shown only in case of
modulating damper mo-
tor
Override outdoor air damper
Overriding is only possible once the unit has started.
●
Set remaining time until overriding terminates
[hh:mm:ss]
●
Activate override: On/ Off
●
Set override operation setpoint [V]
●
Current supply air [m3/h] [l/s]
Extract air/Exhaust air damper
Extract air damper, status
●
Current damper position: Open/closed
●
Current extract air [m3/h] [l/s]
Shown at Belimo Mod-
bus damper motor
Damper motor, Modbus
●
Current damper setting [%]
●
Absolute position [Feedback]
●
Test run: Yes/No
●
Communication [Active] / [Inactive]
Shown at Belimo Mod-
bus damper motor
Shown only if modula-
ted recirculation is con-
figured
Damper motor, Modbus
●
Current damper setting [%]
●
Absolute position [Feedback]
●
Test run: Yes/No
●
Communication [Active] / [Inactive]
3005263-2015-08-20
Service level
42/52