2.2 Installation

2.3 Configuring

EN

 2

The module can be installed in any convenient for user place (mounting rail is recommended), where 

the following conditions are ensured:

• ambient temperature -20 ... 70 °C

• relative humidity 30% ... 85% (without condensation);

• protection against vertical falling water drops (IP 20).

If you are going to use some MB-GATEWAYs in the same LAN, you need to change their IP addresses. LAN 

cannot have more than one unit using the same IP address, thus for configuring of the MB-GATEWAY you 

need to connect it directly to the PC.

Step-by-step configuration:

1

 Apply static TCP/IP settings for the network interface card in the PC that will be used to connect the 

unit. These settings depend on the OS used, see the OS documentation:

•  IP  address  should  begin  with  192.168.0  and  end  with  number  1  to  254  except  51,  for  example: 

192.168.0.11

• Subnet mask: 255.255.255.0.

2

 Connect the power supply (included).

3

 Connect the MB-GATEWAY to the properly configured PC using UTP (RJ45) cable (included). If the 

connection does not work (the PC does not support Auto MDI-X), connect the PC and MB-GATEWAY to 

the switch.

4

 Enter the MB-GATEWAY IP address (the default one is 192.168.0.51) into the browser (Google Chro-

me is recommended) address bar.

5

 Each page is password protected. When you open the configuration page, you will be asked to en-

ter user name and password. Default user name is “admin”, password – “admin”. We recommend to change 

password for security. If you forget your login details you can restore the parameters to factory default 

settings (see “Restoring factory defaults”).

6

 If you performed the above steps properly, the MB-GATEWAY configuration page opens. Here you 

can select the language, set IP address, Modbus (RS485) baudrate, Modbus (RS485) parity, date and time, 

change user name and password, page theme, open the help file, air hand¬ling unit controller’s WEB 

page.

If you cannot connect to the device (have forgotten the password, IP address etc.), you always can restore 

the factory defaults. Steps of restoring the factory defaults:

1

 Turn off the power supply.

2

 Open the top flap.

3

 Holding down the button turn on the power supply.

4

 When you release the button, the factory defaults are restored 

(note: you will need to re-enter set-

tings).

Step-by-step firmware update:

1

 Download (http://salda.lt/lt/products/category/products/) the update FIRMWARE.BIN and save to 

the MicroSD root directory:

a. if you update using FTP client, you do not need to turn off the power supply;

2.5 Updating of the firmware using MicroSD card 

2.4 Restoring factory defaults

Содержание GAUMBGATEWAY001

Страница 1: ...A S Odensevej 76 DK 5550 Langeskov Tel 45 65 66 12 34 Fax 45 65 66 11 10 exhausto exhausto dk www exhausto dk Art no GAUMBGATEWAY001 P0101_BO_0001 Network Module MB gateway Technical manual 3005392 20...

Страница 2: ...e setting window 9 4 3 Fan speed setting window 10 4 4 Fault List window 11 4 5 Menu window 12 4 6 Settings window Set the BOOST function time 13 4 7 Settings window Set the desired CO2 level 14 4 8 S...

Страница 3: ...B MicroSD memory card 2 Sticker with a MAC address and fields for writing down connection settings 3 UTP cable 0 5 m 4 RS485 communication cable with RJ11 plugs 2 m 5 Adapter 6 Installation Manual EN...

Страница 4: ...0 51 into the browser Google Chro me is recommended address bar 5 Each page is password protected When you open the configuration page you will be asked to en ter user name and password Default user...

Страница 5: ...to the normal state 4 When the update is finished the file FIRMWARE BIN is automatically deleted Indications of the RJ45 connector LEDs Both LED indicators flashes slowly and synchronously MB GATEWAY...

Страница 6: ...ick to switch to the Italian language Click to open the control window of automatics The automatics is recognised automatically If parameters of the RS485 communication line are wrong or the device is...

Страница 7: ...ication line is set The date and time of MB GATEWAY module is set The user name of the MB GATEWAY module is set The password of the MB GATEWAY module is set The password of the MB GATEWAY module is re...

Страница 8: ...active Displays the date and time Displays the outdoor air temperature Displays the extract room air temperature Displays the supply air temperature Displays the extract air humidity I1 I4 I2 I5 I3 I...

Страница 9: ...rature setting Click to turn on off the ventilation Click to turn on off the BOOST function now it is active Click to turn on off the Stand by mode Click to open the Alarms list window It is displayed...

Страница 10: ...Click to return to the main window Click to activate the Stand by mode Click to turn on the fan speed 1 Click to turn on the fan speed 2 Click to turn on the fan speed 3 Click to turn on off the BOOS...

Страница 11: ...B2 EN B1 B2 I1 Meaning Plate heat exchanger frost protection function Fire alarm Dirty filter alarm Fans overheat alarm Low voltage DJT 100 temperature sensor alarm Exhaust air temperature sensor alar...

Страница 12: ...ck to open the settings window Click to open the status monitoring window Click to open the weekly schedule setting window Click to switch to the green theme Click to switch to the blue theme Click to...

Страница 13: ...The selection is active when the CO2 sensor is used currently inactive Click to open the night time cooling function settings window Click to open the date and time settings window Click to open the...

Страница 14: ...el 4 Number Function Click to return to the settings window Click to increase decrease the CO2 level setting Number Function Displays the desired CO2 level setting PPM I1 B1 B2 B3 EN B2 B3 I1 B1 The s...

Страница 15: ...oom air temperature setting Click to increase decrease the minimum outdoor air temperature setting Click to increase decrease the air change interval setting in hours B1 B2 B3 B4 B5 B6 B7 B8 B9 B10 4...

Страница 16: ...ck to increase decrease the month setting Click to increase decrease the year setting Click to increase decrease the hour setting Click to increase decrease the minute setting B1 B2 B3 B8 B4 B9 B5 B6...

Страница 17: ...unction Click to return to the settings window Click to reset the filter timer B1 B2 Number Function Displays the remaining filter time in hours Displays the set filter timer limit in hours Displays w...

Страница 18: ...circuit turned on off Set Point system temperature Extract air humidity Active system mode The state of the heater power circuit turned on off The state of the by pass valve The state of the stand by...

Страница 19: ...ick to delete the event Click to copy the event details B1 B2 B3 B13 B4 B5 B6 B12 Number Function Displays the event number 8 total events per day Displays the selected weekday Displays the hour of ev...

Страница 20: ...k to delete weekday events Click to paste day s events from clipboard B1 B4 B2 B3 Click to paste copied details of another event Click to decrease increase hour value Click to decrease increase minute...

Страница 21: ...imal representation of variable address o e value for writing request or amount for reading request when reading some consecu tive addresses Full Modbus request with CRC http address F request g http...

Страница 22: ...o 03 Modbus command Read Holding Registers o 2387 starting with address 9095 0x2387 o 0006 6 variables o delimiter o 01 write to a device that has an address of 01 o 10 Modbus command 16 0x10 Preset...

Отзывы: