Menu 2.4 - Temperature regulating units
2.4 Temp. reg. enheder
Varmegenv.
Eftervarmefl.
VP enhed
Køleenhed
Kølegenvinding
0.0
0.0
0.0
0.0
0.0
%
%
%
%
%
The menu shows the current:
● heat recovery
● Output of heating coil (if installed)
● Output of heat pump unit (if installed)
● Output of cooling unit (if installed)
● Cold recovery (0% or 100%)
Menu 2.5 - Pressure
2.5 Pressure
External pressure:
Supply air duct
Extract air duct
Filter pressure:
Outdoor air filter
Extract air filter
CCW exhaust
ALC pressure:
Extract air chamber
Supply air chamber
Differential pressure
0
0
0
0
0
0
0
0
Pa
Pa
Pa
Pa
Pa
Pa
Pa
Pa
The menu shows:
● external pressure in supply air and extract air duct (if MPT-DUCT installed)
● pressure loss across supply air and extract air filters
● pressure drop across CCW coil in exhaust duct
● current pressure readings for ALC
Menu 2.6 - Heating coil
NB
The menu displays depend on whether a water heating coil or an electric heating
coil is installed as a heating unit (see Menu 3.4 Accessories).
Water heating coil
2.6 Heating coil
Water heating coil:
Supply
Return
External return
Heat retention
Pump
25.0
15.0
15.0
0
Off
°C
°C
°C
%
The menu shows:
● supply water temperature
● return temperature
● external return water temperature (coldest)
● constant temperature - if the constant temperature function is active (speci-
fied as a percentage)
● pump - if the circulation pump in the heating cycle is in operation
Electric heating coil
Electric heating coil:
Power step total
Active power steps
Setpoint
TSA60/80
2.6 Heating coil
1
0
0.0
25.0
%
°C
The menu shows:
● number of power steps in heating coil
● Number of active power steps
● output of the modulating step
● internal temperature in electric heating coil control box
3005167-2022-02-02