 3001434-2006-09-01.fm

9/12

2.3

Installation

Before installation, read through item 2.3.1.

'

If the boilers are not connected to an electronic 

sequencer or management system we recommend 
the EXHAUSTO Relay Box ES12-EU-01 to interface 
a maximum of 4 boilers, use multiple relay boxes for 
more boilers. Please refer to the Instruction Manual 
on ES12-EU-01 for wiring details.

2.3.1 Dipswitch setting (fig. 9-A)

Before starting up the system, check that the 
dipswitch setting corresponds to the required operat-
ing mode.

Factory setting: All OFF

*) Must always be in OFF position if the extra pres-
sure differential switch (PDS) has not been con-
nected.

If the factory setting is to be changed, the black top 
plate must be removed to get access to the dipswitch 
block (see fig. 9).

1.

Remove the 4 serrated screws and lift the top 
plate off the PCB.

2.

Change the dipswitch setting.

Dip-
switch

Name

OFF

ON

1

MANUAL 
RESET

Automatic reset 
after mains drop-
out and draught 
fault

Manual reset 
after mains 
drop-out and 
draught fault

2

POST 
PURGE

No post-purge

3-minutes post-
purge

3

*)

PDS 
CHECK

No control indicat-
ing that the pres-
sure differential 
switch has been in 
position NC before 
starting up.

The pressure 
differential 
switch must be 
in position NC 
before starting 
up

9

Содержание EBC12 Series

Страница 1: ...EXHAUSTO A S Odensevej 76 DK 5550 Langeskov Tel 45 65 66 12 34 Fax 45 65 66 11 10 exhausto exhausto dk www exhausto dk 3001434 2006 09 01 fm Product Instruction EBC12 EU 01 GB...

Страница 2: ...ample 1 Voltage signal fig 5 5 2 2 3 Example 2 Voltage free contact fig 6 6 2 2 4 Example 3 Extra fail safe supervision with pressure differential switch fig 7 7 2 2 5 Example 4 Continuous chimney fan...

Страница 3: ...corresponding less than 80 flow When the boiler cuts out the chimney fan stops too However it is possible to select a 3 minute post run period by means of the POST PURGE dipswitch fig 1 H Alternative...

Страница 4: ...an be mounted in a box with a hole 2 mm in the bottom mainly to ensure cor rect reference pressure but also to prevent water penetration If the sensor is mounted to that insects have direct access to...

Страница 5: ...tion to the boiler automatic Connect the burner start signal L to termi nal 6 Loop terminals 7 and 14 The start signal to the burner will now come on terminal 15 Connect Neutral to terminal 4 Connect...

Страница 6: ...L1 2 Supply N 3 Supply PE 4 5 Boiler thermostat Opto coupler 10 230V 6 7 Boiler thermostat Opto coupler 10 230V 8 24V DC supply to voltage free contact boiler thermostat 9 0V DC supply to voltage fre...

Страница 7: ...connected to terminals 16 21 according to the instruc tions enclosed with the chimney fan The remaining terminals should be connected as in example 1 or 2 Below the connections of example 1 are shown...

Страница 8: ...E 4 5 Boiler thermostat Opto coupler 10 230V 6 7 Boiler thermostat Opto coupler 10 230V 8 24V DC supply to voltage free contact boiler thermostat 9 0V DC supply to voltage free contact boiler thermost...

Страница 9: ...g All OFF Must always be in OFF position if the extra pres sure differential switch PDS has not been con nected If the factory setting is to be changed the black top plate must be removed to get acces...

Страница 10: ...stabilised up down adjustment LEDs are not lit The current draught is shown on the display fig 10 D 3 Final setting of draught Check the draught on the boiler and adjust as above if required 4 Check...

Страница 11: ...wnwards regulation fig 11 E System fault 1 The natural draught in the chimney prevents downwards regulation to the required setpoint Check the setpoint setting 2 The probe is in an unfortunate positio...

Страница 12: ...exhausto co uk EXHAUSTO NORGE A S Lilleakerveien 4 N 0283 Oslo Tel 47 2412 4200 Fax 47 2412 4201 post exhausto no www exhausto no EXHAUSTO Inc 1200 Northmeadow Parkway Suite 180 Roswell GA 30076 USA T...

Отзывы: