![Exhausto BESB Series Скачать руководство пользователя страница 10](http://html1.mh-extra.com/html/exhausto/besb-series/besb-series_manual_2450162010.webp)
3004348_2020_06_11.fm
GB - BESB/FSB – Product information
10/82
1.4.1.2 FSB250-4-1EC, FSB315-4-1EC, BESB/FSB400-4-1ECog BESB/FSB500-4-1EC
Cabletype
Cables for control signals must be shielded.
Diagram
* Not supplied by EXHAUSTO.
Key to diagram
Leakage current
When operating the EC control converters have a leakage current of less than 3.5 mA.
The leakage current must be earthed, as there is a risk of the motor becoming live.
Fig. 10
Terminal
Signal description
100
10 V DC
101
0-10 VDC
102
0 V DC (chassis)
103
Direction of rotation
104
Start/Stop
105
0 V DC (chassis)
106
RS485 + (A)
107
RS485 - (B)
108
0 V DC (chassis)
11
Alarm C
12
Alarm NC
13
Alarm NO