XP125 INSTALLATION AND OPERATION MANUAL
Page 5
DC INPUTS (12 VDC - 108 VDC):
AC OUTPUTS:
LOW BATT / THERM BUZZER ;
OVER VOLTAGE PROTECTION:
UNDER VOLTAGE PROTECTION:
OVER TEMPERATURE PROTECTION:
a 3' non-terminated, two-
conductor power cord is provided. Insulation on the
negative (-)
conductor is black
and insulation on the
positive (+) conductor
is red
.
one NEMA-15 outlet (standard wall receptacle) is
located on the Front Panel.
produces an audible alarm if DC
input voltage falls to a level within 2% to 4% of the low limit of inverter,
or, if there is an over temperature condition.
If input voltage to the inverter
exceeds set limits, the inverter will immediately and without warning
shut off. When input voltage returns to normal range, the inverter will
immediately restart. Since high over voltages tend to have very fast
edges, the inverter must shut down quickly to protect itself. This kind
of fault usually occurs if the battery is suddenly disconnected from the
system and the battery charger continues to supply current.
When battery voltage falls to
within 2% to 4% of low line voltage, the LOW BATT / THERM buzzer
will sound. If the condition continues without reducing load to the
inverter or adding charge to the battery, the inverter will shut off.
When voltage rises to approximately 95% of nominal battery voltage,
the inverter will turn back on and the alarm condition will clear. The
inverter can be manually reset by cycling the on/off switch. This will
reset the protection circuitry and turn the inverter on at any voltage
above minimum voltage.
The inverter is also
.
.
.
.
S
tandard Features
2.0