20
INSTALLATION
excel HE -
Installation and Servicing
F
L
U
E
O
U
T
L
ET
80/125
Part No. Description
Quantity
C24
C28 C32
n/a
Maximum Flue Length (m)
16
12
8
201 548 Flue ext. 80/125
15
11
7
201 547 Terminal Vertical Roof 80/125
1
1
1
158 431 Weather Collar Pitched Roof
1
1
1
158 432 Weather Collar Flat Roof
1
1
1
201 550 90
o
Elbow kit (80/125)
4
4
4
201 551 45
o
Elbow kit (80/125)
4
4
4
201 184 Vertical Connector
1
1
1
201 549 Adaptor (60/100 - 80/125)
1
1
1
22 FLUE TERMINAL POSITION
610 mm
min.
ex7531
610 mm
min.
ex8389
*
*Flat Roof - 600mm
The terminal should be positioned so that products of
combustion can safely disperse at all times.
Pluming may occur at the termination so, where
possible, terminal positions where this could cause
a nuisance should be avoided.
Minimum dimensions are shown below
23 FLUE ARRANGEMENT
Note.
The equivalent flue length resistance of the 90
o
elbow kit
(80/125) is 1.5m and the 45
o
elbow kit (80/125) is 1.0m.
Terminal Position
Minimum Dimension
Directly below an opening,
air brick, windows, etc.
300 mm
Below plastic / painted gutters
300 mm
Painted surface
300 mm
Below eaves or balcony
500 mm