Ewert Energy Systems Orion BMS Скачать руководство пользователя страница 3

tested to verify that it is working properly. 

It is absolutely mandatory that 

the BMS have a direct means to turn off any and all charging sources.

 

3. 

Verify that the maximum cell voltage settings are properly configured. 

Double check that all the cell voltage settings on the “Cell Settings” tab of the 

BMS utility profile settings are correct. If the maximum cell voltage is too low 

that may cause this fault to set prematurely or under normal operation. 

4. 

Verify proper cell voltage wiring and check for wiring related faults. 

Certain subcodes can be caused by incorrectly wired cell voltage inputs (if the 

BMS is not receiving the proper voltages it can prevent the internal circuitry 

from operating properly). Typically an incorrectly wired (or damaged) cell input 

would show up as a secondary fault code (such as 

P0A04

 or 

P0AFA

). If any of 

these fault codes are actively set, they should be investigated first as they may 

help indicate the root cause for this fault being set. 

5. 

Manually verify the cell voltage in question. 

Using a handheld multimeter or voltage measurement device, manually verify 

the voltage of the cell that the BMS has identified as being too low. If the 

voltage measurement does not match what the BMS is reporting then there may 

either be an external wiring related issue or an issue internal to the BMS itself. 

Please see the “Incorrect Cell Voltage Readings” troubleshooting entry in the 

Troubleshooting Guide for more details on ways to diagnose a cell voltage 

reading incorrectly. 

6. 

Download the freeze frame for the fault code using the BMS Utility. 

The BMS will normally produce a freeze frame on the “Diagnostic Trouble 

Codes” screen in the BMS Utility when this fault code occurs that contains a 

comprehensive list of BMS data parameters at the time the fault occurred. 

It is 

strongly recommended that the freeze frame be downloaded from the 

BMS and saved to disk before the fault is cleared again

 as this data may 

assist in the future if further diagnostics are required. 

Additionally this freeze 

frame data may be requested by Technical Support if further assistance is 

required.  

NOTE: 

Only Fault Codes with a (F) next to them have freeze frame data 

available for download. If there is no (F) next to the fault, there is no stored 

freeze frame available and this step can be skipped. 

Steps to download the Freeze Frame: 

1) Connect to the BMS using the Orion BMS utility. 

2) Click the “Diagnostic Trouble Codes” tab at the top. 

 

Document Revision: 1.0 
Last Updated: 1/9/2018 

Ewert Energy Systems, Inc 

161 E. St Charles Rd. Carol Stream, IL 60188 

Phone: (630) 868-3173 

 

Отзывы: