EWELLY EW-802 Скачать руководство пользователя страница 2

Note: When the temperature difference is set at 0, the electric power is entered
           into the heating state.

Ewelly

220V/AC

Heating

Pump

High temp

.

Sensor

Low temp

.

Sensor

EW-MH106

Low 
water level 
detection

Water valve

Note: the output has a high voltage of 220V
Output load: 5A 220V/AC

Heating: When the instrument satisfies the following conditions: 

H

igh temperature zone temperature 

 "low temperature zone set temperature" + 

    "heating temperature difference"

;

Low temperature zone temperature 

 "low temperature zone set temperature" - "temperature difference",the "heating" relay is 

     absorbed and the "heating indicator" is ON.

Stop heating: When the low temperature zone temperature 

 "low temperature set temperature" or "high temperature zone temperature" 

 "low temperature set

      temperature" + "heating temperature difference". Then the "heating" relay is turned off and the "heating indicator" is turned off.

Pump operation: when the "high temperature zone temperature" - "low temperature zone temperature" 

the set "start-up temperature difference". "Pump" relay ON, 

     "pump indicator light" ON.

Pump stop: When "high temperature zone temperature" - "low temperature zone temperature" 

 setting of "stop pump temperature difference". The "water pump" 

      relay is OFF and the "water pump indicator" is OFF.

Automatic watering: When the water level is lower than the “low water level detection” position, the “watering valve” relay is closed, and the “LL” and “low temper-

     ature zone temperature” are displayed alternately. The “watering valve indicator” is ON.

Stop adding water: When the water level is higher than the “high water level detection”, the “watering valve” relay is OFF and the “watering valve indicator” is OFF.

Note: If water level detection is not required, the high and low water level detection and the water level common port can be shorted together.

Wiring Diagram

High
water level 
detection

Water level 
public port

Lights NO

.

Function

Setting

 

range Ex-factory 

Value

Unit

NO.1Indicator

NO.1.2 Indicator

NO.2 Indicator

NO.3 Indicator

NO.4 Indicator

Temperature

 

difference

start

-

up

Temperature 
difference

High temperature 
correction

Low temperature 
correction

 

Temp

.

difference

of

 

stopped

 

pump

+

1

5

0

1

20

-10

10

-10

10

5

5

0

2

0

Stop the pump
 temperature

1

temp

.

difference

started

-

1

Parameters for Procedure

NO.3.4 Indicator

Heating temperature
 difference

0

20

5

Feature

 

Descriptions

Failure

Causes

Precautions

No display when power 

is on.

Check if the power is broken or the 

thermostat failture. 

Check power supply and change fuse.

Check if the input voltage is right or 

change the thermostat with our distributor. 

Displaying but machine 

doesn't work 

The setting  temperature is lower than the 
present temperature.
The heat protector is open circuit because the 
pressure is over loads.

Reset the necessary controlling temperature.
Check the reasons for overload and overheating. 
After the trouble is solved, restart to work.

Displayed temperature is

unstable or there exists 

misplay.

The sensor is interfered; or poor wiring; 

or Together with other power cord bundle

or line damage. 

Separate sensor wiring with power cables 

or change shielded lines or check if the contact

is tight or not.

Measurement error between 
current temperature and 
displayed.

The installation position of the sensor is not 
correct; or the sensor's wiring is too long and
its resistance is over; or the wiring connected 
poor; or the sensor is damaged

All sensors should be corrected at their locations. 

Enlarge the cross section of the expanded wires. 

Make sure the wires sealed is good. or Change the 

sensor. 

Machine does not stop 
when the temperature
reaches.

The sensor is not correctly installed and cannot
measure the correct temperature. Compressor 
contactor fails.

Check if the sensor has accurately measured

the temperature or not. Change compressor 

contactor.

Relay work with overload 

“EH” or “EL” is displayed

Return difference value is too small or the 

setting for pressure protection is not correct.

The sensor is opened or shorted circuit. 

Reset and enlarge return difference value. Adjust
setting for pressure protection.

Check to see if the sensor wiring has good contact 
with coupling end or not.

Trouble shooting 

Warnings

1. Please read this product instruction carefully and connect input/output 

plugs of power & sensor to the  corresponding sockets strictly by following 

connection diagram, otherwise the usage & operations will   be affected. 

Check again to make sure there is no mistake. Tighten all the screw of 

connection plugs again, and then connect it to the power for running.
2. Keep away this product from moist or corrosive air and high magnetic 

field. Otherwise the normal  operation of this product will be affected.
.3. All our products have passed strict quality inspections before leaving 

factory. We provide one-year quality guarantee (which is limited to product 

itself ,and is not responsible for any other joint and several liability) period 

for this product.

Guangzhou Eliweli Autocontrol Tech. Co., Ltd.

 

http://www.eliweli.com

        

  If the products including but not limited to, the following is not the 

product itself quality problem caused by the damage, Install and use 

under the do not conform to the safe environment; That the load capacity 

is beyond the scope of product is allowed; Products by users to 

disassemble and change, change the internal components, etc.,We will 

not be so and damaged products provide a replacement and maintenance 

services, regardless of whether its in the quality assurance period; 

Meanwhile, we will not assume so direct or indirect losses caused by the 

liability to pay compensation.
        Product warranty date on the case is important basis of product 

quality assurance. Appeared including but not limited to full filling 

without permission, to change, to replace lost, damaged, scratched, dirty, 

and so on, we will not provide a replacement and maintenance services 

for these products.

    If you have any doubt or problem concerning the electronic 

temperature or humidity controller made by us, please contact our 

distributors and we will provide you high-quality after-sale services. 