Installing and Wiring the Thermostat
Ultra-Zone Internet Zone Thermostat Installation Guide, Release 1.0
9
Part No. 600-01100-100, Rev. 1
Figure 3
shows an example of a Dual-Stage Heat Pump HVAC system, with reversing
valve activated for heat or cool, connecting to an EWC base plate.
Figure 3
Dual-Stage Heat Pump HVAC Connections
Configuring Remote Sensors for the IZT-250
The Ultra-Zone Internet Zone Thermostats provide two remote (external) sensor ports.
This release supports Analog and Thermistor sensors (go to www.ewccontrols.com for
a complete list of supported sensors).
Analog
sensors convert temperature measurements as Fahrenheit degrees to a voltage
which can be sensed by the thermostat. Analog sensors are active devices which
require power from the thermostat. The Analog sensor is polarized and must be
connected as shown in
Table 4
.
Thermistor
sensors are passive devices which represent thermal measurements as
electrical resistance. Thermistors do not require power from the thermostat. The
Thermistor sensor is not polarized; either lead can be connected as shown in
Table 4
.
EWC Base Plate
Squ
a
re Hole
Wire
HVAC System
RH
Auxiliary
Heat
Fan
Control
Cool &
Heat
Power
G
C
1
W1
Compressor 1
(Single-Stage)
Y2
Y1
Reverse for
heat/cool
(Dual-Stage)
W2
Compressor 2
(Dual-Stage)