Evolution Controls EVO/ECM-Modbus Скачать руководство пользователя страница 41

©

E

v

o

lu

tion

 C

o

n

tr

o

ls

 I

n

c

10

-S

e

p

t-

2020

 

 

 
 

                                      EVO/

™ECM-Modbus RTU 

Series 2

                          

Page 38

 

Application Guide

 

 

©2020 All Rights Reserved 

Evolution Controls Inc. 

San Diego, CA USA

 

 

   

3.

 

Configure the gateway’s BACnet

 IP port. 

Obtain and configure the gateways’ BACnet 

device instances. Each gateway should have its 

unique BACnet device instance number in the automation network. Select the 

System 

Setup

>

BACnet IP Port

 to enter the 

Device Instance

 for each gateway. The default UDP 

port for BACnet traffic is 47808 (0xBAC0) but depending on the project specification other 
ports are also possible. You may also modify the 

Device Object

 

Name

Device Description

 

and 

Device Location

 to make the gateways identifiable in the automation network. 

 

 

 
The number of allocated 

Input Objects

Output Objects

 and 

Value Objects

 are set 

automatically by the selected mapping file discussed in the 

Modbus to BACnet Integration 

Procedure

 section below. 

 

4.

 

Configu

re the gateway’s Modbus port

 

Select 

Modbus

>

Modbus RTU Setup

>

Local Device

 tab to set up the Modbus Port as shown 

here. The 

Baud Rate

Poll Rate

Timeout

 and 

Starting

 address are set automatically by the 

selected mapping file discussed in the 

Modbus to BACnet Integration Procedure

 section 

below. 

 

Содержание EVO/ECM-Modbus

Страница 1: ...ontrols Inc 10 Sept 2020 CONTROLS INC EVO ECM Modbus EVO ECM Modbus RTU Series 2 Voice 858 748 7359 Application Guide Fax 858 679 3365 2020 All Rights Reserved Evolution Controls Inc San Diego CA USA...

Страница 2: ...Motor 4 Out 12 Register 6 Motor 1 RPM 12 Register 7 Motor 2 RPM 12 Register 8 Motor 3 RPM 12 Register 9 Motor 4 RPM 12 Register 10 Motor 1 Default Out 13 Register 11 Motor 2 Default Out 13 Register 1...

Страница 3: ...ple Registers Command 16 21 Read Multiple Coil Registers Command 01 22 Write Single Coil Register Command 05 23 ADDRESSING 24 INTEGRATION 26 BACnet IP 26 Modbus to BACnet Gateway 27 BACnet Mapping 28...

Страница 4: ...on off monitor each motor s RPM and control status and set default values used during power up and communications interruptions A four conductor low voltage control cable connects each motor to the RT...

Страница 5: ...Evolution Controls Inc 10 Sept 2020 EVO ECM Modbus RTU Series 2 Page 2 Application Guide 2020 All Rights Reserved Evolution Controls Inc San Diego CA USA Notes...

Страница 6: ...building codes To reduce EMI electro magnetic interference tightly fasten the control mounting posts to an earthed metal surface of the enclosure Ensure good electrical contact between the mounting p...

Страница 7: ...e 2020 All Rights Reserved Evolution Controls Inc San Diego CA USA Enclosure These drawings detail the minimum inside floor and face dimensions for a suitable enclosure 1 20 2 20 3 58 4 25 1 00 0 20 0...

Страница 8: ...or use an impedance altering means to provide line bias These masters must be placed at the end of the line When possible placing the Modbus RTU master in the center of the trunk improves application...

Страница 9: ...y to receive a reply from the RTU The EVO ECM Modbus reply is very fast Some Masters especially those where turn around is controlled over a higher level network server architecture cannot turn around...

Страница 10: ...g The pneumatic bench tool can be used in the field and is preferred over a hand operated tool 0 10 VDC Motor Output The length of the 0 10 VDC motor control cable is more limited by the line loss and...

Страница 11: ...gisters Each coil is a bit that can be accessed individually The two additional bits are for setting the controller to write defaults to dynamic registers and to reset the controller The chart below d...

Страница 12: ...he data is available when the RTU is powered up Default values are copied to their respective dynamic registers on RTU power up on RTU reset or when a communications timeout occurs Configuration Regis...

Страница 13: ...igh RPM limits If the associated bit is clear 0 the associated motor RPM is between the low and high RPM limits When a motor is turned off the RPM Alarm bit is cleared The alarm bit is held clear for...

Страница 14: ...When the Modbus RTU Master sets the reset flag the EVO ECM Modbus RTU acknowledges the command then resets The reset clears 0 the Reset Flag and sets the Motor On Offs and Motor Outs to their default...

Страница 15: ...r 4 Motor 3 Out See Register 2 description Register 5 Motor 4 Out See register 2 description Register 6 Motor 1 RPM The EVO ECM Modbus RTU reads commutator pulses from ECM motor 1 The RTU integrates t...

Страница 16: ...tor 2 Default Out See register 10 description Register 12 Motor 3 Default Out See register 10 description Register 13 Motor 4 Default Out See register 10 description Register 14 Configurations Low Byt...

Страница 17: ...tiple registers 06 command to be issued to a group of EVO ECM Modbus RTUs None of these RTUs issue a reply to the Modbus Master since all RTUs in the group would try to reply at the same time Some Mod...

Страница 18: ...essage Delay At the end of a transaction the RTU immediately listens for new data In some applications the line may ring or have other noise Setting this bit causes the RTU to wait for three byte time...

Страница 19: ...n Register 14 in one RTU in the group should be set to provide the reply Each RTU may have two group addresses allowing overlap of group functions Register 16 Group 2 Address Group addressing allows a...

Страница 20: ...on Register 18 Baud Rate Baud Rate The EVO ECM Modbus RTU can be configured to one of six different baud rates The Modbus Master should NEVER write to this register during normal operation Only write...

Страница 21: ...imit Register 25 Motor 3 High RPM Limit Register 26 Motor 4 High RPM Limit See Register 19 Motor 1 High RPM Limit When Motor 1 RPM increases above this limit and the motor has been commanded on for at...

Страница 22: ...tarting register is two bytes long The value must be 00 00 when addressing an EVO ECM Modbus RTU The number of registers is two bytes in length The high byte is always 00 The low byte is an integer be...

Страница 23: ...is two bytes long The high byte is 00 the low byte is an integer within the range of valid register Registers 1 5 are dynamic data registers Registers 10 14 are default data registers Registers 15 and...

Страница 24: ...address 0 query All EVO ECM Modbus RTUs process the write but none reply The command code is 16 The EVO ECM Modbus RTU only responds to a query for the first five registers The register number is two...

Страница 25: ...The command code is 01 one byte The starting register is two bytes long The value must be 00 00 when addressing an EVO ECM Modbus RTU The number of registers is two bytes in length The high byte is a...

Страница 26: ...n address 0 query All EVO ECM Modbus RTUs process the write but none reply The command code is 05 The register number is two bytes long The high byte is 00 the low byte is an integer within the range...

Страница 27: ...Modbus RTU Master uses this address when communicating with only that RTU Group Address 1 The Modbus RTU Master may communicate with a group of EVO ECM Modbus RTUs having the same group1 address None...

Страница 28: ...Evolution Controls Inc 10 Sept 2020 EVO ECM Modbus RTU Series 2 Page 25 Application Guide 2020 All Rights Reserved Evolution Controls Inc San Diego CA USA Notes...

Страница 29: ...bus RTU controllers can be integrated to a BACnet building automation network through Modbus to BACnet gateways to operate in response to other subsystems The gateway directs the data flow back and fo...

Страница 30: ...e must first be uploaded to a gateway to provide the information for the connections The BACnet building control network can then act upon the registers through the discovered BACnet objects A set of...

Страница 31: ...Motor 3 Alarm Status 3 R Coil 8 Motor 4 Alarm Status 4 R Coil 15 Reset Comm Time out Flag 5 R W Coil 16 Reset 6 R W Reg 2 Motor 1 Fan Output 1 R W Reg 3 Motor 2 Fan Output 2 R W Reg 4 Motor 3 Fan Out...

Страница 32: ...to the Babel Buster SPX User Guide to configure the settings in the gateway 1 Set Modbus line conditioning Disable RS485 line biasing EVO ECM Modbus RTU has internal failsafe biasing Enable terminati...

Страница 33: ...s to access the gateway website to configure its network settings the first time A Adding a route on your PC If your PC is on the network but the network is not 10 0 0 0 domain you will need to add a...

Страница 34: ...lution Controls Inc San Diego CA USA 5 Open an Internet browser and enter 10 0 0 101 in the address bar and press Enter 6 The browser will access and display the embedded website in the gateway 7 Clic...

Страница 35: ...TU Series 2 Page 32 Application Guide 2020 All Rights Reserved Evolution Controls Inc San Diego CA USA 9 Enter the static IP address Subnet Mask and Network Gateway address then click Change IP button...

Страница 36: ...is not available you will need to change your PC s IP address to access the gateway s website to configure its network settings 1 Connect an ethernet cable directly between the PC s network port and...

Страница 37: ...eserved Evolution Controls Inc San Diego CA USA 4 In the Properties dialog select Internet Protocol Version 4 TCP IPv4 and click the Properties button 5 Record the settings in this dialog You will nee...

Страница 38: ...iego CA USA address subnet mask and Default Gateway in the 10 0 0 0 domain as shown below and click the OK button to close the dialog 6 Click the OK button to close the Properties dialog 7 Open an Int...

Страница 39: ...ECM Modbus RTU Series 2 Page 36 Application Guide 2020 All Rights Reserved Evolution Controls Inc San Diego CA USA 9 Click the System Setup tab The default password is admin for username system 10 Sel...

Страница 40: ...ateway address then click Change IP button 12 Wait until the progress indicator stops spinning 13 Power cycle the gateway and wait until boot up is complete The new IP address is now in use 14 Follow...

Страница 41: ...ding on the project specification other ports are also possible You may also modify the Device Object Name Device Description and Device Location to make the gateways identifiable in the automation ne...

Страница 42: ...Evolution Controls Inc 10 Sept 2020 EVO ECM Modbus RTU Series 2 Page 39 Application Guide 2020 All Rights Reserved Evolution Controls Inc San Diego CA USA...

Страница 43: ...User Guide for details The EVO ECM Modbus RTU addresses in the Modbus trunk must be sequentially incremented from 1 to the number of controllers in the trunk and communication rate must be 38400 Baud...

Страница 44: ...eserved Evolution Controls Inc San Diego CA USA 3 Click the Upload button to upload the selected file to the gateway in the Config File Web page 4 The uploading is complete when the progress indicator...

Страница 45: ...ation Guide 2020 All Rights Reserved Evolution Controls Inc San Diego CA USA 5 After the uploading is completed select the uploaded file in the Local file directory 6 Press the Load button to set the...

Страница 46: ...tton so that the gateway boots up running the correct file after a power cycle or Restart 3 Discover objects in BACnet network The EVO Modbus controller is now ready to be integrated into the BACnet n...

Страница 47: ...Evolution Controls Inc 10 Sept 2020 EVO ECM Modbus RTU Series 2 Page 44 Application Guide 2020 All Rights Reserved Evolution Controls Inc San Diego CA USA...

Страница 48: ...ower and Modbus network are not yet available or at the factory without the need to connect power or making a Modbus connection The EVO TMModbus Configurator a PC software reads the default configurat...

Страница 49: ...EVO ECM Modbus RTU Series 2 Page 46 Application Guide 2020 All Rights Reserved Evolution Controls Inc San Diego CA USA Please refer to the EVO Modbus Configuration User Guide and EVO Modbus Excel Conf...

Страница 50: ...t 7 8 Motor 4 Alarm 0 Norm 1 Alarm High Byte Status Bit 0 9 External Command Flag 0 External Access 1 No Ext Access A global command or reset clears this Flag Bit 1 10 Not Used 0 These Flags are clear...

Страница 51: ...mic integer 0 1500 Updates every 833 milliseconds Y Y High Byte Register 9 Motor 4 RPM Low Byte Dynamic integer 0 1500 Updates every 833 milliseconds Y Y High Byte Register 10 Motor 1 Flow Index Low B...

Страница 52: ...5 22 Not Used Bit 6 23 Group 1 Reply 0 No Reply 1 Reply Set flag causes the respective controller to reply to a group command Bit 7 24 Group 2 Reply 0 No Reply 1 Reply High Byte EEPROM Configuration...

Страница 53: ...rite only 0 s Register 19 Motor 1 Low RPM Limit Low Byte EEPROM V1 2 Above Integer 0 1500 Set to 0 to disable alarm Y Y High Byte Register 20 Motor 2 Low RPM Limit Low Byte EEPROM V1 2 Above Integer 0...

Отзывы: