Содержание PASRW360S-PS-BP

Страница 1: ......

Страница 2: ...Mode Selection ______________________________________________________________________________________ 12 5 4 Target Temperature Setting ________________________________________________________________...

Страница 3: ...atest technology in corrosion protection allowing your new heat pump to maintain it s high efficiency for many years to come The corrugated louvered fin extends the heat exchange surface resulting in...

Страница 4: ...e unit Installation repair or relocations must be done by a fully qualified person and not by the customer If done incorrectly it may cause fire electric shock water leakage and other hazards For unit...

Страница 5: ...ating and chilling applications Functions Heating Cooling Smart defrost Auto Protection Multiple Module Control Automatic Reset for Partial Failure Auto Alert Remote Control Heat Pump Protection Water...

Страница 6: ...ubject to drawings of the heat pump Packing Size L x W x H Subject to data on the package Net Weight Subject to data on the nameplate Gross Weight Subject to data on the package Cooling outdoor temper...

Страница 7: ...orklift can be used to lift the unit with a wooden pallet at the bottom 4 2 Selecting an Installation Location The unit can be installed in any place outdoors which will be able to support the weight...

Страница 8: ...made The pipe must be tested by pressure separately DO NOT test it together with the unit There must be an expansion tank on the top point of the water loop and the water level inside the tank must be...

Страница 9: ...f there are objects stacked around the unit their height should be at least 400mm lower than the top of the unit When installed in a small room measures should be taken to prevent leakage of the refri...

Страница 10: ...e power supply terminals in the controlling box Then connect the 3 signal wire plugs of the wire controller and main controller If an external water pump is required please insert the power supply wir...

Страница 11: ...on of failure The gas gauge can be connected to the check valve to see the high pressure or low pressure of the system during trial running Trial Running Start the heat pump by pressing the UP or DOWN...

Страница 12: ...unction setting interface status parameter failure time 7 Indicating that the unit is powered on 8 Indicates if the unit is in heating or cooling mode 9 Display Circle Operating status Blue cooling mo...

Страница 13: ...om the top of the controller 5 6 Setting a Timer After pressing the Timer button from the main interface select from Temp Timer or Power Timer 5 6 1 Temp Timer This function enabled time sharing tempe...

Страница 14: ...Unit Status Running Status See below image Unit Status Enter the password 22 to inquire the unit status parameter Press one of the 4 buttons to inquire the relevant parameters Running Status Screen Un...

Страница 15: ...for the electricity status is recorded the outage status will not be saved The value of the abscissa indicates the time from the point on the curve to the current time point The leftmost point on the...

Страница 16: ...erating circuit for any failure Syst1 Low Pressure Prot E12 The low voltage switch of the system is disconnected Inspect System 1 voltage switch and refrigerating circuit for any failure Syst2 Low Pre...

Страница 17: ...lectric heating overheat protection switch is disconnected Inspect whether the electric heating is under operation condition of over 150 C for a long time Syst1 User Side Antifreezing Prot 3 E171 The...

Страница 18: ...e temperature sensor Inspect and replace System 2 exhaust temperature sensor Syst2 Low Pressure Sensor Fault PP21 Open circuit or short circuit of the sensor Inspect and replace System 2 low voltage s...

Страница 19: ...t is too large Check if the system 1 fan rotor is locked Fan 1 Overcurrent Prot F105 System 1 fan running current is too large Check if the system 1 fan rotor is locked Fan 1 Over Temp Prot F106 Syste...

Страница 20: ...19 EvoHeat Evo Command Manual 7 Controller Interface Diagrams 7 1 Wire Control Interface Diagram Definition 7 2 Controller Interface Diagrams Definitions...

Страница 21: ...20 EvoHeat Evo Command Manual...

Страница 22: ...vo Command Manual Note 1 JP13_1 represents 12V 485_A1 485_B1 GND on the JP13 terminal 2 JP13_2 represents 12V 485_A2 485_B2 GND on the JP13 terminal 3 JP13_3 represents 12V 485_A3 485_B3 GND on the JP...

Страница 23: ...1 EVI electronic expansion valve 26 AI DI26 System 2 suction temperature 80 CN6 System 2 EVI electronic expansion valve 27 AI DI27 No use 81 CN7 No use 28 AI DI28 No use 82 CN8 No use 29 AI DI29 Syst...

Страница 24: ...ndled separately from domestic waste and must be taken to a recycling centre for electric and electronic devices or handed back to the dealer when purchasing an equivalent appliance Directive 2002 95...

Страница 25: ...148A 2 x 50mm2 50mm2 225A 148 186A 2 x 70mm2 70mm2 250A 186 224A 2 x 95mm2 95mm2 280A Three Phase Unit Nameplate Maximum Current Phase Line Earth Line MCB Creepage Protector Signal Line 10A 3 x 1 5mm...