3.4 Swimming Pool Heat Pumps Plumbing 

Condensation: Since the Heat pump cools down the air about 4 -5

 

, water may condense on 

the fins of the horseshoe shaped evaporator. If the relative humidity is very high, this could 
be as much as several litres an hour. The water will run down the fins into the basepan and 
drain out through the barbed plastic condensation drain fitting on the side of the basepan. 
This fitting is designed to accept 20mm clear vinyl tubing which can be pushed on by hand 
and run to a suitable drain. It is easy to mistake the condensation for a water leak inside the 
unit. 

NB: A quick way to verify that the water is condensation is to shut off the unit  and keep the 
pool pump running. If the water stops running out of the basepan, it is condensation. 

AN EVEN QUICKER WAY IS to TEST THE DRAIN WATER FOR CHLORINE - if the is no 
chlorine present, then it's condensation. 

3.INSTALLATION AND  CONNECTION

5

To   pool

From pump

PVC COUPLER
RECOMMENDED(Provided)

CONDENSATION
DRAIN
BARB FTG

The Swimming Pool Heat Pumps exclusive rated flow titanium heat exchanger requires no 
special plumbing arrangements except bypass(please set the flow rate according to the 
nameplate). The water pressure drop is less than 10kPa  at max. Flow rate. Since there is no 
residual heat or flame Temperatures, The unit does not need copper heat sink piping. PVC  
pipe can be run straight into the unit.

Location: Connect the unit in the pool pump discharge (return) line downstream of all filter and 
pool pumps, and upstream of any chlorinators, ozonators or chemical pumps.

Standard model have slip glue fittings which accept  32mm or 50 mm PVC pipe for connection 
to the pool or spa filtration piping. By using a 50 NB to 40NB you can plumb 40NB 

Give serious consideration to adding a quick coupler fitting at the unit inlet and outlet to allow 
easy draining of unit for winterizing and to provide easier access should servicing be required. 

Содержание Fusion 13

Страница 1: ......

Страница 2: ...3 Location minimum clearances 3 4 Swimming Pool Heat Pumps Plumbing 3 5 Swimming Pool Heat Pumps Electrical Wiring 3 6 Initial Start up of the Unit 4 Usage and Operation 4 1 Function of the controlle...

Страница 3: ...cording to the recommended time and frequency as stated in this manual Use genuine standard spare parts only Failure to comply with these recommendations will invalidate the warranty Swimming Pool Hea...

Страница 4: ...2 2 The dimensions for Swimming Pool Heat Pump Unit 2 SPECIFICATION 2 Unit mm Fusion 9 13 98 956 602 976 Water outlet 1 5 inch 344 372 545 350 Water inlet 1 5 inch...

Страница 5: ...2 2 The dimensions for Swimming Pool Heat Pump Unit 2 SPECIFICATION 2 Unit mm Fusion 17 Water inlet 1 5 inch Water outlet 1 5 inch...

Страница 6: ...me 1 Open valve and charge water 2 Make sure that the pump and the water in pipe have been filled with water 3 Close the valve and start the unit ATTN It is necessary that the water in pipe is higher...

Страница 7: ...talling the heat pump no greater than 7 5 meters away from the water s edge due to heat loss from the piping If you do not have a location with these suggested clearances please contact our EvoHeat Te...

Страница 8: ...then it s condensation 3 INSTALLATION AND CONNECTION 5 To pool From pump PVC COUPLER RECOMMENDED Provided CONDENSATION DRAIN BARB FTG The Swimming Pool Heat Pumps exclusive rated flow titanium heat ex...

Страница 9: ...me Delay The unit is equipped with a 3 minute built in solid state restart delay included to protect control circuit components and to eliminate restart cycling and contactor chatter This time delay w...

Страница 10: ...y to turn on off the unit Up Down Timer on indicator Timer off indicator Key Key name Key function LED display Press this key to select the upward option or increase the parameter value Press this key...

Страница 11: ...is no operation for 5s system would remember parameter setting and back to the main interface In the main interface press for 2s to see the outlet temp The parameter flashes and the display returns t...

Страница 12: ...unit is in alarming state the key lock can be removed automaticly 4 2 3 Mode switch p In the main interface press and for 0 5s can set the mode press or to change the current mode you can switch diffe...

Страница 13: ...can check the current error codes list by pressing or key You can refer to the malfunction table to find out the failure cause and solution For example Water inlet temp Sensor failure 4 3 Parameter t...

Страница 14: ...10 4 4 Malfunction Table 4 USAGE...

Страница 15: ...e energy The operation pressure of the refrigerant system should only be serviced by a certified technician Discharge all water in the water pump and water system so that freezing of the water in the...

Страница 16: ...ater pump 220 230VAC OUT4 High speed of fan motor 220 230VAC OUT3 OUT1 No Symbol Meaning 4way valve 220 230VAC Compressor of system1 220 230VAC NET GND 12V Wire controller DI01 GND On Off Switch input...

Страница 17: ...parately from domestic waste must be taken to a recycling centre for electric and electronic devices or handed back to the dealer when purchasing an equivalent appliance 6 Directive 2002 95 EC RoHs Th...

Страница 18: ...line MCB Creepage protector Signal line 2 n 0 5mm Nameplate maximum current Earth line No more than 10A 20A 32A 40A 40A 63A 80A 100A 125A 160A 225A 250A 280A 2 1 5mm 2 2 5mm 2 4mm 2 6mm 2 10mm 2 16mm...

Страница 19: ...ustries d When a unit is installed by an unqualified person e Where a unit is incorrectly installed f When failure occurs due to improper or faulty installation g Failure due to improper maintenance r...

Страница 20: ..._______________________ Email _________________________________________________________________________ Please tell us about which EvoHeat product you bought who you bought it from and what you will b...

Страница 21: ...Code 20151212 0003...

Отзывы: