background image

P

 

a g

 

e

 |

26

 

 Repairs to sealed components 

1) During repairs to sealed components, all electrical supplies shall be disconnected from the equipment

being worked upon prior to any removal of sealed covers, etc. If it is necessary to have an electrical supply to

equipment during servicing, then a permanently operating form of leak detection shall be located at the

most critical point to warn of a potentially hazardous situation.

2) Particular attention shall be paid to the following to ensure that by working on electrical components, the

casing is not altered in such a way that the level of protection is affected. This shall include damage to

cables, excessive number of connections, terminals not made to original specification, damage to seals,

incorrect fitting of glands, etc.

Ensure that apparatus is mounted securely. 

Ensure that seals or sealing materials have not degraded such that they no longer serve the purpose of 

preventing the ingress of flammable atmospheres. Replacement parts shall be in accordance with the 

manufacturer's specifications. 

NOTE: The use of silicon sealant may inhibit the effectiveness of some types of leak detection equipment. 

Intrinsically safe components do not have to be isolated prior to 

Repair to intrinsically safe components 

Do not apply any permanent inductive or capacitance loads to the circuit without ensuring that this will not 

exceed the permissible voltage and current permitted for the equipment in use. 

Intrinsically safe components are the only types that can be worked on while live in the presence of a 

flammable atmosphere. The test apparatus shall be at the correct rating. Replace components only with 

parts specified by the manufacturer. Other parts may result in the ignition of refrigerant in the atmosphere 

from a leak. 

Detection of flammable refrigerants 

Under no circumstances shall potential sources of ignition be used in the searching for or detection of 

refrigerant leaks. A halide torch (or any other detector using a naked flame) shall not be used. 

Leak detection methods 

The following leak detection methods are deemed acceptable for systems containing flammable refrigerants. 

Electronic leak detectors shall be used to detect flammable refrigerants, but the sensitivity may not be 

adequate, or may need re-calibration. (Detection equipment shall be calibrated in a refrigerant-free area.) 

Ensure that the detector is not a potential source of ignition and is suitable for the refrigerant used. Leak 

detection equipment shall be set at a percentage of the LFL of the refrigerant and shall be calibrated to the 

refrigerant employed and the appropriate percentage of gas (25 % maximum) is confirmed. 

Leak detection fluids are suitable for use with most refrigerants but the use of detergents containing chlorine 

shall be avoided as the chlorine may react with the refrigerant and corrode the copper pipe-work. 

If a leak is suspected, all naked flames shall be removed/ extinguished. 

If a leakage of refrigerant is found which requires brazing, all of the refrigerant shall be recovered from the 

system, or isolated (by means of shut off valves) in a part of the system remote from the leak. Oxygen free 

nitrogen (OFN) shall then be purged through the system both before and during the brazing process. 

Содержание EVO Force-i19

Страница 1: ...P a g e 1...

Страница 2: ...uction 11 4 2 Controller Functions 12 4 2 1 Start up and Shutdown 12 4 2 2 Mode Switch and Target Temperature Setting 12 4 2 3 Clock Setting 13 4 2 4 Silent Silent Timing Setting 15 4 2 5 Fault Histor...

Страница 3: ...ply with these recommendations will invalidate the warranty The Force i series has the following characteristics Durable The heat exchanger is made of PVC Titanium tubing with can withstand prolonged...

Страница 4: ...30 m2 Spaces where refrigerant pipes shall be compliance with national gas regulations Servicing shall be performed only as recommended by the manufacturer The appliance shall be stored in a well ven...

Страница 5: ...95 EC RoHs This product is compliant with directive 2002 95 EC RoHs concerning restrictions for the use of harmful substances in electric and electronic devices The unit CANNOT be installed near flamm...

Страница 6: ...P a g e 6 2 Unit Dimensions Force i19 Force i24 Force i28 3 40 40 40 40...

Страница 7: ...e user or the installer ATTENTION Please follow these steps when using for the first time 1 Open valve and charge water 2 Make sure that the pump and the water in pipe have been filled with water 3 Cl...

Страница 8: ...urthermore EvoHeat recommend installing the heat pump no greater than 7 5 meters away from the water s edge due to heat loss from the piping If you do not have a location with these suggested clearanc...

Страница 9: ...quick coupler fitting at the unit inlet and outlet to allow easy draining of unit for winterizing and to provide easier access should servicing be required Since the Heat pump cools down the air about...

Страница 10: ...e Unit NOTE For the unit to heat the pool or spa the filter pump must be running to circulate water through the heat exchanger Start up Procedure After installation is completed you should follow thes...

Страница 11: ...P a g e 11 4 Usage and Operation Instructions 4 1 Controller Introduction...

Страница 12: ...P a g e 12 4 2 Controller Functions 4 2 1 Start up and Shutdown 4 2 2 Mode Switch and Target Temperature Setting MODE SWITCH TARGET TEMP SETTING...

Страница 13: ...P a g e 13 4 2 3 Clock Setting 4 2 3 1 Time Setting...

Страница 14: ...P a g e 14 4 2 3 2 Timing Setting...

Страница 15: ...P a g e 15 4 2 4 Silent Silent Timing Setting 4 2 4 1 The Silent Button...

Страница 16: ...P a g e 16 4 2 4 2 Timing Silent Function Setting...

Страница 17: ...on any interface until you hear a long beep Then you will enter the calibration interface Click to start calibration When you hear the beep again you will finish the calibration and exit The wire cont...

Страница 18: ...P a g e 18 4 2 7 Temperature Curve In the main interface click the curve display button It will display as follows 4 2 7 1 The average power curve...

Страница 19: ...the pipe water flow and whether water system is jammed or not Low temperature protection Non The environment temp is low Comp Overcurrent Prot E051 The compressor is overload Check whether the system...

Страница 20: ...ge measurement Inv Sampling Volt F11 The input voltage sampling fault Check and adjust the current measurement Comm Err DSP PFC F12 DSP and PFC connect fault Check the communication connection Input O...

Страница 21: ...get temperature set point 27 C Adjustable Heating the target temperature set point 27 C Adjustable Automatic target temperature set point 27 C Adjustable 4 4 Interface Drawing 1 Wire Control Interface...

Страница 22: ...ut temperature input 14 AI DI07 Water output temperature input 15 AI DI08 System fan coil temperature input 16 AI DI09 Ambient temperature input 17 AI DI10 Mode switch input 18 AI DI11 Master slave ma...

Страница 23: ...larly Check the water inlet outlets often for leaks You should avoid the condition of no water or air entering into the system as this will influence unit s performance and reliability You should clea...

Страница 24: ...to ensure the technician is aware of potentially flammable atmospheres Ensure that the leak detection equipment being used is suitable for use with flammable refrigerants i e non sparking adequately...

Страница 25: ...ble shall be corrected Refrigeration pipe or components are installed in a position where they are unlikely to be exposed to any substance which may corrode refrigerant containing components unless th...

Страница 26: ...hile live in the presence of a flammable atmosphere The test apparatus shall be at the correct rating Replace components only with parts specified by the manufacturer Other parts may result in the ign...

Страница 27: ...t has been de commissioned and emptied of refrigerant The label shall be dated and signed Ensure that there are labels on the equipment stating the equipment contains flammable refrigerant Recovery Wh...

Страница 28: ...ylinders conform to the appropriate standards d Pump down refrigerant system if possible e If a vacuum is not possible make a manifold so that refrigerant can be removed from various parts of the syst...

Страница 29: ...line MCB Creepage protector Signal line No more than 10A 3 x 1 5mm2 1 5mm2 20A 30mA less than 0 1 sec n x 0 5mm2 10 16A 3 x 2 5mm2 2 5mm2 32A 30mA less than 0 1 sec 16 25A 3 x 4mm2 4mm2 40A 30mA less...

Страница 30: ...Instructions h No Fault Found service calls where the perceived problem is explained within the i Costs associated with delivery handling freighting or damage to the product in transit 5 If warranty...

Страница 31: ...P a g e 31 7 1 Warranty Registration x...

Отзывы: