Chlorine
Heavy greenish-yellow gas with a pungent, irritating odour. Highly toxic and
corrosive.
Chlorine is used in chemical industry and for bleaching and desinfection.
Chemical formula
Cl
2
Molar weight
70.9
Relative gas density (to air)
2.44
Conversion
1 ppm = 2.90 mg/m
3
Boiling point
-34.04 °C
Odour
Pungent, irritating smell
Odour detection threshold
Some individuals will not notice the
odour until it is more than three times
the exposure limit.
Hazards
Nonflammable, but a strong oxidizer,
may react explosively with many
common chemicals.
Potent irritant of the eyes, mucous
membrane, skin and respiratory system.
Death can occur within minutes after
exposure of 400 to 1000 ppm. Chronic
exposure of 1 ppm can cause a
moderate, but permanent, reduction in
pulmonary function.
Exposure limits (Directive
2006/15/EC)
TWA
not specified
STEL
1.5 mg/m
3
/0.5 ppm
IDLH (NIOSH)
10 ppm
Conversion of ppm to mg/m
3
is calculated for 25°C and 1 atm.
Installation guidelines
(See Installation and connections section for general information.)
Chlorine is considerably heavier than air and tends to sink. The sensor should be
placed at ca. 15 cm above the floor.
Calibration
E2618-Cl2 transmitters have been calibrated by Manufacturer with standard gas
mixtures before delivery. Provided that the sensor is used under moderate
conditions,the recommended interval for field recalibration is 6 months. Please
contact your dealer for more information.
Maintenance
Do not perform any maintenance operation with the power on.
Clean the device with soft damp cloth. Do not use any abrasive cleaning agents. Do
not immerse the device into water or any cleaning media.
Delivery set
–Transmitter E2618 (wall mount or duct mount version)
– Mounting accessories:
4 screws with plastic dowels for wall mount version
rubber flange for duct mount version.
fixing clamp for remote probe version
E2618-Cl2_UM_EN
Rev 16.07.2019
Specifications
Sensor type
electrochemical cell
Sampling method
diffusion
Typical detection range
0...10 ppm
Maximum overload
100 ppm
Resolution / digital unit
0.1 ppm
Response time T90
<60s
Sensor lifetime
> 2 years
Calibration interval
6 months
Signal update
every 1 second
Load resistance
R
L
< (Us - 2 V) / 22 mA for 4-20 mA
R
L
> 250 kOhm for 0-10 V mode
Digital interface
RS485, Modbus RTU protocol
no galvanic isolation
Power supply options
11...30 VDC or 24 VAC
Power consumption
< 2 VA
Analog outputs
2 × 4-20 mA / 0-10 V, user settable
Outputs assignment
OUT1 2 gas; OUT2 2 gas
NOTE For LCD version only OUT1 is available.
Cable connections
screwless spring loaded terminals
Enclosure
grey ABS, wall or duct mount, protection class IP65
Dimensions
H82 × W80 × D55 mm
CE marking
according to 2014/30/EU and EN61326-1 requirements
Operating conditions
-20...+50 °C, 15...90 %RH, atmospheric pressure ±10%
non ATEXrated areas, non-aggressive atmosphere
NOTE The sensor may exhibit considerable sensitivity to
hydrogensulfide, nitrogen dioxidу and sulfur dioxide
LCD option
Operating temperature
0...+50 °C
Display dimensions
72 × 36 mm
Number of digits
3.5 7-segment
Character height
14 mm
Other features
Backlight
Other options
Remote probe
Protection IP65, default cable length 3.0 m;
max height 80 mm, max diameter 65 mm
Warranty
This product is warranted to be free from defects in material and workmanship for a
period of one year from the date of original sale. During this warranty period
Manufacturer will, at its option, either repair or replace product that proves to be
defective. This warranty is void if the product has been operated in conditions outside
ranges specified by Manufacturer or damaged by customer error or negligence or if
there has been an unauthorised modification.
Evikon MCI OÜ
Teaduspargi 7, Tartu
Tel. +372 733 6310
50411 Estonia
www.evikon.eu
PluraSens
®
Chlorine Transmitter
E2618-Cl2
User Manual