Electrical connections

Unscrew four lid screws and detach the lid from the device. Use the M16 cable gland to let
in cables of the power supply and of the external devices. Attach the power cable to the
device without turning it on. Using the connection diagram below, connect the analog
outputs and digital interface terminals to the relevant devices according to your tasks.

Version without PSU

Version with PSU

Jumpers

J1

OUT1 type (open: 4-20 mA; closed 0-10 V)

J2

OUT2 type (open: 4-20 mA; closed 0-10 V)

X6

Reset Modbus network parameters to default

X4 terminals

OUT1

4-20 mA / 0-10 V output

OUT2

4-20 mA / 0-10 V output

0V

0 V / 24 VAC Neutral (optional)

A

RS485 A / Data +

B

RS485 B / Data -

+U

+24 VDC / 24 VAC Phase (optional)

10

Содержание PluraSens E2608-ETO

Страница 1: ...PluraSens Ethylene Oxide Detector Transmitter E2608 ETO User Manual...

Страница 2: ...n 7 Mounting dimensions 8 Sensor probe handling 9 Gas sensor replacement procedures 9 Electrical connections 10 Operation 12 Maintenance 12 Calibration 12 Delivery set 13 Order code for E2608 ETO opti...

Страница 3: ...ical formula C2H4O Molar weight 44 Relative gas density to air 1 52 Conversion 1 ppm 1 80 mg m3 Boiling point 10 7 C Low explosive limit LEL vol in air 3 Upper explosive limit UEL vol in air 100 Odor...

Страница 4: ...s options Power consumption 2 VA Analog outputs 2 4 20 mA 0 10 V user settable Outputs assignment OUT1 Gas OUT2 Gas Output scale width 10 resolution Recommended 20 100 of the detection range Load resi...

Страница 5: ...9 1 1 atm explosion safe indoor areas non aggressive atmosphere NOTE The sensor may exhibit considerable sensitivity to carbon monoxide toluene and other organic compounds Other options Remote probe P...

Страница 6: ...o the safety provisions applicable in the country of use Do not perform any maintenance operation with the power on Do not let water or foreign objects inside the device Removal of the PCB from the en...

Страница 7: ...radius For early leakage detection install the sensor as close as possible to the potential leakage sources flanges valves pressure reducers pumps etc taking into consideration other points listed ab...

Страница 8: ...E2608 ETO Rev 05 05 2021 Mounting dimensions Wall mount version with mounting lugs Duct mount version 8...

Страница 9: ...ensor head cap and remove the old filter Place a new filter into the cap and tighten it again NOTE Never stab or press the filter near its center where the sensor is located since this may damage the...

Страница 10: ...connection diagram below connect the analog outputs and digital interface terminals to the relevant devices according to your tasks Version without PSU Version with PSU Jumpers J1 OUT1 type open 4 20...

Страница 11: ...A and B on the device represent DATA and DATA respectively polarity must be respected when connecting to an external RS485 network Both analog outputs can be independently changed between 4 20 mA and...

Страница 12: ...g the Modbus communication cycle Short on off pulses Normal operating measurement Continuously on or off Make sure that the detector transmitter is properly mounted the external devices connected powe...

Страница 13: ...rubber flange for Remote probe option Fixing clamp for Remote probe option Order code for E2608 ETO options E2608 options Order code Remote probe 3 m cable E2608 ETO RP33 3 Remote probe 10 m cable E26...

Страница 14: ...arameter Flexible setting of analog output scales for each output Output zero and slope adjustment for calibration Free assignment of each of two relays to the chosen parameter Several relay control l...

Страница 15: ...le registers 06 Write a single register Error codes 01 Illegal function 02 Illegal data address 03 Illegal data value 04 Slave device failure details of last error 04 can be read from register 0x0008...

Страница 16: ...dec Default 0x00A5 165 40166 RW Zero adjustment for gas data ADC 32000 32000 ADC units 0 0x00A6 166 40167 RW Slope adjustment for gas data 1 65535 512 0x00A7 167 40168 RW Change rate limit for gas da...

Страница 17: ...40217 RW Switching delay for relay RE2 0 1000 s 0 0x00D9 217 40218 RW Minimal on off time for relay RE1 0 1000 s 0 0x00DA 218 40219 RW Minimal on off time for relay RE2 0 1000 s 0 Address Reg MHR RW D...

Страница 18: ...ling off on analog output1 bit 3 0 1 in case the sensor is absent turn on signaling with low current high current on analog output1 if bit 2 0 this bit will be ignored bit 4 0 1 in case of sensor abse...

Страница 19: ...0107 263 40264 RW 0 value for analog output 2 32000 32000 gas units User defined 0x0108 264 40265 RW 100 value for analog output 2 32000 32000 gas units User defined The new value is applied after res...

Страница 20: ...manufacturer will at its option either repair or replace a product that proves to be defective This warranty is void if the product has been operated in conditions outside ranges specified by the Manu...