E2608-Cl2
Rev 05.05.2021
0x00DD
221 /
40222
RW
LOW setpoint for relay
RE1
0...65535 (gas units)
see
Specifications
0x00DE
222 /
40223
RW
HIGH setpoint for relay
RE1
0...65535 (gas units)
see
Specifications
0x00DF
223 /
40224
RW
LOW setpoint for relay
RE2
0...65535 (gas units)
see
Specifications
0x00E0
224 /
40225
RW
HIGH setpoint for relay
RE2
0...65535 (gas units)
see
Specifications
0x00FF
255 /
40256
RW
Sensor, analog outputs,
LED and buzzer status
bit[0]=0/1 – sensor
present/absent, RO
bit[1]=0/1 – analog outputs
deactivated/activated
bit[2]=0/1 – in case the
sensor is absent, turn
signaling off/on analog
output1
bit[3]=0/1 – in case the
sensor is absent, turn on
signaling with low
current/high current on
analog output1; if bit[2]=0
this bit will be ignored
bit[4]=0/1 – in case of
sensor absent, turn signaling
off/on analog output2
bit[5]=0/1 – in case of
sensor absent, turn on
signaling with low
current/high current on
analog output2; if bit[4]==0
this bit will be ignored
bit[6]=0/1 – current/voltage
output detected on output1,
RO
bit[7]=0/1 – current/voltage
output detected on output2,
RO
bit[8]=0/1 – LED
deactivated/activated
bit[9]=0/1 – buzzer
deactivated/activated
bit[10]=0/1 - LED is on/off in
normal condition
bit[11]=0/1 - 1 Hz (50% on,
50% off) LED signal off/on if
relay1 turned on
bit[12]=0/1 - 2 Hz (50% on,
user
defined
18