9 - forced Modbus control,
value set in MHR (4)0205

0x00CB

(4)0204 RW

Forced value for analog
output 1***

0...1000 (0.0%...100.0%  of
output scale)

0

0x00CC

(4)0205 RW

Forced value for analog
output 2***

0...1000 (0.0%...100.0%  of
output scale)

0

0x00FF

(4)0256 RW

Sensor and analog outputs
status

bit [0] = 0 / 1  - sensor present /
absent, read-only!
bit [1] = 0 / 1  - analog outputs
deactivated / activated
bit[2]= 0/1 - if the sensor is
absent, turn signaling off/on at
analog output 1,
bit[3]=0/1 - if the sensor is
absent, turn on signaling with
low current/high current on
analog output1; if bit[2]=0, this
bit will be ignored,
bit[4]=0/1 -if the sensor is
absent, turn signaling off/on at
analog output 2
bit[5]=0/1 - in case of sensor
absent, turn on signaling with
low current/high current at
analog output2; if bit[4]=0, this
bit will be ignored,
bit[6]=0/1 - output 1:
current/voltage output,
read-only!
bit[7]=0/1 - output 2:
current/voltage output,
read-only!
bit[8]=0/1 - LED
deactivated/activated,
bit[9]=0/1 - buzzer
deactivated/activated,
bit[10]=0/1 - LED on/off
(normal measurement)
Notes: LED/buzzer
signalization (if activated):

in case of detectable sensor

absence or malfunction -
0.5Hz (90% off, 10% on) light
and/or sound signal;

in case of Modbus response

the light signal is modulated
with short on-off pulses, even
single Modbus cycle is visible;

15

Содержание PluraSens E2218

Страница 1: ...PluraSens Humidity Temperature Transmitter E2218 User Manual...

Страница 2: ...5 Operating conditions 5 Installation and connections 6 Sensor probe handling 9 Delivery set 9 Order code for E2218 options 10 Emergency mode 11 Return to default settings 11 Modbus RTU Communication...

Страница 3: ...e Digital interface RS485 Modbus RTU protocol no galvanic isolation Cable connections Screwless spring loaded terminals Probe connector Round industrial M12 IP68 Standard probe HT RP16 grey painted al...

Страница 4: ...IP54 protection 0 100 RH 40 85 C Micro probe HT RP04 stainless steel body 4 50 mm IP54 protection 0 100 RH 40 85 C attached PVC insulated cable 2 or 5 m Heavy duty probe HT RP16 H black painted alumi...

Страница 5: ...d to the main unit using standard water and dustproof M12 connectors Two freely configurable 4 20 mA or 0 10 V analog outputs can be used to connect the transmitter to secondary instruments Each outpu...

Страница 6: ...ounting holes on the wall at the chosen mounting place see dimensional drawing Unscrew four lid screws and detach the lid from the instrument Fix the transmitter through mounting holes by screws Plug...

Страница 7: ...en 4 20 mA closed 0 10 V J2 OUT2 type open 4 20 mA closed 0 10 V X6 Reset Modbus network parameters to default X4 terminals OUT1 4 20 mA 0 10 V output OUT2 4 20 mA 0 10 V output 0V 0 V 24 VAC Neutral...

Страница 8: ...to connect the transmitter to the Fieldbus network polarity must be respected when connecting to an external RS485 network Overall length of all connections via RS485 interface should not exceed 1200...

Страница 9: ...to snap into the groove Note Never stab or press the filter near its center where the sensor is located as this may damage the sensor Do not remove the filter as it may cause the device to show incor...

Страница 10: ...stem 15 L200 mm 40 85 C E2218 DM With remote probe PVC cable 2 5 m 40 85 C E2218 RP16 2 With remote probe PVC cable 5 0 m 40 85 C E2218 RP16 5 With micro remote probe 4 50 mm 2 5 m PVC cable 40 85 C E...

Страница 11: ...ection with the sensor is lost The signal may be set to 3 8 mA or 21 5 mA Return to default settings To reset the device s Slave ID baud rate and stop bit number to factory settings proceed as follows...

Страница 12: ...ity bit 1 2 3 4 default 1 17 RW write 42330 to restart 168 RW integrating time constant 0 32000 s 201 RW OUT1 parameter 0 none 1 T 2 RH 202 RW OUT2 parameter 0 none 1 T 2 RH 258 R temperature C 100 si...

Страница 13: ...rs Reg are shown in hexadecimal 0 based format Modbus holding register numbers MHR are shown in decimal 1 based format and may be addressed either from 00001 or 40001 base Reg hex MHR dec RW Descripti...

Страница 14: ...Zero adjustment for humidity data RH 100 32000 32000 320 00 320 00 RH 0 0x00A6 4 0167 RW Slope adjustment for humidity data 1000 32000 32000 32 000 32 000 0 0x00A7 4 0168 RW Change rate limit for hum...

Страница 15: ...log output1 if bit 2 0 this bit will be ignored bit 4 0 1 if the sensor is absent turn signaling off on at analog output 2 bit 5 0 1 in case of sensor absent turn on signaling with low current high cu...

Страница 16: ...signed integer 1000 1000 1000 1000 C RH 100 0x0107 4 0264 RW 0 value for analog output 2 C RH g m3 signed integer 1000 1000 1000 1000 C RH 0 0x0108 4 0265 RW 100 value for analog output 2 C RH g m3 s...

Страница 17: ...nufacturer will at its option either repair or replace a product that proves to be defective This warranty is void if the product has been operated in conditions outside ranges specified by the Manufa...

Отзывы: