Modbus RTU Communication

RS485 communication interface

Databits: 8
Parity: none / odd / even
Stop bits: 1 or 2
Protocol: Modbus RTU

Supported Modbus functions:
03 – Read multiple registers
06 – Write a single register

Communication parameters

Parameter

Permitted values

Default

Supported baud rates 1200, 2400, 4800, 9600, 19200, 38400, 57600

9600

Data bits

8

8

Parity

none / odd / even

none

Stop bits

1, 2

1

Protocol

Modbus RTU

Modbus functions

03 - Read multiple registers
06 - Write a single register

Error codes

01 – Illegal function
02 – Illegal data address
03 – Illegal data value
04 – Slave device failure

(details of last error 04 can be read from register 0x0008)

Modbus holding registers

Register addresses are shown 0-based, Address in hexadecimal, Reg in decimal format.
Modbus holding register numbers MHR are shown in the decimal 1-based format and may
be addressed either from 00001 or 40001 base.

Address Reg / MHR RW Description

Supported values (dec)

Default

0x0001

1 / 40002

R

Hardware version

-

0x0002

2 / 40003

R

Software version

-

0x0003

3 / 40004

R

Product serial number

1...65535

-

0x0004

4 / 40005 RW Slave ID (net address) *

1...247 **

1

16

Содержание E2638-H2S

Страница 1: ...PluraSens Hydrogen Sulfide Detector Transmitter E2638 H2S User Manual...

Страница 2: ...dling 9 Gas sensor replacement procedures 9 Electrical connections 10 Correct and incorrect cabling for 24 VAC 12 Operation 13 Maintenance 13 Calibration 13 Delivery set 14 Order code for E2638 H2S op...

Страница 3: ...described as sweet or sickeningly sweet Odor threshold 0 01 1 5 ppm Note Sense of smell becomes rapidly fatigued and can NOT be relied upon to warn of the continuous presence of H2S Hazards Highly fl...

Страница 4: ...kOhm for 0 10 V mode Digital interface RS485 Modbus RTU protocol No galvanic isolation Enclosure Grey ABS wall mount protection class IP65 Dimensions H90 W145 D55 mm overall dimensions H140 W145 D55...

Страница 5: ...termined by user within 5 95 of the range Signaling options Visual Red and green LEDs Acoustic alarm Buzzer 85 dB LCD indicator option Operating temperature 0 50 C Display dimensions 72 36 mm Number o...

Страница 6: ...power supply module LCD indicator Remote probe The version of your device is marked on the package If the symbol is marked on the equipment consult the documentation for further information Safety req...

Страница 7: ...ties of the space under investigation room geometry direction and velocity of airflows etc Hydrogen sulfide is slightly heavier than air and spreads evenly in the room The recommended location is clos...

Страница 8: ...E2638 H2S Rev 21 06 2021 Mounting dimensions Front view Bottom view 8...

Страница 9: ...old filter Place a new filter into the cap and tighten it again NOTE Never stab or press the filter near its center where the sensor is located since this may damage the sensor Do not remove the filt...

Страница 10: ...er supply and of the external devices Without turning on the power plug the power cable and connect the analog relay outputs and or digital interface terminals to the necessary devices according to th...

Страница 11: ...wide range of wires with a cross section of 0 2 1 5 mm2 We recommend striping the wire end by 8 9 mm and using wire end sleeves To connect the wire insert the wire end into the terminal hole To disco...

Страница 12: ...he Specifications table To power the instrument from an external power source connect terminals 0V and U to the source If the integrated mains power supply module is used connect terminals L and N to...

Страница 13: ...off pulses Normal operating measurement Continuously on or off Make sure that the detector transmitter is properly mounted the external devices connected power LED green on and control LED red constan...

Страница 14: ...0 Duct mount option stem 35 L230 mm E2638 H2S DM Integrated 24 VAC power supply module E2638 H2S 24VAC Integrated 90 265 V mains power supply module E2638 H2S 230 Local LCD single value display 36 mm...

Страница 15: ...xible setting of analog output scales for each output Output zero and slope adjustment for calibration Free assignment of each of two relays to the chosen parameter Several relay control logic modes S...

Страница 16: ...le registers 06 Write a single register Error codes 01 Illegal function 02 Illegal data address 03 Illegal data value 04 Slave device failure details of last error 04 can be read from register 0x0008...

Страница 17: ...W Zero adjustments for gas data ADC 32000 32000 ADC units 0 0x00A6 166 40167 RW Slope adjustment for gas data 1 65535 512 0x00A7 167 40168 RW Change rate limit for gas units s 1 32000 0 no limit 0 0x0...

Страница 18: ...40215 RW Forced state for relay RE2 0 off 1 on 0 0x00D7 215 40216 RW Switching delay for relay RE1 0 1000 s 0 0x00D8 216 40217 RW Switching delay for relay RE2 0 1000 s 0 0x00D9 217 40218 RW Minimal o...

Страница 19: ...5535 gas units see Specifications 0x00FF 255 40256 RW Sensor analog outputs LED and buzzer status bit 0 0 1 sensor present absent RO bit 1 0 1 analog outputs deactivated activated bit 2 0 1 in case th...

Страница 20: ...put 1 32000 32000 gas units User defined 0x0106 262 40263 RW 100 value for analog output 1 32000 32000 gas units User defined 0x0107 263 40264 RW 0 value for analog output 2 32000 32000 gas units User...

Страница 21: ...Manufacturer will at its option either repair or replace a product that proves to be defective This warranty is void if the product has been operated in conditions outside ranges specified by the Manu...

Отзывы: